background image

Adjustable Current Switches

 

Installation and Operation

 

 

 

#NSA-A/ACS2, NSA-A/ASCS2, NSA-A/ASCS2-L 

– 11/14/2019 

 

Specifications subject to change without notice. 

Catalog No. 11-808-743-01 

Page 

7

 of 

7

 

Application Examples 

See Figure 5 and Figure 6  for two different current switch applications. Figure 5 shows the use of the Go/No Go Current 
Switch as a Digital Input to your BAS/PLC Controller. Figure 6 shows a Go/No/Go Current Switch in conjunction with a 
Contactor to control an exhaust fan. 

NOTE

  The Go/No Go Current switches are only rated at 0.2A @ 200 VAC/VDC and must use an additional Contactor if 

controlling motor/fans. 

 

 

Calibration of Adjustable Trip Point 

 

The adjustable current switch has an operating range of 0-250 Amps, 

Do not exceed!

 The current switch has an 

adjustable trip point range of 0.50 - 220 Amps, 1.50 - 220 Amps, or 0.60 - 180 Amps depending on the model. See the 
Specifications table to determine the adjustable trip point range per model number. The adjustable current switch comes 
with its fifteen-turn adjustment potentiometer set to the maximum trip point position. The adjustable current switch can 
monitor Underload, Normal Load, and Overload conditions, depending on how it’s set. The procedure below is for the 
Normal load condition for part numbers NSA-A/ACS2, NSA-A/ASCS2 and NSA-A/ASCS2-L. 

 

Normal Loads 

With power on, turn the 15-turn adjustment potentiometer clockwise until the Red LED turns on and stop immediately. 
Clockwise is referenced with the terminal block location on the right. The adjustable current switch is now tripped. The 
adjustable current switch Hysteresis (Dead Band) is 10% of the trip point typically. 

 

Clockwise = Decrease Trip 

 

Counter-clockwise = Increase Trip 

 

 

Troubleshooting 

 

Problem 

Solution 

LED is on 

but the current switch didn’t activate 

Disconnect the wires from the current switch output. 
Measure the resistance across the contacts with an 
Ohmmeter. See Specifications table for the actual 
resistance readings for an open or closed switch reading. 

LED 

didn’t turn on and the current switch didn’t 

activate 

Verify that the current flowing in the conductor being 
monitored is above the fixed trip point as listed in the 
operating specifications. If the sensor is monitoring less 
than the fixed trip point, see Figure 3. 

LED not on but the Current Switch is Activated 

LED not indicating correctly, may have been damaged. 

Current Switch is operating at a low-level current or 
failing to operate within the accuracy specifications 

For NSA-A/ASCS2 Series, visually check the mating parts 
of the core to ensure there is no debris between the split 
contacts. Remove all debris or dust manually and close 
the current sensor, see Figure 2. Retest the sensor in your 
application. 

 

Summary of Contents for NSA-A/ACS2

Page 1: ...ng management system or PLC Applications Overload Conditions Underload Conditions Normal Operating Conditions Broken Belts Belt Slippage Locked Rotors Equipment Failure Fans Pumps Compressors Motors Ovens Industrial Equipment Lighting Status and Usage Electrical Load Status Local Alarms Strobes and Audible Alarms Preventative Maintenance Scheduling Part Numbers NSA A ACS2 NSA A ASCS2 NSA A ASCS2 L...

Page 2: ...t File E309723 CE RoHS2 WEEE Product Weight NSA A ACS2 0 216 lbs 0 097 kg NSA A ASCS2 0 270 lbs 0 123 kg NSA A ASCS2 L 0 280 lbs 0 127 kg Product Dimensions L x W x H Solid Core 2 760 70 11 mm x 3 343 84 92 mm x 1 050 26 67 mm Split Core 2 780 70 51 mm x 3 238 82 25 mm x 1 120 28 45 mm Response Time Model 0 50 Amps 0 60 Amps 0 75 Amps 1 0 Amps 1 5 Amps 10 Amps 20 Ampls NSA A ACS2 221 mS 144 mS 109...

Page 3: ...ly on the Red LED to determine whether power is present at the current switch At very low monitored input currents the Red LED may not light to indicate the current is above the trip point Installation Ensure all installations are in compliance with all national and local electrical codes Only qualified individuals that are familiar with codes standards and proper safety procedures for high voltag...

Page 4: ... the tongue on the base CAUTION Mating surfaces of the magnetic core are exposed when the sensor is open Electrical contact grease present on the cores to prevent corrosion can capture grit and dirt if care is not exercised Operation can be impaired if anything prevents good contact between pole pieces Visually check the mating parts of the core before closing the current sensor Figure 2 LED The R...

Page 5: ...urrent of 0 4 Amps flowing through the NSA A ACS2 Formula Example 0 25A 0 1A 2 5 1 3 5 which rounded up equals 4 loops Wiring Instructions Carrier recommends the use of a two conductor 16 to 22 AWG shielded cable or twisted pair copper wire only for all current switch applications A maximum wire length of less than 30 meters 98 4 feet should be used between the current switch and the Building Mana...

Page 6: ...Switches Installation and Operation NSA A ACS2 NSA A ASCS2 NSA A ASCS2 L 11 14 2019 Specifications subject to change without notice Catalog No 11 808 743 01 Page 6 of 7 Digital Circuit Figure 5 Motor Fan Control Figure 6 ...

Page 7: ...r part numbers NSA A ACS2 NSA A ASCS2 and NSA A ASCS2 L Normal Loads With power on turn the 15 turn adjustment potentiometer clockwise until the Red LED turns on and stop immediately Clockwise is referenced with the terminal block location on the right The adjustable current switch is now tripped The adjustable current switch Hysteresis Dead Band is 10 of the trip point typically Clockwise Decreas...

Reviews: