SCENARIO 2: SINGLE ZONE OUTDOOR 
UNITS (38MBR) WITH APPROVED 
DUCTLESS INDOOR UNITS

• Cassette (sizes 36K-48K)
• Ducted (sizes 36K-58K) (*refer to 

NOTES

 in the adjacent column)

• Console (sizes 36K-58K)

Installation Steps:

1. Run the interconnecting piping from the indoor unit to the outdoor

unit using the correct indoor piping size.

2. Run the interconnecting wiring from the outdoor unit to the 24V

interface using terminal connections L1, L2, and G. Connect the

wiring for the S1 and S2 outdoor interface to CN8.

3. Run the interconnecting wiring from the 24V interface to the indoor

unit using terminal connections L1, L2, and G. Connect the wiring

for the S1 and S2 outdoor interface to CN9.

4. Run the thermostat wiring from the thermostat to the 24V interface

using connections R and C on CN15 and Y, W, G on CN19.

5. Configure the dip switches on the 24V interface accordingly.

6. Configure the thermostat to operate in single stage cooling and heating

scenarios (

DO NOT

 configure the thermostat as a 

Heat Pump

). 

NOTES: 

Follow the indoor and outdoor unit's general installation instructions. 
*For Ducted units, in order to initially setup the static pressure, the 

24V interface must be bridged. Temporarily connect the 

communication wires, S1 and S2, from the indoor unit to the outdoor 

unit until the static pressure settings are complete (see the Ducted 

unit installation manual). When the static pressure is adjusted, 

connect S1 and S2 to CN8 and CN9 (see Fig. 21).

On selected indoor units, the Up-Down Swing Louver functions as a 

control to turn off the indoor unit display (LED) and is available on 

the unit's wireless remote controller. The Wi-Fi accessories KSAIF 

and wired remote controllers KSACN are not functional when using 

the 24V interface. 

Fig. 10 — Wiring Diagram 

Refer to the Compatibility Charts on hvacpartners.com for the proper 
matches and serial number compatibility. Units built prior to the generation 
of this serial number would require a Control Board Replacement on the 
Indoor unit.

CAUTION

The conventional thermostat must be configured for use with a single stage
air conditioner (Y output 

ONLY

) and a single stage heating (W) system.

CAUTION

Do not
install T1
indoor sensor

Power supply from outdoor unit disconnect
Two wires are line voltage and the other is a ground wire.

NOTE: Dashed Lines indicate
OPTIONAL COMPONENTS

GROUND

BUS BAR

G

G

G

G

Summary of Contents for KSAIC0301230

Page 1: ...y Understand these signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which may result in severe personal injury or de...

Page 2: ...refrigerant compressors Pressurized mixtures of air or gases containing oxygen can lead to an explosion WARNING INSTALLATION Entrust a licensed contractor to install the unit Installation by unskilled...

Page 3: ...ble 3 24V Interface Clearance Dimensions NOTE 24 in 610mm minimum for service access or use local code Fig 3 Clearances Clearances Unit Minimum Value In mm Sides 5 9 150 Front 24 610 Top and Bottom 3...

Page 4: ...er the screw SYSTEM CONFIGURATION NOTES The thermostat should be configured for use with a as a single stage Cooling and Heating DO NOT configure the thermostat as a Heat Pump The wireless remote cont...

Page 5: ...ndoor to the outdoor unit until the static pressure settings are complete refer to the Ducted unit installation manual On selected indoor units the Up Down Swing Louver functions as a control to turn...

Page 6: ...general installation instructions For Ducted units in order to initially setup the static pressure the 24V interface must be bridged Temporarily connect the communication wires S1 and S2 from the indo...

Page 7: ...it until the static pressure settings are complete see the Ducted unit installation manual When static pressure is adjusted reconnect L1 L2 S and G wires to the terminal blocks In the AUTO mode the sy...

Page 8: ...a single stage cooling and heating DO NOT configure the thermostat as Heat Pump NOTES Follow the indoor and outdoor unit s general installation instructions The T1 Return air temperature sensor should...

Page 9: ...oor unit s general installation in the next column 9 Configure the dip switches on the 24V Interface for proper operation For Heat Pump all switches OFF except SW1 1 ON For Cooling Only all switches O...

Page 10: ...he Teflon gasket on the brass tip of the Piping Adapter and insert into the aluminum distributor head Thread the piping adapter brass nut onto the distributor line and tighten finger tight 1 2 turn Fi...

Page 11: ...Using a Conventional Fan Coil The following steps should be taken when using this device with a conventional fan coil unit scenarios 4 and 5 1 Indoor coil metering device TXV Piston must be removed 2...

Page 12: ...il only available on scenarios 1 through 3 Table 11 DIP Switch 2 2 NOTE Applicable only to the Ductless Style Indoor Heat Pump units in the HEATING mode DIP Switch 3 1 On Ductless systems Dry is used...

Page 13: ...emperature sensor T5 malfunction Outdoor Service Manual F4 Outdoor unit EEPROM parameter error Outdoor Service Manual F5 Outdoor fan speed has been out of control Outdoor Service Manual F6 T2b sensor...

Page 14: ...opens and closes based on the system s alarm status This is normally a an open dry contact Work Output CN6 This contact is a dry contact that opens and closes based on the system s running or not run...

Page 15: ...minal System Size MBTUH Indoor Model Number Outdoor Model Number Recommended Maximum Indoor Fan Speed Tap Number FMA4 Vertical Fan Coil 208 230 1 KSAIC0301230 12 FMA4X1800AL 38MAQB12R 3 Tap 1 18 FMA4X...

Page 16: ...door coil s size No refrigerant addition is necessary for the FV4 any size All the outdoor units are shipped from the factory pre charged for 25ft of piping length See the outdoor unit s installation...

Reviews: