5.7 - Condenser water flow rates
30hZ/hZV Passes
Minimum flow rate, l/s*
Maximum flow rate, l/s**
Closed loop Open loop
043
2
1.20
3.60
14.80
052
2
1.20
3.60
14.80
065
2
1.40
4.20
17.00
091
2
2.47
7.42
30.00
101
2
2.60
7.64
31.00
111
2
3.04
9.13
37.00
121
2
3.54
10.62
43.00
141
2
3.54
10.62
43.00
161
2
3.54
10.62
43.00
195
2
4.00
12.00
48.00
225
2
4.46
13.40
54.00
250
2
5.04
15.14
61.00
280
2
5.62
16.88
68.00
* Based on a water velocity of 0.3 m/s in closed-loop and 0.9 m/s in open-loop
systems.
** Based on a water velocity of 3.6 m/s.
legend
1 30HZ/HZV 043-052
2 30HZ/HZV 065
3 30HZ/HZV 091
4 30HZ/HZV 101
5 30HZ/HZV 111
6 30HZ/HZV 121-141
7 30HZ/HZV 161
8 30HZ/HZV 195
9 30HZ/HZV 225
10 30HZ/HZV 250
11 30HZ/HZV 280
Pressure drop, kPa
Water flow rate, l/s
Condenser pressure drop curves, standard units
5.8 - Condenser water flow restrictor
CAUTION: To ensure correct operation of the units, these
restrictors must be installed. The restrictor is supplied with
the machine, inside the control box.
30hZ/hZV Passes* OD, mm location
043
2
31
Condenser 09RS 022 circuit B - water outlet
091
2
47
Condenser 09RS 054 - water outlet
111
2
47
Condenser 09RS 054 - water outlet
195
2
47
Condenser 09RS 070 - water outlet
250
2
56
Condenser 09RS 084 - water outlet
* No. of passes
1
2
3
9
4 5 6
7 8
10
11
1
10
100
1
10
100