background image

10

Table 3 – Status Codes

OPERATION

FAULT

AMBER LED

FLASH CODE

Possible Cause and Action

Standby – no call

for unit operation

None

On solid, no flash

Normal operation --- 3 thermostat wires or 4 wire Infinity Control

Standby – no call

for unit operation

None

Off

Normal operation --- No call for cooling with 2---wire connection or indoor unit not

powered.

Cooling Operation

None

1, pause

Normal operation

System Communications

Failure

16

Communication with user interface lost. Check wiring to UI, indoor and outdoor

units

High Pressure

Switch Open

31

High pressure switch trip. Check refrigerant charge, outdoor fan operation and coils

for airflow restrictions.

Low Pressure

Switch Open

32

Low pressure switch trip. Check refrigerant charge and indoor air flow

Control Fault

45

Outdoor unit control board has failed. Control board needs to be replaced.

Brown Out

(24 v)

46

The control voltage is less than 15.5v for at least 4 seconds. Compressor and fan

operation not allowed until control voltage is a minimum of 17.5v. Verify control

voltage.

Outdoor Air Temp Sen-

sor Fault

53

Outdoor air sensor not reading or out of range. Ohm out sensor and check wiring

Outdoor Coil Sensor

Fault

55

Coil sensor not reading or out of range. Ohm out sensor and check wiring

Thermistors out

of range

56

Improper relationship between coil sensor and outdoor air sensor. Ohm out sen-

sors and check wiring.

Thermal Cutout

72

Compressor voltage sensed after start---up, then absent for 10 consecutive sec-

onds while cooling demand exists. Possible causes are internal compressor over-

load trip or loss of high voltage to compressor without loss of control voltage. The

control will continue fan operation and wait 15 minutes to attempt a restart. Fault

will clear when restart is successful, or low voltage power is cycled.

Contactor Shorted

73

Compressor voltage sensed when no demand for compressor operation exists.

Contactor may be stuck closed or there is a wiring error.

No 230V at

Compressor

74

Compressor voltage not sensed when compressor should be starting. Disconnect

may be open or contactor may be stuck open or there is a wiring error.

Thermal Lockout

82

Thermal cutout occurs in three consecutive cycles. Unit operation locked out for 4

hours or until 24v power recycled.

Low Pressure Lockout

83

Low pressure switch trip has occurred during 5 consecutive cycles. Unit operation

locked out for 4 hours or until 24v power recycled.

High Pressure

Lockout

84

High pressure switch trip has occurred during 5 consecutive cycles. Unit operation

locked out for 4 hours or until 24v power recycled.

24AN

B

6

Summary of Contents for Infinity 24ANB6

Page 1: ...ult in enhanced installation reliability or operation WARNING ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before installing modifying or servicing system main electrical disconnect switch must be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label CUT HAZARD Failure to follow this c...

Page 2: ...t must be reinstalled before unit is placed into operation A11380 Fig 2 Louver Spacer Location Install on a Solid Level Mounting Pad If conditions or local codes require the unit be attached to pad tie down bolts should be used and fastened through knockouts provided in unit base pan Refer to unit mounting pattern in Fig 3 to determine base pan size and knockout hole location For hurricane tie dow...

Page 3: ...LINE APPLICATIONS Over 80 ft 24 38 m Crankcase Heater Yes Yes Compressor Start Assist Capacitor and Relay Yes Yes Evaporator Freeze Thermostat Yes For non Infinity systems only No Liquid Line Solenoid Valve No See Long Line Application Guideline Low ambient Pressure Switch Yes For non Infinity system only No Support Feet Recommended No Thermal Expansion Valve TXV Hard Shutoff Yes Yes Winter Start ...

Page 4: ...hould be evacuated using the recommended deep vacuum method of 500 microns An alternate triple evacuation method may be used See triple evacuation method in Service Manual IMPORTANT Always break a vacuum with dry nitrogen Deep Vacuum Method The deep vacuum method requires a vacuum pump capable of pulling a vacuum of 500 microns and a vacuum gage capable of accurately measuring this vacuum depth Th...

Page 5: ...sory transformer as required Final Wiring Check IMPORTANT Check factory wiring and field wire connections to ensure terminations are secured properly Check wire routing to ensure wires are not in contact with tubing sheet metal etc Compressor Crankcase Heater When equipped with a crankcase heater furnish power to heater a minimum of 24 hr before starting unit To furnish power to heater only set th...

Page 6: ...by subcooling method If any adjustment is necessary adjust charge slowly and allow system to operate for 15 minutes to stabilize before declaring a properly charged system If the indoor temperature is above 80_F 26 67_C and the outdoor temperature is in the favorable range adjust system charge by weight based on line length and allow the indoor temperature to drop to 80_F 26 67_C before attempting...

Page 7: ... the LED will be turned OFF until the next valid communication Amber Status Light An amber colored STATUS light is used to display the operation mode and fault codes as specified in the troubleshooting section See Table 3 for codes and definitions NOTE Only one fault code will be displayed on the outdoor unit control board the most recent with the highest priority Crankcase Heater Operation The cr...

Page 8: ... is ON when outdoor coil temp outdoor air temperature 25_F 3 89_C or outdoor coil temp 80_F 26 67_C or if outdoor fan has been OFF for 30 minutes Fan is turned on to allow refrigerant system to stabilize S Low pressure switch is ignored for first 3 minutes during low ambient start up After 3 minutes if LPS trips then outdoor fan motor is turned off for 10 minutes with the compressor running If LPS...

Page 9: ...three consecutive cycles then unit operation is locked out for 4 hours and the appropriate fault code See Table 3 is displayed CONTACTOR SHORTED DETECTION If there is compressor voltage sensed when there is no demand for compressor operation the contactor may be stuck closed The control will flash the appropriate fault code Check the contactor and control box wiring NO 230V AT COMPRESSOR If the co...

Page 10: ...not reading or out of range Ohm out sensor and check wiring Thermistors out of range 56 Improper relationship between coil sensor and outdoor air sensor Ohm out sen sors and check wiring Thermal Cutout 72 Compressor voltage sensed after start up then absent for 10 consecutive sec onds while cooling demand exists Possible causes are internal compressor over load trip or loss of high voltage to comp...

Page 11: ... Fig 10 Resistance vs Temperature Chart Outdoor Coil Temp OCT Outdoor Air Temp OAT COMM STATUS A06314 Fig 11 Single Stage Control Board LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD SPLICE CONNECTION A10089 Fig 12 Infinity Control Four Wire Connection Wiring Diagrams See Thermostat Installation Instructions for specific unit combinations 24ANB6 ...

Page 12: ... operate CAUTION R R C W W1 Y Y2 G W Y C G R Y C 24VAC HOT 24VAC COM HEAT STAGE 1 HEAT STAGE 2 INDOOR FAN A C THERMOSTAT TYPICAL FURNACE or FAN COIL AIR CONDITIONER FIELD INSTALLED JUMPER WIRE R R C W W1 Y Y2 G W Y C G R Y C 24VAC HOT 24VAC COM HEAT STAGE 1 HEAT STAGE 2 INDOOR FAN A C THERMOSTAT TYPICAL FURNACE or FAN COIL AIR CONDITIONER A10091 LEGEND 24 V FACTORY WIRING 24 V FIELD WIRING FIELD S...

Page 13: ...manifold hose when charging into suction line with compressor operating S Manifold sets should be 700 psig high side and 180 psig low side with 550 psig low side retard S Use hoses with 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S Puron refrigerant as with other HFCs is only compatible with POE oils S Vacuum pumps will not remove moisture from oi...

Page 14: ...W Morris St D Indianapolis IN 46231 Printed in U S A Edition Date 08 11 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 24ANB6 2SI Replaces 24ANB6 1SI 24ANB6 ...

Reviews: