background image

Specifications are subject to change without notice.

25

441 01 1422 00

This furnace is permitted to be vented into a clay tile

lined

masonry chimney that is exposed to the outdoors below the roof

line, provided:

1. Vent connector is Type

B double

wall, and

2. This furnace is common vented with at least 1 draft hood

equipped appliance, and

3. The combined appliance input rating is less than the maxi-

mum capacity given in Table 8, and

4. The input rating of each space heating appliance is greater

than the minimum input rating given in Table 9 for the lo-

cal 99% Winter Design Temperature. Chimneys having in-

ternal areas greater than 38 square inches require furnace

input ratings greater than the input ratings of these fur-

naces. See footnote at bottom of Table 9, and

5. The authority having jurisdiction approves.

If all of these conditions cannot be met, an alternative venting

design shall be used, such as the listed chimney adapter kit with

these furnaces, which are listed for use with the kit, a listed

chimney

lining system, or a Type

B common vent.

Inspections before the sale and at the time of installation will

determine the acceptability of the chimney or the need for repair

and/or (re)lining. Refer to the Fig. 26 to perform a chimney

inspection. If the inspection of a previously used tile

lined

chimney:

a. Shows signs of vent gas condensation, the chimney

should be relined in accordance with local codes and the

authority having jurisdiction. The chimney should be re-

lined with a listed metal liner, Type

B vent, or a listed

chimney adapter kit shall be used to reduce condensation.

If a condensate drain is required by local code, refer to

the current edition of NFGC NFPA54/ANSI Z223.1,

Section 12.10 for additional information on condensate

drains.

b. Indicates the chimney exceeds the maximum permissible

size in the tables, the chimney should be rebuilt or relined

to conform to the requirements of the equipment being

installed and the authority having jurisdiction.

A chimney without a clay tile liner, which is otherwise in good

condition, shall be rebuilt to conform to current edition of

ANSI/NFPA 211 or be lined with a UL listed metal liner or UL

listed Type

B vent. Relining with a listed metal liner or Type

B

vent is considered to be a vent

in

a

chase.

If a metal liner or Type

B vent is used to line a chimney, no other

appliance shall be vented into the annular space between the

chimney and the metal liner.

Exterior Masonry Chimney FAN + NAT

Installations with Type

B Double Wall Vent

Connectors 

{

NFPA & AGA

Table 8 – Combined Appliance Maximum Input Rating in

Thousands of BTUH per Hour

VENT HEIGHT

FT. (M)

INTERNAL AREA OF CHIMNEY 

IN

2

 (MM

2

)

12

(7741)

19

(12258)

28

(18064)

38

(24516)

6 (1.8)

74

119

178

257

8 (2.4)

80

130

193

279

10 (3.0)

84

138

207

299

15 (4.5)

NR

152

233

334

20 (6.0)

NR

NR

250

368

30 (9.1)

NR

NR

NR

404

Table 9 – Minimum Allowable Input Rating of Space

Heat-

ing Appliance in Thousands of BTUH per Hour

VENT HEIGHT

FT (M)

INTERNAL AREA OF CHIMNEY

IN

2

. (MM

2

)

12

(7741)

19

(12258)

28

(18064)

38

(24516)

Local 99% Winter Design

Temperature: 17 to 26

_

F (-8 to -3

_

C)

6 (1.8)

0

55

99

141

8 (2.4)

52

74

111

154

10 (3.0)

NR

90

125

169

15 (4.6)

NR

NR

167

212

20 (6.1)

NR

NR

212

258

30 (9.1)

NR

NR

NR

362

Local 99% Winter Design

Temperature:  5 to 16

_

F* (-15 to -9

_

C)

6 (1.8)

NR

78

121

166

8 (2.4)

NR

94

135

182

10 (3.0)

NR

111

149

198

15 (4.6)

NR

NR

193

247

20 (6.1)

NR

NR

NR

293

30 (9.1)

NR

NR

NR

377

Local 99% Winter Design

Temperature:  -10 to 4

_

F* (-23 to -16

_

C)

6 (1.8)

NR

NR

145

196

8 (2.4)

NR

NR

159

213

10 (3.0)

NR

NR

175

231

15 (4.6)

NR

NR

NR

283

20 (6.1)

NR

NR

NR

333

30 (9.1)

NR

NR

NR

NR

Local 99% Winter Design

Temperature:  -11

_

F (-24

_

C) or lower

Not recommended for any vent configuration.

*The 99.6% heating db temperatures found in the 1997 or 2001 ASHRAE
Fundamentals Handbook, Climatic Design Information chapter, Table 1A
(United States) or the 2005 ASHRAE Fundamentals handbook, Climatic
Design Information chapter, and the CD-ROM included with the 2005
ASHRAE Fundamentals Handbook.

APPLIANCE APPLICATION REQUIREMENTS

Appliance operation has a significant impact on the performance

of the venting system. If the appliances are sized, installed,

adjusted, and operated properly, the venting system and/or the

appliances should not suffer from condensation and corrosion.

The venting system and all appliances shall be installed in

accordance with applicable listings, standards, and codes.
The furnace should be sized to provide 100 percent of the design

heating load requirement plus any margin that occurs because of

furnace model size capacity increments. Heating load estimates

can be made using approved methods available from Air

Conditioning Contractors of America (Manual J); American

Society of Heating, Refrigerating, and Air

Conditioning

Engineers; or other approved engineering methods. Excessive

oversizing of the furnace could cause the furnace and/or vent to

fail prematurely. When a metal vent or metal liner is used, the

vent must be in good condition and be installed in accordance

with the vent manufacturer’s instructions.

Summary of Contents for N8MXL

Page 1: ...ONNECTION TO J BOX 21 BX CABLE INSTALLATION IN FURNACE J BOX 21 24 V WIRING 21 ACCESSORIES 22 VENTING 24 GENERAL VENTING REQUIREMENTS 24 MASONRY CHIMNEY REQUIREMENTS 24 APPLIANCE APPLICATION REQUIREMENTS 25 ADDITIONAL VENTING REQUIREMENTS 27 SIDEWALL VENTING 27 START UP ADJUSTMENT AND SAFETY CHECK 31 GENERAL 31 START UP PROCEDURES 31 ADJUSTMENTS 31 CHECK SAFETY CONTROLS 33 CHECKLIST 34 SERVICE AND...

Page 2: ... a location and position as spe cified in the Location section of these instructions 3 Provide adequate combustion and ventilation air to the furnace space as specified in Air for Combustion and Ventilation section 4 Combustion products must be discharged outdoors Con nect this furnace to an approved vent system only as spe cified in the Venting section of these instructions 5 Never test for gas l...

Page 3: ...1 16 2 1 16 51 6 51 6 5 1 5 1 130 5 130 5 1 7 1 7 43 5 43 5 Ø7 8 Ø7 8 22 2 22 2 ACCESSORY 2 ACCESSORY 2 AIR FLOW AIR FLOW AIR FLOW AIR FLOW BOTTOM RETURN BOTTOM RETURN WIDTH WIDTH AIR FLOW AIR FLOW KNOCK OUTS FOR KNOCK OUTS FOR VENTING 5 VENTING 5 PLACES PLACES A10290 NOTES 1 Two additional 7 8 in 22 mm diameter holes are located in the top plate 2 Minimum return air openings at furnace based on m...

Page 4: ...Specifications are subject to change without notice 4 441 01 1422 00 A10269 Fig 2 Clearances to Combustibles ...

Page 5: ... DISCHARGE ESD PRECAUTIONS PROCEDURE FURNACE RELIABILITY HAZARD Improper installation or service of furnace may cause premature furnace component failure Electrostatic discharge can affect electronic components Follow the Electrostatic Discharge Precautions Procedure listed below during furnace installation and servicing to protect the furnace electronic control Precautions will prevent electrosta...

Page 6: ...OXIDE POISONING HAZARD Failure to follow this warning could result in personal injury or death and unit component damage Corrosive or contaminated air may cause failure of parts containing flue gas which could leak into the living space Air for combustion must not be contaminated by halogen compounds which include fluoride chloride bromide and iodide These elements can corrode heat exchangers and ...

Page 7: ... also prevents the entrainment of drywall dust into combustion air which can cause fouling and plugging of furnace components The temperature of the return air to the furnace is maintained between 55_F 13_C and 80_F 27_C with no evening setback or shutdown The use of the furnace while the structure is under construction is deemed to be intermittentoperation per our installation instructions The ai...

Page 8: ...ipped with means to prevent operation of either unit unless the damper is in the full heat or full cool position AIR FOR COMBUSTION AND VENTILATION Provisions for adequate combustion ventilation and dilution air must be provided in accordance with S U S installations Section 9 3 of the current edition of NFGC NFPA54 ANSI Z223 1 Air for Combustion and Ventilation and applicable provisions of the lo...

Page 9: ...IDE POISONING HAZARD Failure to follow this warning could result in death and or personal injury Many homes require air to be supplied from outdoors for furnace combustion ventilation and dilution of flue gases The furnace combustion air supply must be provided in accordance with this instruction manual WARNING CIRCULATING AIR DUCTS 6 MIN FRONT Ü CIRCULATING AIR DUCTS VENT THROUGH ROOF 1 SQ IN PER...

Page 10: ...electrical and gas lines etc Combination of Indoor and Outdoor Air 1 Indoor openings shall comply with the Indoor Combus tion Air Method below and 2 Outdoor openings shall be located as required in the Out door Combustion Air Method mentioned previously and 3 Outdoor openings shall be sized as follows a Calculate the Ratio of all Indoor Space volume divided by required volume for Indoor Combustion...

Page 11: ...l as shown in Fig 13 NOTE It is required that the perforated supply air duct flanges be completely folded over or removed from furnace when installing the furnace on a factory supplied cased coil or coil box To remove the supply air duct flange use wide duct pliers or hand seamers to bend flange back and forth until it breaks off Be careful of sharp edges See Fig 14 Bottom Return Air Inlet These f...

Page 12: ...ired 15 7 8 403 19 483 16 1 2 419 19 5 8 498 Downflow Applications on Combustible Flooring subbase required 15 1 8 384 19 483 16 3 4 425 20 5 8 600 Downflow Applications on Combustible Flooring Coil with Coil END4X ENW4X or Coil Casing NAEA subbase not required 15 1 2 394 19 483 16 1 2 419 20 508 21 533 Upflow Applications on Combustible or Noncombustible Floor ing subbase not required 19 1 2 495 ...

Page 13: ...ir Inlet These furnaces are shipped with bottom closure panel installed in bottom return air opening This panel MUST be in place when side return air inlet s is used without a bottom return air inlet Not all horizontal furnaces are approved for side return air connections See Fig 21 FILTER ARRANGEMENT CARBON MONOXIDE AND POISONING HAZARD Failure to follow this warning could result in personal inju...

Page 14: ...upply air outlet on furnace Bend flange inward past 90_ with wide duct pliers See Fig 14 The supply air duct must be connected to ONLY the furnace supply outlet or air conditioning coil casing when used When installed on combustible material supply air duct must be connected to ONLY the factory approved accessory subbase or a factory approved air conditioning coil casing DO NOT cut main furnace ca...

Page 15: ...S IN BOTTOM A10131 Fig 16 Horizontal Suspension with Straps 30 IN 762mm MIN WORK AREA 6 MIN TYPE B VENT 17 3 4 22 SHEET METAL SEDIMENT TRAP EQUIPMENT MANUAL SHUT OFF GAS VALVE LINE CONTACT ONLY PERMISSIBLE BETWEEN LINES FORMED BY INTERSECTIONS OF THE TOP AND TWO SIDES OF THE FURNACE JACKET AND BUILDING JOISTS STUDS OR FRAMING GAS ENTRY 17 3 4 451mm OVERALL 4 3 4 121mm UNDER DOOR 1 25mm UNDER FURNA...

Page 16: ...e shall be installed at the furnace gas control valve and extend a minimum of 2 in 51 mm outside the furnace WARNING Gas piping must be installed in accordance with national and local codes Refer to current edition of NFGC Installations must be made in accordance with all authorities having jurisdiction If possible the gas supply line should be a separateline running directly from meter to furnace...

Page 17: ...775 715 665 595 530 455 0901714 Gray 5 1355 1320 1285 1245 1210 1165 1125 1080 1025 815 Yellow 4 1295 1255 1220 1185 1140 1100 1055 1005 955 815 Blue 3 1220 1185 1150 1105 1065 1025 975 915 840 740 Orange 2 1030 985 940 900 845 790 715 655 590 535 Red 1 3 945 905 855 800 750 670 600 540 490 435 0902116 Gray 5 1625 1580 1535 1490 1445 1395 1340 1260 1135 995 Blue 4 1440 1395 1350 1305 1255 1200 114...

Page 18: ...98 285 87 1 1 4 32 1 380 35 1400 427 950 290 770 235 660 201 580 177 1 1 2 38 1 610 41 2100 640 1460 445 1180 360 990 301 900 274 Cubic ft of natural gas per hr for gas pressures of 0 5 psig 14 In W C or less and a pressure drop of 0 5 In W C based on a 0 60 specific gravity gas Ref Chapter 6 current edition of ANSI Z223 NFPA 54 Piping should be pressure and leak tested in accordance with NFGC in ...

Page 19: ...o change without notice 19 441 01 1422 00 A02163 Fig 20 Downflow Return Air Configurations and Restrictions A02162 Fig 21 Horizontal Return Air Configurations and Restrictions 2 51mm Street Elbow A08551 Fig 22 Burner and Manifold ...

Page 20: ...ires prior to disconnection Reconnect wires correctly Verify proper operation after servicing WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Blower access panel door switch opens 115 v power to control No component operation can occur Do not bypass or close switch with panel removed WARNING See Fig 25 for field wiring diagram showing typical...

Page 21: ...g 3 Fasten the electrical box to casing by driving two field supplied screws from inside electrical box into casing steel 4 Remove and save two screws holding J Box 5 Pull furnace power wires out of 1 2 in 12 mm diameter hole in J Box Do not loosen wires from strain relief wire tie on outside of J Box 6 Route furnace power wires through holes in casing and electricalbox and into electrical box 7 P...

Page 22: ...um combined humidifier if used to the inch male quick connect HUM terminal and NEUTRAL inch quick connect The HUM ter minal is energized when the inducer motor is energized IDR See Fig 24 and 47 NOTE A field supplied 115 v controlled relay connected to EAC terminals may be added if humidifier operation is desired during blower operation NOTE DO NOT connect furnace control HUM 24VAC terminal to H h...

Page 23: ... WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 230 V SINGLE PHASE BLOWER DOOR SWITCH WHT BLK WHT BLK NOTES Connect Y terminal in furnace as shown for proper blower operation Some thermostats require a C terminal connection as shown If any of the original wire as supplied must be replaced use same type or equivalent wire W Y Y2 GND THERMOSTAT TERMINALS 1 2 3 Repre...

Page 24: ... proper vent sizing and installation requirements including local building codes the current edition of National Fuel Gas Code ANSI Z223 1 NFPA 54 NFGC Parts 12 and 13 the local building codes and furnace and vent manufacturers instructions These furnaces are design certified as Category I furnaces in accordance with current edition of ANSI Z21 47 CSA 2 3 and operate with a non positive vent stati...

Page 25: ...ce between the chimney and the metal liner Exterior Masonry Chimney FAN NAT Installations with Type B Double Wall Vent Connectors NFPA AGA Table 8 Combined Appliance Maximum Input Rating in Thousands of BTUH per Hour VENT HEIGHT FT M INTERNAL AREA OF CHIMNEY IN2 MM2 12 7741 19 12258 28 18064 38 24516 6 1 8 74 119 178 257 8 2 4 80 130 193 279 10 3 0 84 138 207 299 15 4 5 NR 152 233 334 20 6 0 NR NR...

Page 26: ...ebris in cleanout Mortar tile metal vent fuel oil residue Is liner and top seal in good condition Is chimney property lined with clay tile liner Crown condition Missing mortar or brick Rebuild crown Yes Yes No No No Reline Yes Repair Yes Yes Yes No No Remove mortar and tile debris Remove metal vent or liner No No No No Yes Yes Suitable Suitable Not Suitable Line chimney with property sized listed ...

Page 27: ...rews The factory supplied vent elbow does NOT count as part of the number of vent connector elbows The vent connector can exit the furnace through one of 5 locations on the casing 1 Attach the single wall vent connector to the furnace vent elbow and fasten the vent connector to the vent elbow with at least two field supplied corrosion resistant sheet metal screws located 180_ apart NOTE An accesso...

Page 28: ... 2 Horizontal Left Vent elbow right Fig 35 132 000 5 127 7 2 NOTE All vent configurations must also meet National Fuel Gas Code venting requirements NFGC 4 in 102 mm inside casing or vent guard Including 4 in 102 mm vent section s SEE NOTES 1 2 4 7 8 9 on the page following these figures A03208 Fig 27 Upflow Application Vent Elbow Up SEE NOTES 1 2 3 4 7 8 9 on the pages following these figures A03...

Page 29: ... Left then Up SEE NOTES 1 2 3 4 5 7 8 9 on the page following these figures A03212 Fig 32 Downflow Application Vent Elbow Up then Right SEE NOTES 1 2 4 7 8 9 on the page following these figures A03213 Fig 33 Horizontal Left Application Vent Elbow Left SEE NOTES 1 2 4 5 7 8 9 on the page following these figures A03214 Fig 34 Horizontal Left Application Vent Elbow Right then Up ...

Page 30: ... and downflow installations must use Type B vent immediately after exiting the furnace except when factory authorized Downflow Vent Guard Kit is used in the downflow position See Specification Sheet for accessory listing 4 Type B vent where required refer to Note 1 above 5 Four inch single wall 26 ga min vent must be used inside furnace casing and when the Downflow Vent Guard Kit is used external ...

Page 31: ...ot be turned on See Fig 24 ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Blower access door switch opens 115 v power to control No component operation can occur unless switch is closed Caution must be taken when manually closing this switch for service purposes WARNING NOTE The furnace control allows all components except the gas valve to be run fo...

Page 32: ...nput rate of clockwise in to increase input rate h Install regulator seal cap i Leave manometer or similar device connected and pro ceed to Step 4 NOTE DO NOT set manifold pressure less than 3 2 In W C or more than 3 8 In W C for natural gas at sea level If manifold pressure is outside this range change main burner orifices Refer to Table 10 11 12 and 13 NOTE If orifice hole appears damaged or it ...

Page 33: ...ile measuring current 1 Remove thermostat from subbase or from wall 2 Connect an amp meter as shown in Fig 42 across the R and W subbase terminals or R and W wires at wall 3 Record amp draw across terminals when furnace is in heating and after blower starts 4 Set heat anticipator on thermostat per thermostat in structions and install on subbase or wall b Electronic thermostat Set cycle rate for 4 ...

Page 34: ... off 115 v power to furnace b Disconnect inducer motor lead wires from wire harness c Turn on 115 v power to furnace d Set thermostat to call for heat and wait 1 minute When pressure switch is functioning properly hot surface ignit er should NOT glow and control flashes a status code 3 If hot surface igniter glows when inducer motor is discon nected shut down furnace immediately e Determine reason...

Page 35: ... 116 290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 95 237 29 124 248 621 78 46 92 231 30 120 240 600 80 45 90 225 31 116 232 581 82 44 88 220 32 113 225 563 84 43 86 214 33 109 218 545 86 42 84 209 34 106 212 529 88 41 82 205 35 103 206 514 90 40 8...

Page 36: ...Specifications are subject to change without notice 36 441 01 1422 00 Table 12 Orifice Size and Manifold Pressure In W C for Gas Input Rate A10180 ...

Page 37: ...Specifications are subject to change without notice 37 441 01 1422 00 Table 12 Orifice Size and Manifold Pressure In W C for Gas Input Rate CONT A10180A ...

Page 38: ...Specifications are subject to change without notice 38 441 01 1422 00 Table 13 Orifice Size And Manifold Pressure In W C For Gas Input Rate A10181 ...

Page 39: ...Specifications are subject to change without notice 39 441 01 1422 00 Table 13 Orifice Size And Manifold Pressure In W C For Gas Input Rate CONT A10181A ...

Page 40: ...r is discharged upward Since this furnace can be installed in any of the 4 positions shown in Fig 4 you must revise your orientation to component location accordingly ELECTRICAL CONTROLS AND WIRING ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury or death There may be more than one electrical supply to the furnace Check accessories and cooling unit for add...

Page 41: ...WARNING CARBON MONOXIDE POISONING AND FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Never operate unit without a filter or with filter access door removed WARNING CUT HAZARD Failure to follow this caution may result in personal injury Sheet metal parts may have sharp edges or burrs Use care and wear appropriate protective clothing safety gl...

Page 42: ...ent Blower wheel blades may be cleaned with a small paint or flux brush Do not remove or disturb balance weights clips on blower wheel blades 8 Vacuum any loose dust from blower housing wheel and motor 9 If a greasy residue is present on blower wheel remove wheel from the blower housing and wash it with an appro priate degreaser To remove wheel NOTE Before disassembly mark blower motor and blower ...

Page 43: ...ternal vent pipe remove internal vent pipe within the casing 5 Disconnect wires to the following components Mark wires to aid in reconnection of be careful when discon necting wires from switches because damage may occur a Draft safeguard switch b Inducer motor c Pressure switch es d Limit over temperature switch e Gas valve f Hot surface igniter g Flame sensing electrode h Flame rollout switches ...

Page 44: ...ematic diagram follow the sequence of operation through the different modes Read and follow the wiring diagram very carefully NOTE If a power interruption occurs during a call for heat W the control will start a 90 sec blower only ON period two seconds after power is restored if the thermostat is still calling for gas heating The GREEN LED light will flash code 1 2 during the 90 sec period after w...

Page 45: ...al EAC 1 AMP is energized as long as the blower motor BLWM is ener gized During a call for heat the blower BLWM will stop during igniter warm up 17 sec ignition and blower ON delay 25 sec allowing the furnace heat exchangers to heat up more quickly then restarts at the end of the blower ON delay period at HEAT speed When the thermostat calls for cooling the blower motor BLWM will operate at COOL s...

Page 46: ...Specifications are subject to change without notice 46 441 01 1422 00 Fig 47 Wiring Diagram ...

Page 47: ...Specifications are subject to change without notice 47 441 01 1422 00 ...

Page 48: ...Specifications are subject to change without notice 48 441 01 1422 00 NOTE NUMBER IN UPPER LEFT HAND CORNER REPRESENTS FLASH CODE Fig 48 Troubleshooting Guide ...

Page 49: ... X ECM Blower Motor S Single stage T Two stage TYPE N Standard L Low Nox FEATURE 045 45 000 BTU hr 070 70 000 BTU hr 090 90 000 BTU hr 110 110 000 BTU hr 135 135 000 BTU hr HEAT INPUT 14 143 16 17 171 2 21 21 24 241 2 CABINET WIDTH 08 800 CFM 12 1200 CFM 14 1400 CFM 16 1600 CFM 18 1800 CFM 20 2000 CFM 22 2200 CFM COOLING AIRFLOW SALES MAJOR REVISION DIGIT ENGINEERING MINOR REVISION DIGIT TO OBTAIN...

Page 50: ...Specifications are subject to change without notice 50 441 01 1422 00 Copyright 2018 International Comfort Products Lewisburg TN 37091 USA ...

Reviews: