Compressor Rotation
To determine whether or not compressor is rotating in the proper
direction:
1. Connect service gages to suction and discharge pressure
fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge pressure
should rise, as is normal on any start-up.
4. If the suction pressure does not drop and the discharge pres
-
sure does not rise to normal levels, the compressor may be
rotating in the wrong direction.
5. Since the compressor and fan motors are connected in phase
during production, it is likely that the evaporator and con
-
denser fans are probably also rotating in the wrong direction.
6. Turn off power to the unit, lock and tag disconnect per stan
-
dard safety procedures.
7. Reverse any two of the unit power leads.
8. Remove lock and tag per standard safety procedures and
reapply power to the unit.
9. The suction and discharge pressure levels should now move
to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direction,
the unit makes an elevated level of noise and does not provide
cooling.
Operating Sequence
All units require the addition of a thermostat accessory package to
complete the control circuit. The sequence of operation may vary
depending on which package is selected.
ROOM-MOUNTED THERMOSTAT
These units use an electronic thermostat mounted in the condi
-
tioned space.
FAN CIRCULATION
The indoor-fan motor is energized through G on the thermostat
and the indoor-fan contactor is energized. This starts the indoor-
fan motor (IFM). The fan will operate to provide continuous air
circulation.
COOLING
The indoor fan will operate continuously or when the compressor
runs, depending on the setting of the thermostat fan selector
switch. When the thermostat closes (on a call for cooling Y1 on
the thermostat), the control relay (CR), outdoor-fan contactor
(OFC) and compressor contactor(s) (C1 and C2 on 50XCR12-16
units) close. The control relay will start the indoor fan if it is not
already running. The compressor contactors will immediately start
the first stage compressor(s).
A second stage on 50XCR12-16 units will close if additional cool
-
ing demand is required, and will then start the second-stage com
-
pressor. When the thermostat is satisfied, the second stage com
-
pressor will stop first, and then the first stage compressors will
stop when cooling demand is satisfied.
2-SPEED FAN OPERATION SEQUENCE
On the VFD the following parameters must be set on each unit. To
change the parameters:
1. Press MENU.
2. Select Parameters.
3. Press ENTER.
4. Select sub-group (first two digits of the parameters).
5. Press SEL.
6. Select parameter.
7. Press EDIT.
8. Select the new value (see Table 12).
9. Press SAVE.
10. Select any other parameters of the group to change and go to
Step 7.
11. When complete, press EXIT.
12. Select any other parameter groups to change and go to Step 5.
13. When complete, press EXIT.
14. Press EXIT until the status menu is visible (HZ, PSI)
Table 12 —
VFD Parameters
On the VFD, the following parameters must be loaded from the
IFM-VFD configuration keypad. The parameter list is provided
should the keypad be damaged and the points loaded manually
(see Table 13). To download parameters from the configuration
keypad:
1. Press MENU.
2. Select PAR backup.
3. Press SEL.
4. Select download to drive ALL.
5. Press SEL.
6. When download is complete press SEL.
Table 13 —
IFM - VFD Parameters
Should it be necessary to upload data to the configuration keypad:
1. Press MENU.
2. Select PAR backup.
3. Press SEL.
4. Select upload to panel.
5. Press SEL.
6. When download is complete, press SEL.
ALL UNITS
The control circuit incorporates a current sensing lockout relay
(Cycle-LOC™ device) that locks off the compressor(s) for 5 min
-
utes when any safety device is activated (low or high pressure
switches, or compressor internal overload). If any compressor
safety device opens, the compressor will stop. High and low-pres
-
sure switches and compressor motor overload protectors will reset
automatically when the condition which caused the device to trip
has dropped below the reset condition. To reset the Cycle-LOC
control device, manually turn the control power OFF, then back
ON.
PARAMETER
INDEX
PARAMTER
FUNCTION
CHANGES FROM STANDARD
MACRO
9906
Motor Nominal Voltage
Set to Unit Voltage (208/230v=
230v, 460v, Or 575v)
9907
Motor Nominal Current
Motor FLA
9908
Motor Nominal Speed
Motor Nameplate
9909
Motor Nominal Power
Motor HP
PARAMETER
INDEX
PARAMETER
FUNCTION
CHANGES FROM STANDARD
MACRO
9902
Application Macro
1 (HVAC Default)
1101
Keypad Ref Sel
2 - REF2 (%)
1102
EXT 1 - EXT 2 SEL
7- EXT 2
1106
REF2 Select
2 - AL2
1107
REF2 Minimum
67%
1201
Constant Speed Select
-2 - DI2(INV)
1202
Const Speed 1
60 HZ
1601
Run Enable
1-DI1
1608
Start Enable
0 - Not Sel
1611
View
Long View