4–59
T-362
Figure 4.11 DataCorder Probe Calibration Screen
e. Using the System Tools screen (see
) in the DataLine software perform a “Trip Start.”
Figure 4.12 DataCorder Systems Tool Screen
4.6.9
ISO Trip Header
DataLINE provides the user with an interface to view/ modify current settings of the ISO trip header through the
ISO Trip Header screen.
The ISO Trip Header screen is displayed when the user clicks on the “ISO Trip Header” button in the “Trip
Functions” Group Box on the System Tools screen.
F9 function - Provides the user with a shortcut for manually triggering the refresh operation. Before sending
modified parameter values, the user must ensure that a successful connection is established with the controller.
If the connection is established with the DataCORDER, the current contents of the ISO Trip Header from the
DataCORDER will be displayed in each field. If the connection is not established with the DataCORDER, all fields
on the screen will be displayed as “Xs.” If at any time during the display of the ISO Trip Header screen the
connection is not established or is lost, the user is alerted to the status of the connection.
After modifying the values and ensuring a successful connection has been made with the DataCORDER, click on
the “Send” button to send the modified parameter values.
The maximum allowed length of the ISO Trip Header is 128 characters. If the user tries to refresh the screen or
close the utility without sending the changes made on the screen to the DataCORDER, the user is alerted with a
message.