HN72ZA001: Installation Instructions
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
2
Connecting Wiring to RGAPA Unit
1. From the white quick-connect from the common on the
transformer, run a wire to the white lead in the electrical box on the
RGAPA unit.
2. From the black quick-connect from the 240V connection on the unit
transformer, connect to one side of the current sensing relay.
3. From current sensing relay, run out to the black connection at the
electrical box on the RGAPA unit.
4. Wrap the common wire on unit fan motor at least 3 times through
the current sensing relay
.
5. Secure all loose wiring with cable ties.
A12251
Fig. 1 – Quick-Connect Kit
A210032
Fig. 2 – Connection Wiring Diagram
A210033
Fig. 3 – Wrap Common through Relay