SPECIFICATIONS

MODEL FY4A

018

024

030

036

042

048

060

COIL

Puron

r

Refrigerant

Metering Device

TXV --- factory installed hard---shutoff, bi---flow type for heat pump application

TXV Size

2 ton

3 ton

4 ton

Rows/Fins Per In.

3 / 14.5

Face Area (Sq. Ft.)

2.23

2.97

3.46

4.45

5.93

7.42

Configuration

Slope

A

FAN

CFM (Nominal)

600

800

1000

1200

1400

1600

2000

Motor Type

PSC

PSC

PSC

PSC

PSC

PSC

PSC

Motor Hp

1/6

1/4

1/4

1/3

1/2

3/4

3/4

FILTER*

21---1/2” / 546 mm X

13” / 330 mm

16---3/8” / 417 mm

19---7/8” / 505 mm

23---5/16” / 585 mm

CABINET CONFIGURATION OPTIONS

1---piece

1---piece

1---piece

1---piece

1---piece

1---piece

Modular

*Filter must be field---supplied for FY4A units.

MODEL FA4C

018

024

030

036

042

048

060

R---22 Refrigerant

Metering Device

TXV --- factory installed hard---shutoff, bi---flow type for heat pump application

TXV SIZE

3 ton

5 ton

6 ton

COIL

Rows/Fins Per In.

3 / 14.5

Face Area (Sq. Ft.)

2.23

2.97

3.46

4.45

5.93

7.42

Configuration

Slope

A

FAN

CFM (Nominal)

600

800

1000

1200

1400

1600

2000

Motor Type

PSC

PSC

PSC

PSC

PSC

PSC

PSC

Motor Hp

1/6

1/4

1/4

1/3

1/2

3/4

3/4

FILTER*

21---1/2” / 546 mm X

13” / 330 mm

16---3/8” / 417 mm

19---7/8” / 505 mm

23---5/16” / 585 mm

CABINET CONFIGURATION OPTIONS

1---piece

1---piece

1---piece

1---piece

1---piece

1---piece

Modular

*Filter must be field---supplied for FA4C units.

PERFORMANCE DATA

AIRFLOW PERFORMANCE (CFM)

MODEL & SIZE

BLOWER

SPEED

TOTAL EXTERNAL STATIC PRESSURE

0.10

0.20

0.30

0.40

0.50

0.60

FY4A, FA4C

018

High

816

795

753

690

607

504

Low

633

620

588

538

468

380

FY4A, FA4C

024

High

1055

991

926

860

793

724

Low

934

878

818

754

686

614

FY4A, FA4C

030

High

1070

1032

978

908

822

721

Low

910

888

849

791

715

621

FY4A, FA4C

036

High

1352

1316

1273

1223

1167

1103

Low

1137

1112

1081

1043

998

946

FY4A, FA4C

042

High

1720

1668

1602

1521

1426

1316

Medium

1576

1540

1488

1421

1338

1239

Low

1388

1367

1330

1278

1209

1124

FY4A, FA4C

048

High

1902

1824

1743

1659

1571

1479

Medium

1830

1763

1690

1611

1527

1436

Low

1625

1584

1531

1465

1387

1296

FY4A, FA4C

060

High

2128

2050

1965

1875

1778

1674

Medium

1959

1898

1829

1750

1663

1566

Low

1748

1709

1659

1598

1525

1442

--- Shading --- Airflow outside 450 cfm/ton.

NOTES

:

1. Airflow based upon dry coil at 230v with factory---approved filter and electric heater (2 element heater sizes 18 thru 36, 3 element heater sizes 42 thru 60).

Airflow at 208 volts is approximately 10% lower.

2. To avoid potential for condensate blowing out of drain pan prior to making drain trap:

Return static pressure must be less than 0.40 in. wc.

Horizontal applications of 042 --- 060 sizes must have supply static greater than 0.20 in. wc.

3. Airflow above 400 cfm/ton on 048---060 size could result in condensate blowing off coil or splashing out of drain pan.

