Appendix A:  VVT Bypass Controller Points/Properties 

 

 

VVT Bypass Controller 

Carrier Proprietary and Confidential 

CARRIER CORPORATION ©2017   

Installation and Start-up Guide 

 

All rights reserved 

 

31 

 

Point Name/Description

 

Default/Range

 

 

Test and Balance

 

Zero Cal

 – Closes the bypass damper and waits for the air source to go to the 

Off mode before zeroing out the static pressure sensor. This does not occur if 

the static pressure is > .05 in. H

2

O (.0125 kPa) . 

Pressure Sensor Cal

 – Allows you to calibrate the pressure sensor after the 

Zero Cal has been performed. To enter a value here, neither the damper nor 

the pressure sensor can be locked, the bypass cannot be in LAT mode and the 

damper position must be >0% and <100%. The value entered will be the actual 

static pressure measured with an accurate static pressure measuring device. 

Damper Full Open

 – Overrides the damper to its full open position. 

Automatic Control

 – Returns the damper to its normal control routines. 

This 

must be activated when you finish using any of the other Test and Balance 

commands.

 

Damper Full Close

 – Overrides the damper to its full closed position. 

 

 
 

  

Local Sensor Calibration

 

 

 

Supply Air Temperature

 – Displays the current supply air temperature. 

R:  -56 to 245°F 

(-48.9 to 118.3°C) 

Supply Air Temp Calibration

 – A calibration offset value to allow the supply air 

temperature sensor to be adjusted to match a calibrated standard measuring the 

temperature in the same location. 

R:  -20 to 20 °F 

(-11.1 to 11.1 °C) 

 
 

 

Maintenance 

 

Navigation:

 

i-Vu® / Field Assistant: 

Properties 

Control Program 

Maintenance

 

   

Point Name/Description

 

Range

 

Static Pressure 

– The current supply duct static pressure. 

R: 

0 to 2.0 in. H

2

(0 to .498 kPa 

Controlling Pressure Setpoint

 – The active static pressure setpoint that the bypass 

controls to. 

R: 

.1 to 2.0 in. H

2

(.025 to .498 kPa) 

Max Duct Pressure Setpoint

 – The Pressure Control Deadband that is added to the 

active static pressure setpoint. 

R: 

0 to 2.0 in. H

2

(0 to .498 kPa 

Min Duct Pressure Setpoint

 – The Pressure Control Deadband that is subtracted from 

the active static pressure setpoint. 

R: 

0 to 2.0 in. H

2

(0 to .498 kPa 

 
 

 

Summary of Contents for OPN-VVTBP

Page 1: ...t tr ro ol ll le er r I In ns st ta al ll la at ti io on n a an nd d S St ta ar rt t u up p G Gu ui id de e CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol...

Page 2: ...ur local Carrier office Important changes are listed in Document revision history at the end of this document CARRIER CORPORATION 2017 All rights reserved throughout the world i Vu is a registered tra...

Page 3: ...Wiring and mounting the Equipment Touch 15 Start up 17 Configuring the VVT Bypass Controller s properties 17 Performing system checkout 18 Bypass damper 18 Variable frequency drive VFD 19 Sequence of...

Page 4: ......

Page 5: ...e actuator Or the controller can drive multiple external damper actuators The air source supply fan s variable frequency drive VFD NOTE The VVT Bypass Controller controller is available in both Englis...

Page 6: ...er Carrier Proprietary and Confidential CARRIER CORPORATION 2017 Installation and Start up Guide All rights reserved 2 NOTE This document gives instructions for field installation of a VVT Bypass Cont...

Page 7: ...to 5 of full flow at 2 in H20 498 kPa Integral actuator Brushless DC motor torque 35 inch pounds 4 Nm runtime 205 seconds for 90 degree travel during control or 25 seconds in high speed test and bala...

Page 8: ...7 lbs 0 77 kg BACnet support Conforms to the BACnet Advanced Application Controller B AAC Standard Device Profile as defined in ANSI ASHRAE Standard 135 2012 BACnet Annex L Protocol Revision 9 Listed...

Page 9: ...hock Hazard Failure to follow this warning could cause personal injury death and or equipment damage Disconnect all power to the unit before performing maintenance or service Unit may automatically st...

Page 10: ...atic pressure probe To install the VVT Bypass Controller 1 Mount the controller page 7 2 Wire the controller for power page 9 3 Set the controller s address page 10 4 Wire the controller to the BACnet...

Page 11: ...of the controller and adjacent surfaces End view inlet Controller Allow 1 ft 3 m clearance for service access 2 5 in 6 35 cm To mount the controller 1 Turn the damper shaft to fully close the damper...

Page 12: ...actuator s fully open position a Loosen the appropriate stop clamp screw See figure below b Move the stop clamp until it contacts the edge of the actuator cam c Tighten the screw Move stop clamp if ne...

Page 13: ...nals CAUTIONS The VVT Bypass Controller is powered by a Class 2 power source Take appropriate isolation measures when mounting it in a control panel where non Class 2 circuits are present Carrier cont...

Page 14: ...e VVT Bypass Controller has been wired for power pull the screw terminal connector from the controller s power terminals labeled Gnd and 24 Vac The controller reads the address each time you apply pow...

Page 15: ...nds 3 Connect the communications wiring to the controller s screw terminals labeled Net Net and Shield NOTE Use the same polarity throughout the network segment 4 Set the communication type and baud r...

Page 16: ...jacket of the cable Do not pull or draw cable with a force that may harm the physical or electrical properties Avoid splices in any control wiring Wiring a Duct Air Temperature sensor to an input Part...

Page 17: ...high torque actuator or parallel actuators to the controller s 0 10 Vdc analog output NOTE You cannot use the VVT Bypass Controller s built in actuator if wiring external actuator s to the analog outp...

Page 18: ...can wire up to 4 of the following Belimo actuators to the VVT Bypass Controller s analog output Link actuators whose travel times and other parameters coincide LMX24 MFT P 10028 45 in lb 5 Nm actuato...

Page 19: ...or Wiring and mounting the Equipment Touch CAUTION If the equipment is used in a manner not specified by the manufacturer the protection provided by the equipment may be impaired See the Equipment Tou...

Page 20: ...ier part number 33ZCT55SPT to the Equipment Touch Wire the Equipment Touch directly to the controller s Rnet port as shown below 1 Turn off the VVT Bypass Controller s power 2 Partially cut then bend...

Page 21: ...Touch Installation and Setup Guide for detailed instructions CAUTION If multiple controllers share power but polarity was not maintained when they were wired the difference between the controller s gr...

Page 22: ...hen verify that the damper is fully closed d Click Damper Full Open then verify that the damper is fully open e Click Zero Cal to close the bypass damper and zero the pressure sensor When Done appears...

Page 23: ...ass damper Then verify that the low pressure connector is not blocked 5 Calibrate the VFD and pressure sensor a Disable the air source heating cooling and fan outputs using one of the following method...

Page 24: ...the measured value next to the button then click Apply j Remove the magnehelic gauge from the High connector then reinsert the pressure tubing k Click Automatic Control to return the bypass to normal...

Page 25: ...is in either of the following modes Fire shutdown or evacuation mode The bypass damper will be fully open If controlling a VFD the VFD output will be at 0 Pressurization mode The bypass damper will b...

Page 26: ...ly closed or VFD is commanded to maximum speed after 1 minute the controller assumes that the equipment fan turned off The bypass damper then modulates to 65 open and the VFD speed is commanded to 35...

Page 27: ...r source fan is on and providing cooling using only the economizer and usually during an unoccupied period The terminal modulates its primary air damper to maintain the midpoint between the configured...

Page 28: ...ng data over the network segment CW The actuator motor is turning clockwise CCW The actuator motor is turning counterclockwise The Run and Error LED s indicate controller and network status If Run LED...

Page 29: ...ct the VVT Bypass Controller in the navigation tree 2 Right click and select Module Status To restore factory defaults CAUTION This erases all archived information and user configuration settings You...

Page 30: ...ttery s polarity 4 Insert the new battery matching the battery s polarity with the polarity indicated on the controller s cover 5 Replace the VVT Bypass Controller s cover 6 Download the VVT Bypass Co...

Page 31: ...or on a repair bench 1 Disconnect the High and Low flow sensor tubes 2 Insert the compressed air straw 1 4 into the controller s High connector High Low 3 Press the air can s trigger twice for no more...

Page 32: ...ion manual may cause harmful interference to radio communications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to c...

Page 33: ...current open damper position R 0 to 100 VFD output If Control Device Type is VFD this is the current VFD speed capacity R 0 to 100 LAT Control The status of LAT Limit duct static pressure override co...

Page 34: ...c pressure is greater than the controlling setpoint this value the output modulates accordingly CAUTION If this value is too low the damper may oscillate to maintain the static pressure This could cau...

Page 35: ...ntrol routines This must be activated when you finish using any of the other Test and Balance commands Damper Full Close Overrides the damper to its full closed position Local Sensor Calibration Suppl...

Page 36: ...Air Linkage Status If Active the controller is part of a linked system If Not Active the controller is operating as a stand alone device R Active Not Active Air Source Mode If Airside Linkage Status...

Page 37: ...CORPORATION 2017 Installation and Start up Guide All rights reserved 33 Point Name Description Range SAT Sensor The current duct air temperature sensor that is physically connected to the controller...

Page 38: ...for generating a particular mode Evacuation Shutdown changed to Evacuation C AE WB E Specifications Added ARC156 C D Cover What is the VVT Bypass Controller Updated picture C D 2 22 16 Start up Added...

Page 39: ......

Page 40: ...CARRIER CORPORATION 2017 A member of the United Technologies Corporation family Stock symbol UTX Catalog No 11 808 436 01 2 7 2017...

Reviews: