72
APPENDIX A — DISPLAY TABLES (cont)
Configuration Mode and Sub-Mode Directory (cont)
SUB-MODE
ITEM
DISPLAY
ITEM DESCRIPTION
COMMENT
M.MST
MOTORMASTER
MMR.S
YES/NO
Motormaster Select
P.GAN
XX
Head Pressure P Gain
Default: 1
Range: 1 to 4
I.GAN
XX.X
Head Pressure I Gain
Default: 0.1
Range: -20 to 20
D.GAN
XX.X
Head Pressure D Gain
Default: 0.0
Range: -20 to 20
MIN.S
XX
Minimum Fan Speed
RSET
RESET COOL TEMP
CRST
X
Cooling Reset Type
Default: 0
0 = No Reset
1 = 4 to 20 mA Input
2 = Outdoor Air Temperature
3 = Return Temperature
4 = Space Temperature
MA.DG
XX.X
Δ
F
4-20 - Degrees Reset
Default: 0.0
Δ
F
Range: -30 to 30
Δ
F
RM.NO
XXX.X °F
Remote - No Reset Temp
Default: 125 F
Range: 0º to125 F
RM.F
XXX.X °F
Remote - Full Reset Temp
Default: 0 F
Range: 0º to125 F
RM.DG
XX.X °F
Remote - Degrees Reset
Default: 0.0
Δ
F
Range: -30 to 30
Δ
F
RT.NO
XXX.X
Δ
F
Return - No Reset Temp
Default: 10.0
Δ
F
Range: 0º to125 F
RT.F
XXX.X
Δ
F
Return - Full Reset Temp
Default: 0
Δ
F
Range: 0º to125 F
RT.DG
XX.X °F
Return - Degrees Reset
Default: 0.0
Δ
F
Range: -30 to 30
Δ
F
DMDC
X
Demand Limit Select
Default: 0
0 = None
1 = Switch
2 - 4 to 20 mA Input
3 = CCN Loadshed
DM20
XXX%
Demand Limit at 20 mA
Default: 100%
Range: 0 to 100%
SHNM
XXX
Loadshed Group Number
Default: 0
Range: 0 to 99
SHDL
XXX%
Loadshed Demand Delta
Default: 0%
Range: 0 to 60%
SHTM
XXX
Maximum Loadshed Time
Default: 60 minutes
Range: 0 to 120 minutes
DLS1
XXX%
Demand Limit Switch 1
Default: 80%
Range: 0 to 100%
DLS2
XXX%
Demand Limit Switch 2
Default: 50%
Range: 0 to 100%
SLCT
SETPOINT AND RAMP LOAD
RL.S
ENBL/DSBL
Ramp Load Select
Default: Enable
CRMP
ENBL/DSBL
Cooling Ramp Loading
Default: 1.0
Range: 0.3 to 2
SCHD
XX
Schedule Number
Default: 1
Range: 1 to 99
Z.GN
X.X
Deadband Multiplier
Default: 1
Range: 1 to 4
SERV
SERVICE CONFIGURATION
EN.A1
YES/NO
Enable Compressor A1
EN.A2
YES/NO
Enable Compressor A2
EN.A3
YES/NO
Enable Compressor A3
EN.B1
YES/NO
Enable Compressor B1
EN.B2
YES/NO
Enable Compressor B2
EN.B3
YES/NO
Enable Compressor B3
EN.FB
YES/NO
Enable Compressor FBack
REV.R
YES/NO
Reverse Rotation Enable
BCST
BROADCAST CONFIGURATION
T.D.B
ON/OFF
CCN Time/Date Broadcast
OAT.B
ON/OFF
CCN OAT Broadcast
G.S.B
ON/OFF
Global Schedule Broadcst
BC.AK
ON/OFF
CCN Broadcast Ack'er
Summary of Contents for GEMINI SELECT 38APD025
Page 6: ...6 Fig 4 Power Wiring Schematic 38APS APD025 030...
Page 7: ...7 Fig 5 Power Wiring Schematic 38APS040 050...
Page 8: ...8 Fig 6 Power Wiring Schematic 38APD040 060...
Page 9: ...9 Fig 7 Power Wiring Schematic 38APD070 100...
Page 10: ...10 Fig 8 Control Wiring Schematic 38APS025 050...
Page 11: ...11 Fig 9 Control Wiring Schematic 38APD025 060...
Page 12: ...12 Fig 10 Control Wiring Schematic 38APD070 100...
Page 85: ......