Appendix B: The Chilled Water System Optimizer Commissioning view of the Properties page
Chilled Water System Optimizer v2
CARRIER CORPORATION ©2019
Installation and Start-up Guide
69
All rights reserved
Section 1 - Chilled Water System Optimizer - Enable conditions
Navigation:
i-Vu®
Properties
>
Control Program
>
Chilled Water Temperature Optimizer Reset
>
Section 1 - Chilled Water System Optimizer - Enable Conditions
Point Name/Description
Range
1. CHWS Optimizer ON Switch:
— Displays Disabled/Enabled status.
CAUTIONS
You must set this to
DISABLED
until the system is set up and ready to run.
The
Main ON Switch
in
Section 1 - Optimizer - Primary Enable Conditions
(page 60) must also be enabled for the CHWS Optimizer to be enabled.
D:
R:
DISABLED
DISABLED/ENABLED