Table 14A — 19XR Waterbox Cover Weights — English (lb)
HEAT
EXCHANGER
WATERBOX
DESCRIPTION
FRAME 1
FRAME 2
FRAME 3
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
COOLER/
CONDENSER
NIH, 1 Pass Cover, 150 psig
177
204
320
350
320
350
NIH, 2 Pass Cover, 150 psig
185
218
320
350
320
350
NIH, 3 Pass Cover, 150 psig
180
196
310
340
310
340
NIH/MWB End Cover, 150 psig
136
136
300
300
300
300
NIH, 1 Pass Cover, 300 psig
248
301
411
486
411
486
NIH, 2 Pass Cover, 300 psig
255
324
411
518
411
518
NIH, 3 Pass Cover, 300 psig
253
288
433
468
433
468
NIH/MWB End Cover, 300 psig
175
175
400
400
400
400
HEAT
EXCHANGER
WATERBOX
DESCRIPTION
FRAME 4
FRAME 5
FRAME 6
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
COOLER/
CONDENSER
NIH, 1 Pass Cover, 150 psig
485
521
616
652
802
838
NIH, 2 Pass Cover, 150 psig
487
540
590
663
770
843
NIH, 3 Pass Cover, 150 psig
504
520
629
655
817
843
NIH/MWB End Cover, 150 psig
379
379
428
428
583
583
NIH, 1 Pass Cover, 300 psig
593
668
764
839
880
956
NIH, 2 Pass Cover, 300 psig
594
700
761
878
844
995
NIH, 3 Pass Cover, 300 psig
621
656
795
838
901
952
NIH/MWB End Cover, 300 psig
569
569
713
713
833
833
HEAT
EXCHANGER
WATERBOX
DESCRIPTION
FRAME 7 COOLER
FRAME 7 CONDENSER
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
COOLER/
CONDENSER
NIH, 1 Pass Cover, 150 psig
1392
1469
1205
1282
NIH, 2 Pass Cover, 150 psig
1345
1461
1163
1279
NIH, 3 Pass Cover, 150 psig
1434
1471
1222
1280
NIH/MWB End Cover, 150 psig
1022
1022
920
920
NIH, 1 Pass Cover, 300 psig
1985
2150
1690
1851
NIH, 2 Pass Cover, 300 psig
1934
2174
1628
1862
NIH, 3 Pass Cover, 300 psig
2009
2090
1714
1831
NIH/MWB End Cover, 300 psig
1567
1567
1440
1440
HEAT
EXCHANGER
WATERBOX
DESCRIPTION
FRAME 8 COOLER
FRAME 8 CONDENSER
Standard
Nozzles
Flanged
Standard
Nozzles
Flanged
COOLER/
CONDENSER
NIH, 1 Pass Cover, 150 psig
1831
1909
1682
1760
NIH, 2 Pass Cover, 150 psig
1739
1893
1589
1744
NIH, 3 Pass Cover, 150 psig
1851
1909
1702
1761
NIH/MWB End Cover, 150 psig
1480
1480
1228
1228
NIH, 1 Pass Cover, 300 psig
2690
2854
2394
2549
NIH, 2 Pass Cover, 300 psig
2595
2924
2269
2578
NIH, 3 Pass Cover, 300 psig
2698
2861
2417
2529
NIH/MWB End Cover, 300 psig
1923
1923
1767
1767
LEGEND
NIH
— Nozzle-in-Head
MWB — Marine Waterbox
NOTE: Weight for NIH 2-Pass Cover, 150 psig is included in the heat exchanger weights shown in Tables 10A and 10B.
88
Summary of Contents for HERMETIC CENTRIFUGAL LIQUID CHILLERS 19XR
Page 13: ...Fig 10 Control Panel Fig 11 Power Panel 13 ...
Page 47: ...Fig 25 19XR Leak Test Procedures 47 ...
Page 102: ......
Page 103: ......