Carrier RG10 Series Manual Download Page 7

RG-10:Service Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

7

12

Pr

Indoor fan speed

SERVICE AND 

INQUIRY

Change the heating frequency lower limit 

selection.

Displays “

Ch

”. Press 

OK

 to return the current 

heating minimum frequency limit selection 

code. Press 

UP

 and 

DOWN

 to select the 

minimum heating frequency limit value. Press 

OK

 to confirm.

13

Lr

Electronic 

Expansion Valve 

(EEV) opening

SERVICE AND 

INQUIRY

Change the maximum operating frequency of 
T4 Cooling Only intervals.

Displays “

Ch

”. Press 

OK

 to return the current 

operating frequency code of the T4 Cooling 
Only intervals. Press 

UP

 or 

DOWN

 to select the 

limit value and then press 

OK

.

14

ir

Indoor fan speed

INQUIRY ONLY

Multiple the display number by 8 to 

calculate the actual RPM

15

HU

Relative Humidity

INQUIRY ONLY

Available in INQUIRY mode for the high 

tier/new mid tier units that have an RH 

sensor.

16

TT

Setpoint 

compensation 

temperature

INQUIRY ONLY

17

dT

Dust 

concentration 

(not used)

INQUIRY ONLY

18

WIFI

Wi-Fi signal 

strength

INQUIRY ONLY

The value is measured in 

dBm

. The 

display values are 0, 1, 2, 3 and 4 (4 is the 

highest and 0 is the lowest)

19

----

Not available

SERVICE ONLY

Change the cooling frequency upper limit 
selection in Hz.

Displays 

“Ch”

. Press 

OK

 to return the current 

frequency limit. Press 

UP

 or 

DOWN

 to select 

the preferred frequency upper limit value (in 
Hz). Press 

OK

 to confirm.

For example, the unit may be factory set to 
fluctuate between 40 and 84 Hz. If set to 
50, the unit will now be limited to operating 
between 40 and 50 Hz.

20

oT

Indoor fan target 

frequency

SERVICE AND 

INQUIRY

Change the heating frequency upper limit 
selection in Hz.

Displays “

Ch

”; press 

OK

 to return the current 

frequency limit. Press 

UP

 or 

DOWN

 to select 

the preferred frequency upper limit value (in 
Hz). Press 

OK

 to confirm.

For example, the unit may be factory set to 
fluctuate between 40 and 84 Hz. If set to 
50, the unit is limited to operating between 
40 and 50 Hz.

21

----

Cooling 

Temperature 

Compensation

SERVICE ONLY

Change the cooling temperature compensation 
value.

Displays “

Ch

”. Press 

OK

 to return the current 

temperature compensation value code. Press 

UP

 or 

DOWN

 to select the cooling temperature 

difference compensation value. 
Press 

OK

 to confirm.

This setting is used to adjust for 
temperature differences due to the height 
of the unit install. The offset value can be 
set at a range of -6° to +6°. 

22

----

Heating 

Temperature 

Compensation

SERVICE ONLY

Change the heating temperature compensation 
value.

Displays “

Ch

”. Press 

OK

 to return the current 

temperature compensation value code. Press 

UP

 or 

DOWN

 to select the heating temperature 

difference compensation value. 
Press 

OK

 to confirm.

This setting is used to adjust for 
temperature differences due to the height 
of unit installation. The offset value can be 
set at a range of -6° to +6°. 

23

----

Maximum Cooling 

Fan Speed

SERVICE ONLY

Change the maximum cooling fan speed setting 
as it relates to RPM.

Displays “

Ch

”. Press 

OK

 to return the current 

maximum cooling fan speed setting. Press 

UP

 

or 

DOWN

 to select the maximum cooling fan 

speed. Press 

OK

 to confirm.

For example, the unit may be factory set to 
fluctuate between 300 and 1000 RPM. If 
set to 800, the unit is limited to operating 
between 300 and 800 RPM.

 (Sheet 2 of 3)

CODE INQUIRY

INQUIRY 

DESCRIPTION

SERVICE/

INQUIRY

FOR SERVICE,

 PRESS ON/OFF FOR 2 SECONDS TO:

SELECTION GUIDE/NOTES

Summary of Contents for RG10 Series

Page 1: ...his service manual provides the necessary information to use the service functions on the RG10 series wireless remote controller Use the TABLE OF CONTENTS to locate a desired topic Fig 1 RG10A B2S BGE...

Page 2: ...ies in the remote controller if the remote is not going to be used for 2 or 3 months Dispose old batteries in the appropriate recycle bins Fig 7 Remove the back cover Remote Controller Specification T...

Page 3: ...llowing is a brief introduction of the remote controller Fig 8 Remote Controller NOTE To alternate between C and F buttons must be pressed gently otherwise the remote will not recognize the command Tu...

Page 4: ...es the right to change at any time specifications and designs without notice and without obligations 4 REMOTE CONTROLLERS Fig 9 RG10A B2S BGEFU1 Fig 10 RG10B B1 BGEFU1 Fig 11 RG10A5 B1 BGCEFU1 Fig 12...

Page 5: ...ng the batteries use UP or DOWN to scroll through the INQUIRY modes d To enter the SERVICE mode for an applicable INQUIRY mode press ON OFF for 2 seconds e After SERVICE adjustments have been made pre...

Page 6: ...un time of 50 mins 11 Terminate after run time of 60 mins 3 T3 Outdoor Coil Temperature SERVICE AND INQUIRY Change the option to control the COOLING and HEATING modes available for use on the unit Pre...

Page 7: ...fan target frequency SERVICE AND INQUIRY Change the heating frequency upper limit selection in Hz Displays Ch press OK to return the current frequency limit Press UP or DOWN to select the preferred f...

Page 8: ...ting as it relates to RPM Displays Ch Press OK to return the current maximum heating fan speed setting Press UP or DOWN to select the maximum heating fan speed Press OK to confirm For example the unit...

Reviews: