background image

Miniature Adjustable Current Switches

 

Installation and Operation

 

 

 

#NSA-A/MCS-A, NSA-A/MSCS-A 

– 11/14/2019 

 

Specifications subject to change without notice. 

Catalog No. 11-808-762-01 

Page 

1

 of 

5

 

Overview 

 

The Miniature Adjustable Current switches are designed for use in any AC current 
monitoring application in which you are looking for an adjustable current switch to 
monitor normal operating conditions, equipment failure or preventative 
maintenance scheduling for a particular piece of equipment. The adjustable current 
switches should be installed on the line side of the power to the motor, pump, 
compressor or other equipment. The miniature adjustable current switches are 
available in both solid and split-core versions in a smaller enclosure style than that 
of the NSA-A/ACS2 and NSA-A/ASCS2 Series adjustable current switches. The 
solid-core versions are a great choice for new installations or OEM applications in 
which cost sensitivity, lower trip points and environmental issues may be of 
concern. The split-core version of the current switches work great in retrofit 
applications and for use in service vehicles since one part will work in most applications and can be installed without 
disconnecting any wires. The adjustable current status switches can also be used to determine the run time of your 
equipment where you want to know when your piece of equipment runs and for how long it runs when logging the contact 
closures on your building management system or PLC. 

Applications

: Overload Conditions, Under Load Conditions, Normal Load Conditions, Broken Belts, Belt Slippage, Locked 

Rotors, Electrical Failure, Load Status, Local Alarms such as Strobes/Audible Alarms, Pumps, Fans, Compressors, 
Lighting Status and Usage Information, Ovens, Process Control, Industrial Equipment, Equipment Maintenance, OEM 

 

 

Part Numbers 

 

NSA-A/MCS-A 

 

NSA-A/MSCS-A 

 

 

Specifications 

 

Monitored Current Type: 

AC Current 

Maximum AC Voltage: 

600 VAC 

Operating Frequency Range: 

50/60 Hz 

Core Style: 

NSA-A/MCS-A

: Solid | 

NSA-A/MSCS-A

: Split 

Sensor Power: 

Induced from the Monitored Conductor (Insulated Conductors only) 

Amperage Range: 

Max Sensing Current Voltage: 600 VAC | Max Continuous Current: 158 A 
Max Current for 6 Seconds: 204 A | Max Current for 1 Second: 600 A 

Isolation Voltage: 

2200 VAC 

Output Switch Rating 

1.00 Amp @ 36 VAC/VDC 

Trip Point Style | Adjustable Trip Point Range: 

Adjustable Trip Point | 

NSA-A/MCS-A

: 0.32 

– 150 A 

NSA-A/MSCS-A

: 0.70 - 150 A 

Hysteresis: 

10% Trip Point, typical 

Contact Type: 

Normally-

Open “N/O” 

Contact Rating: 

1A Continuous @ 36 VAC/VDC 

Contact “On” Resistance | “Off” Resistance: 

< 0.5 Ohms (tripped) | > 1 Meg Ohms (Open) 

Response Time: 

NSA-A/MCS-A

: < 90 mS, typical | 

NSA-A/MSCS-A

: < 45 mS typical 

Status LED Indication

1

Red LED (Current above trip point) | Blue LED (Current below trip point) 

Aperture Size (Diameter): 

0.53” (13.46 mm) 

Operating Temperature Range: 

-22 to 140ºF (-30 to 60ºC) 

Operating Humidity Range: 

0 to 95%, non-condensing 

Recommended Storage Temperature | RH Range: 

41 to 95°F (5 to 35°C) | 40% to 85% RH, non-condensing 

Enclosure Material | Flammability Rating: 

PC/ABS (Polycarbonate/ABS Blend) | UL94-V0 

Wiring Connections: 

2 Position Screw Terminal Block (Not Polarity Sensitive) 

Wire Size: 

16 to 22 AWG (1.31 mm

2

 to 0.33 mm

2

) Copper Wires only 

Terminal Block Torque Rating: 

4.43 to 5.31 in-lbs. (0.5 to 0.6 Nm) 

Summary of Contents for NSA-A/MCS-A

Page 1: ...Conditions Normal Load Conditions Broken Belts Belt Slippage Locked Rotors Electrical Failure Load Status Local Alarms such as Strobes Audible Alarms Pumps Fans Compressors Lighting Status and Usage Information Ovens Process Control Industrial Equipment Equipment Maintenance OEM Part Numbers NSA A MCS A NSA A MSCS A Specifications Monitored Current Type AC Current Maximum AC Voltage 600 VAC Operat...

Page 2: ...34792 CE RoHS2 WEEE Product Weight NSA A MCS A 0 15 lbs 0 068 kg NSA A MSCS A 0 20 lbs 0 091 kg Product Dimensions L x W x H NSA A MCS A Solid Core 2 510 63 82 mm x 0 940 23 94 mm x 2 000 50 80 mm NSA A MSCS A Split Core 2 650 67 19 mm x 0 940 23 94 mm x 2 380 60 49 mm 1 The LED should not be used to determine if current is present At low currents the LED may not be visible 2 Maximum wire length n...

Page 3: ... are familiar with codes standards and proper safety procedures for high voltage installations should attempt installation The current switches will not require external power since the power for the current switch is induced from the conductor being monitored The NSA A MCS A and NSA A MSCS A Current Switches should be used on Insulated Conductors Only The current switch may be mounted in any posi...

Page 4: ... controller NOTE When using a shielded cable be sure to connect only 1 end of the shield to ground at the controller Connecting both ends of the shield to ground may cause a ground loop When removing the shield from the sensor end make sure to properly trim the shield so as to prevent any chance of shorting The current switch output terminals represent a solid state switch for controlling both AC ...

Page 5: ...LED just turns on and stop immediately The adjustable current switch is now tripped Now verify the output with an Ohmmeter to verify that the contacts of the switch are approximately 0 200 Ohms The adjustable current switch Hysteresis Dead Band is typically 10 of the trip point Troubleshooting Problem Solution Red LED is on but the current switch didn t activate Disconnect the wires from the curre...