background image

Miniature Adjustable Current Switches

 

Installation and Operation

 

 

 

#NSA-A/MCS-A, NSA-A/MSCS-A 

– 11/14/2019 

 

Specifications subject to change without notice. 

Catalog No. 11-808-762-01 

Page 

5

 of 

5

 

Calibration of Adjustable Trip Point 

 

The adjustable current switch has an operating range of 0-150 Amps. Do not exceed! The adjustable current switch comes 
with its fifteen-turn adjustment potentiometer set to the 100 Amp trip point position. The adjustable current switch can be 
used to monitor Under Load, Normal L

oad, and Over Load conditions, depending on how it’s set. The procedure below is 

for the Normal load condition for part numbers NSA-A/MCS-A- and NSA-A/MSCS-A. 

 

Normal Loads 

With current flowing through the aperture of the NSA-A/MCS-A and NSA-A/MSCS-A current switches, first verify that the 
Blue LED is on. If the Blue LED is on, now slowly adjust the potentiometer clockwise until the Red LED just turns on and 
stop immediately. This sets the trip point at your normal operating load current. If the RED LED is on after initial power up, 
this means that you need to slowly adjust the potentiometer counter-clockwise until the Blue LED turns on and then slowly 
adjust the potentiometer clockwise until the Red LED just turns on and stop immediately. The adjustable current switch is 
now tripped. Now verify the output with an Ohmmeter to verify that the contacts of the switch are approximately 0.200 
Ohms. The adjustable current switch Hysteresis (Dead Band) is typically 10% of the trip point. 

 

 

Troubleshooting 

 

Problem 

Solution 

Red LED is on but the current switch didn’t activate  

Disconnect the wires from the current switch output. 
Measure the resistance across the contacts with an 
Ohmmeter. See the table below for resistance 
readings for a good unit. 

Red LED didn

’t turn on and the current switch didn’t 

activate 

Verify that the conductor you are monitoring is above 
the adjustable trip point. If the sensor is monitoring 
less than the adjustable trip point, see Figure 3

Error! 

eference source not found.

Sensor doesn't switch at all, regardless of current 
level. 

Adjustment potentiometer is probably set to its 
maximum or minimum position. Turn the Pot counter-
clockwise all the way and verify if the LED switches 
from Red to Blue. 

 

 

Resistance Readings 

Carrier Model # 

 

Resistance if switch open 

 

Resistance if switch closed 

 

NSA-A/MCS-A 

Greater than 1 Meg ohms  

Approximately 0.2 ohms  

NSA-A/MSCS-A 

Greater than 1 Meg ohms  

Approximately 0.2 ohms  

 

 

W.E.E.E. Directive 

 

At the end of their useful life the packaging and product should be disposed of via a suitable recycling center. Do not 
dispose of with household waste. Do not burn. 

Summary of Contents for NSA-A/MCS-A

Page 1: ...Conditions Normal Load Conditions Broken Belts Belt Slippage Locked Rotors Electrical Failure Load Status Local Alarms such as Strobes Audible Alarms Pumps Fans Compressors Lighting Status and Usage Information Ovens Process Control Industrial Equipment Equipment Maintenance OEM Part Numbers NSA A MCS A NSA A MSCS A Specifications Monitored Current Type AC Current Maximum AC Voltage 600 VAC Operat...

Page 2: ...34792 CE RoHS2 WEEE Product Weight NSA A MCS A 0 15 lbs 0 068 kg NSA A MSCS A 0 20 lbs 0 091 kg Product Dimensions L x W x H NSA A MCS A Solid Core 2 510 63 82 mm x 0 940 23 94 mm x 2 000 50 80 mm NSA A MSCS A Split Core 2 650 67 19 mm x 0 940 23 94 mm x 2 380 60 49 mm 1 The LED should not be used to determine if current is present At low currents the LED may not be visible 2 Maximum wire length n...

Page 3: ... are familiar with codes standards and proper safety procedures for high voltage installations should attempt installation The current switches will not require external power since the power for the current switch is induced from the conductor being monitored The NSA A MCS A and NSA A MSCS A Current Switches should be used on Insulated Conductors Only The current switch may be mounted in any posi...

Page 4: ... controller NOTE When using a shielded cable be sure to connect only 1 end of the shield to ground at the controller Connecting both ends of the shield to ground may cause a ground loop When removing the shield from the sensor end make sure to properly trim the shield so as to prevent any chance of shorting The current switch output terminals represent a solid state switch for controlling both AC ...

Page 5: ...LED just turns on and stop immediately The adjustable current switch is now tripped Now verify the output with an Ohmmeter to verify that the contacts of the switch are approximately 0 200 Ohms The adjustable current switch Hysteresis Dead Band is typically 10 of the trip point Troubleshooting Problem Solution Red LED is on but the current switch didn t activate Disconnect the wires from the curre...

Reviews: