Appendix A: Network Points List for RTU Open
RTU Open v3
Carrier Proprietary and Confidential
CARRIER CORPORATION ©2016
Integration Guide
All rights reserved
35
Network points list for BACnet and Modbus
BACnet
Modbus
Point Name
Point
Access
Units
Default
Value
BACnet Point Name
BACnet Object
ID
Modbus Register Type Modbus
Register #
Active Heat
Stages
R
heat_run
AV:2003
Input Register (Float) 33
Effective Cool
Setpoint
R
°F
eff_cl_stpt
AV:3005
Input Register (Float) 55
High Space
Temperature
R
0=Normal
1=Alarm
spt_hi_alarm
BV:7011
Discrete Input
35
Low Space
Temperature
R
0=Normal
1=Alarm
spt_lo_alarm
BV:7012
Discrete Input
39
Input_6
R
°F
ai_6
AI:1006
Supply Fan Relay
State
R
0=Off
1=On
sfan
BV:2001
Discrete Input
23
Supply Fan Status R
0=Off
1=On
sfan_status
BV:1003
Discrete Input
24
Economizer
Output
R
%Open
econ_output
AV:2022
Input Register (Float) 51
Outdoor Air
Quality Sensor
R
0=Normal
1=Alarm
oaq_fail
BV:7006
Discrete Input
41
DCV Max Vent
Damper Pos
R/W
%Open
50
iaq_dpr_max
AV:9011
Holding Register
(Float)
47
Space
Temperature -
Prime Variable
R
°F
space_temp
AV:2007
Input Register (Float) 107
HP Rev Cycle
Lockout Temp
R/W
°F
-3
hp_rev_cycle_lockout
AV:9004
Holding Register
(Float)
71
System Outdoor
Air Temperature
R/W
°F
-999
system_oat
AV:1901
Holding Register
(Float)
119
Economizer Purge
Min Pos
R/W
%Open
40
econ_purge_min
AV:9029
Holding Register
(Float)
75
Active
Compressor
Stages
R
comp_run
AV:2020
Input Register (Float) 31
System Mode
R
1=Off
2=Fan Only
3=Economizer
Cooling
4=Cooling
5=Heating
6=Dehumidificati
on
7=Test
8=Shutdown
9=Unocc Free
Cooling
10=Fire
Shutdown
11=IAQ Override
12=Pre-occ Purge
run_status
MSV:2002
Input Register
(Signed)
1
Appendix A: Network Points List for RTU Open