background image

Outside Air Temperature Sensor  

Installation and Operation

 

Specifications subject to change without notice.

 

2 of 2

 

Catalog No. 11-808-633-01

 

 

 

 

 

#20909 – 3/2/18

 

 

Mounting 

 

 

Sensor location is critical to good performance. The sensor must be mounted in the shade away from building 

windows, doors or vents. It should never be in direct sunlight or you will have higher than expected temperature 

readings by as much as +30%. The ideal shaded location in the Northern hemisphere is on the North side of the 

building. In the Southern hemisphere, the South side of the building is ideal.

 

 

The sensor shield and probe should always point down and be mounted between four feet above the ground/roof and 

one foot minimum below the eave. (

NOTE

  Four feet keeps the sensor above the ground or roof top radiation and one 

foot under the eave prevents measurement of trapped heat from under the eave.)

 

 

Drill the mounting holes and mount as shown in the Figure 2. Snug up the mounting screws to ensure that the foam 

backing compresses to about 50% of its thickness to make a gasket type seal against the wall surface.

 

 

Route the wires into the box and terminate with sealant filled connectors to prevent water from attacking the 

connection, thereby preventing costly callbacks. Best practice is to caulk the wiring hole after the wiring is installed. 

Close the cover of the enclosure and secure with provided cover screws. 

 
Wiring and Termination 

 

Carrier 

recommends using twisted pair of at least 22AWG for all wire connections. Larger gauge wire may be required 

for long runs. All wiring must comply with the National Electric Code (NEC) and local codes. Do NOT run this device’s 

wir-  ing in the same conduit as high or low voltage AC power wiring.  Tests show that inaccurate signal levels are 

possible when AC power wiring is present in the same conduit as the sensor wires. 

 
 
 
 
 
 
 
 

 
 

 

 

Diagnostics 

 

Possible  Problem: 

Controller reports higher or 

lower than actual 

temperature

 

Possible Solutions:

 

- Confirm the input is set up correctly in the front end software.

 

- Check wiring for proper termination and continuity (shorted or open).

 

- Disconnect wires and measure sensor resistance and verify the “Sensor” output is 

correct.

 

 

 

 

To Controller 

Analog Input (AI) 

(No Polarity) 

 

Figure 3:  

2 Wire Lead Wire Termination for Thermistor 

 

To Controller 

Analog Input (AI) 

(No Polarity)

 

Sensor

 

Reviews: