
11
Table 2 – Cooling Tonnage vs. Airflow (CFM)
AIR CONDITIONING TONS
(12,000 BTU/HR)
AIRFLOW (CFM)
040, 060, &
3T---080 MODEL
5T---080 & 100
MODEL
120 MODEL
1---1/2
525
X
2
700
X
X
X
2---1/2
875
X
X
X
3
1050
X
X
X
3---1/2
1225
X
X
X
4
1400
X
X
5
1750
X
X
6
2100
X
525
2
700
2
700
875 1050
875
700
875
2
1050
1050
1
1225
1225
1225
1400
1400
1225
1750
1
1750
1
1225
1750
2100
DEF.
DEF.
DEF.
040, 060, 3T-080
5T-080, 100
120
BASED ON 350 CFM/TON (SETUP SWITCH SW1-5 OFF)
SETUP SWITCH SW2/SW3 POSITIONS
MODEL
SIZE
600
2
800
2
800
1000 1200
1000
800 1000
2
1200
1200
1
1400
1400
1400
1600
1600
1400
2000
1
2000
1
1400
2000
2100
DEF.
DEF.
DEF.
040, 060, 3T-080
5T-080, 100
120
BASED ON 400 CFM/TON (SETUP SWITCH SW1-5 ON)
1. DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION
2. DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
3. SWITCH POSITIONS ARE ALSO SHOWN ON FURNACE WIRING DIAGRAM
SETUP SWITCH SW2/SW3 POSITIONS
MODEL
SIZE
A10472
Air Conditioning or Continuous Fan Airflow Selection Chart
HIGH HEAT TEMPERATURE RISE TOO LOW -- Generally, this indicates the HI solenoid
in gas valve GV has failed or the furnace is extremely underfired.
STEP
ACTION
YES
NO
GO TO
1.
Remove the blower access panel. Disconnect the R thermostat lead from the furnace con-
trol board. If setup switch SW1--2 is ON then set it to OFF.
2
2.
Depress the door switch. Use piece of tape to hold it closed.
3
3.
Jumper R and W/W1 thermostat terminals.
4
4.
When the furnace is running in low heat, clock the low heat gas rate. You have 16 minutes
on this first call for heat before unit switches to high heat. On propane installations check
the manifold pressure.
5
5.
When the furnace is running in high heat, clock the high heat gas rate. On propane installa-
tions check the manifold pressure.
6
6.
Is the high heat rate approximately the same as the low heat rate?
7
11
7.
Do you have 24 vac across gas valve terminals HI and C
OM--24
V on 2--stage gas valve dur-
ing high heat?
10
8
8.
You have an open wire or bad terminal on the BROWN wire from the high heat pressure
switch HPS to the gas valve GV. Repair it or replace the harness.
9
9.
Go to the page number indicated in Index for the CLEANUP AND STARTUP INSTRUC-
TIONS.
INDEX
10.
Replace the gas valve.
9
11.
Is the high heat rate within 2% of that specified on the rating plate?
13
12