MAXIMUM EQUIVALENT VENT LENGTH -- FT. (M) (CONTINUED)

Table 2 – Deductions from Maximum Equivalent Vent Length -- Ft. (M)

Pipe Diameter (in):

1-1/2

2

2-1/2

3

4

Mitered 90º Elbow

8

(2.4)

8

(2.4)

8

(2.4)

8

(2.4)

8

(2.4)

Medium Radius 90º Elbow

5

(1.5)

5

(1.5)

5

(1.5)

5

(1.5)

5

(1.5)

Long Radius 90º Elbow

3

(0.9)

3

(0.9)

3

(0.9)

3

(0.9)

3

(0.9)

Mitered 45º Elbow

4

(1.2)

4

(1.2)

4

(1.2)

4

(1.2)

4

(1.2)

Medium Radius 45º Elbow

2.5

(0.8)

2.5

(0.8)

2.5

(0.8)

2.5

(0.8)

2.5

(0.8)

Long Radius 45º Elbow

1.5

(0.5)

1.5

(0.5)

1.5

(0.5)

1.5

(0.5)

1.5

(0.5)

Tee

16

(4.9)

16

(4.9)

16

(4.9)

16

(4.9)

16

(4.9)

Concentric Vent Termination

NA

0

(0.0)

NA

0

(0.0)

NA

Standard Vent Termination

0

(0.0)

0

(0.0)

0

(0.0)

0

(0.0)

0

(0.0)

Venting System Length Calculations

The maximum length for each vent pipe (inlet or exhaust) equals the Maximum Equivalent Vent Length (MEVL) from Table 1 or Table 3
minus the number of elbows multiplied by the deduction for each elbow in Table 2.
Standard vent terminations and concentric vent terminations count for zero deductions.
See Vent Manufacturers’ data for equivalent lengths of flexible vent piping.
DO NOT ASSUME that one foot of flexible vent pipe is equivalent to one foot of standard PVC vent pipe.

Example

A direct--vent 60,000 Btuh furnace installed at 2100 ft. (640 M) with 2--in.(51 mm) vent piping. Venting system includes,

FOR EACH

PIPE

, (3) 90

_

long radius elbows, (2) 45

_

long radius elbows and a concentric vent kit.

Maximum Equivalent Vent Length

=

127 ft.

(From Table 1)

Deduct (3) 90 long radius

3

x

3 ft.

=

- 9 ft.

(From Table 2)

Deduct (2) 45 long radius

2

x

1.5 ft.

=

- 3 ft.

(From Table 2)

No deduction for Concentric Vent Kit

0 ft.

=

- 0 ft.

(From Table 2)

Maximum Vent Length

=

115 ft.

For

EACH

vent or inlet pipe

59TP5A

Summary of Contents for Performance 59TP5A Series

Page 1: ...y levels in the home when used with a compatible humidity control system S ComfortFan technology allows control of continuous fan speed from a compatible thermostat S Ideal height 35 889 mm cabinet sh...

Page 2: ...ogy leadership and innovation in providing a reliable and durable product Performancet ECM Blower Motor This basic ECM or electronically commutated motor can provide an efficiency enhancement for sele...

Page 3: ...Air Filtration System Factory Supplied Media Cabinet Field Supplied Filter Filter Used for Certified Watt Data KGAWF1606UFR KGAWF1306UFR KGAWF1306UFR KGAWF1406UFR KGAWF1406UFR KGAWF1506UFR Electrical...

Page 4: ...w 15 16 040 40 000 BTU 060 60 000 BTU 080 80 000 BTU 100 100 000 BTU 120 120 000 BTU Not all familes have these models A11158 FURNACE COMPONENTS RATING PLATE NOT SHOWN LOCATED ON BLOWER DOOR GAS VALVE...

Page 5: ...3 Last 2 digits of Part Number indicate filter size 4 Last 2 digits of Part Number indicate orifice size 5 Choose IAQ filter assembly appropriate for the designed system airflow and static pressure Us...

Page 6: ...195 2110 2030 1935 1835 1725 1605 Yellow 1950 1900 1855 1800 1755 1705 1655 1605 1560 1485 Blue 1750 1700 1650 1605 1555 1500 1455 1395 1350 1300 Orange 1570 1520 1460 1410 1350 1300 1240 1195 1140 10...

Page 7: ...0 32 0 30 0 22 0 11 0 20 0 70 0 104 0 87 0 67 0 20 0 70 0 124 0 104 0 82 0 M 6 1 9 8 9 1 6 7 3 4 6 1 21 3 31 7 26 5 20 4 6 1 21 3 37 8 31 7 25 0 20 30 Ft 20 0 17 0 14 0 6 0 0 0 20 0 70 0 71 0 57 0 40...

Page 8: ...5 13 7 198 60 4 232 70 7 NA NA 60 000 27 8 2 127 38 7 222 67 7 250 76 2 NA 80 000 17 5 2 64 19 5 165 50 3 222 67 7 249 75 9 100 000 NA 22 6 7 104 31 7 223 68 0 250 76 2 120 000 NA NA 11 3 4 93 28 3 23...

Page 9: ...uals the Maximum Equivalent Vent Length MEVL from Table 1 or Table 3 minus the number of elbows multiplied by the deduction for each elbow in Table 2 Standard vent terminations and concentric vent ter...

Page 10: ...63 19 2 8001 to 9000 2438 to 2743 40 000 10 3 0 121 36 9 130 39 6 NA NA 60 000 7 2 1 82 25 0 152 46 3 168 51 2 NA 80 000 NA 35 10 7 111 33 8 148 45 1 156 47 5 100 000 NA NA 67 20 4 157 47 9 170 51 8...

Page 11: ...at exchangers motors and controls 60 80 27 C 16 C SUPPLY AIR A10490 MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS POSITION CLEARANCE Rear 0 0 mm Front Combustion air openings in furnace and in structure...

Page 12: ...Coil Assembly or Coil Box 22 1 8 562 0 19 482 6 23 3 4 603 3 20 3 8 517 5 1 The plenum should be constructed 1 4 in 6 mm smaller in width and depth than the plenum dimensions shown above Concentric Ve...

Page 13: ...BLOCK THREE WIRE HEATING ONLY FIVE WIRE NOTE 2 NOTE 1 1 STAGE THERMOSTAT TERMINALS FIELD SUPPLIED FUSED DISCONNECT CONDENSING UNIT FURNACE COM R W C Y R G GND GND FIELD 24 VOLT WIRING FIELD 115 208 2...

Page 14: ...14 DIMENSIONAL DRAWING A11590 59TP5A...

Page 15: ...__________ Media Filter Casing Casing shall be of 030 in thickness minimum pre painted galvanized steel Draft Inducer Motor Draft inducer motor shall be two speed design Primary Heat Exchangers Primar...

Page 16: ...Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 01 12 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No...

Reviews: