62-12119
22
b. Press the ENTER key and hold for five seconds. After the
ENTER key has been pressed, the display reads “CAL” (for
calibration).
43. Press the ALT MODE key and hold for five seconds. After the
calibration has been completed, Cd45 will display 0 CMH /
CFM.
44. Download (interrogate) the unit DataCORDER using a
PCMCIA downloading card, USB adapter or DataLINE. It is
recommended to get an "ALL DATA" download for records.
The minimum should be "LAST TRIP START" to ensure all
PM temperature and PTI data is obtained.
45. Turn the unit off and disconnect from the power supply.
46. Print out the trip report and retain it as a permanent record of
the PM.
47. Retain the download and inspection sheet as a record of the
annual inspection.