5–5
T-362
5.5 Connect Remote Monitoring Receptacle
If remote monitoring is required, connect the remote monitor plug at the unit receptacle (see
).
When the remote monitor plug is connected to the remote monitoring receptacle, the following remote circuits are
energized:
• Sockets B to A: Energizes remote cool light
• Sockets C to A: Energizes remote defrost light
• Sockets D to A: Energizes remote in-range light
5.6 Starting and Stopping Instructions
WARNING
!
Make sure that the unit circuit breaker(s) CB-1 & CB-2 and the Start-Stop switch (ST) are in the
“O” (OFF) position before connecting to any electrical power source.
NOTE
The electronic phase detection system will check for proper compressor rotation within the first 30 sec
-
onds. If rotation is not correct, the compressor will be stopped and restarted in the opposite direction.
If the compressor is producing unusually loud and continuous noise after the first 30 seconds of oper
-
ation, stop the unit and investigate.
5.6.1
Starting the Unit
1. Verify that power is properly applied, the fresh air vent is in proper position, and (if required) the water-
cooled condenser is connected.
2. Place the Start-Stop switch (ST) to position “I” (ON) (see
). The controller function codes for the
container ID (Cd40), software version (Cd18) and unit model number (Cd20) will be displayed in sequence.
3. Continue with the Start Up Inspection. See
.
5.6.2
Stopping the Unit
1. To stop the unit, place the Start-Stop switch (ST) in position “0” (OFF).
5.7 Start-Up Inspection
5.7.1
Physical Inspection
Check rotation of condenser fan and evaporator fans.
5.7.2
Check Controller Function Codes
Check, and if required, adjust controller function codes (Cd27 through Cd37) in accordance with desired operating
.
5.7.3
Start Temperature Recorder
1. Check and, if required, set the DataCORDER Configuration in accordance with desired recording
parameter. See
.
2. Enter a “Trip Start” with the following instructions:
a. Press the ALT MODE key. When the left display shows “dC”, press the ENTER key.
b. Scroll to code dC30.
c. Press and hold the ENTER key for five seconds.
d. The “Trip Start” event will be entered in the DataCORDER.
5.7.4
Complete Inspection
Allow the unit to run for five minutes to stabilize conditions, and then perform a pre-trip diagnosis in accordance
with