FY4

A

/F

A

4C

Summary of Contents for FA4C series

Page 1: ...al check valve for reverse flow bi pass capability All units come with solid state fan controls 1 in thick insulation with R value of 4 2 super quiet multispeed motors and fully wettable coils Units c...

Page 2: ...speed motor in 042 through 060 sizes S Cooling controls S Time delay relay TDR S Pre painted galvanized steel cabinet gray S High density super thick R 4 2 insulation S Newly improved filter rack area...

Page 3: ...uronr Refrigerant 4 Multipoise C N 208 230v 1ph 60Hz B Modular C Factory Disconnects F Single piece 018 18 000 024 24 000 030 30 000 036 36 000 042 42 000 048 48 000 060 60 000 T00 ArmorCoatt 000 No H...

Page 4: ...12 7 16 316 12 5 16 313 10 7 16 265 12 305 024 030 Slope 47 11 16 1211 5 17 5 8 448 15 3 4 400 15 5 8 397 15 3 8 391 17 432 036 Slope 53 7 16 1357 21 1 8 537 19 1 4 489 19 1 8 486 19 3 16 487 19 483 0...

Page 5: ...FY FA COIL TYPE F G in mm in mm 018 Slope 18 1 8 460 18 5 8 473 024 030 Slope 23 1 8 587 23 5 8 600 036 Slope 26 15 16 684 27 1 2 699 042 A 23 7 16 593 23 1 8 587 048 A 27 1 4 692 26 15 16 684 060 A...

Page 6: ...lar cabinet C Disconnect F Single piece cabinet 10th digit 0 Standard copper coil T ArmorCoatt ODS CATALOG ORDERING NO FACTORY INSTALLED HEAT kW NOMINAL COOLING CAPACITY BTUH DIMENSIONS SHIPPING WEIGH...

Page 7: ...lied for FA4C units PERFORMANCE DATA AIRFLOW PERFORMANCE CFM MODEL SIZE BLOWER SPEED TOTAL EXTERNAL STATIC PRESSURE 0 10 0 20 0 30 0 40 0 50 0 60 FY4A FA4C 018 High 816 795 753 690 607 504 Low 633 620...

Page 8: ...2 0 04 38 28 0 04 28 23 0 05 62 17 52 41 0 05 44 37 0 05 36 33 0 05 28 28 0 11 24 24 0 26 1200 72 22 87 43 0 00 78 39 0 00 68 34 0 03 57 30 0 04 46 25 0 05 67 19 72 44 0 05 63 40 0 05 53 35 0 06 42 31...

Page 9: ...30 0 04 34 26 0 04 24 21 0 06 62 17 48 39 0 05 40 35 0 05 32 31 0 06 26 26 0 16 22 22 0 31 1200 72 22 79 39 0 00 71 35 0 03 62 31 0 04 52 27 0 05 41 23 0 05 67 19 65 41 0 05 57 37 0 05 48 33 0 06 38 2...

Page 10: ...970 970 920 1040 042 1225 1225 1225 1225 1225 1225 048 1400 1400 1400 1400 1400 1400 1400 1400 060 1750 1750 1750 1750 1750 1750 1750 1750 Indicates medium speed blue All other motor speeds at low ta...

Page 11: ...57 4 55 4 53 4 49 4 048 1600 0 25 69 0 65 0 61 0 58 0 56 0 54 0 50 0 060 2000 0 25 70 0 66 0 62 0 59 0 57 0 55 0 51 0 Est sound power levels have been derived using the method described in the 1987 A...

Page 12: ...55 4 60 60 18 1 20 0 22 6 25 0 25 25 NOTE All units 208 230 single phase 60 Hz MCA Minimum Circuit Amps FLA Full Load Amps ELECTRICAL DATA FOR UNITS WITHOUT FACTORY INSTALLED HEATERS MODEL NO MTR HP...

Page 13: ...None 37 6 41 5 55 5 60 4 6 6 10 8 60 70 76 77 KFCEH3201F20 20 15 0 1 Fuse 72 3 79 9 36 2 40 0 36 2 40 0 98 9 108 4 53 8 58 5 45 3 50 0 3 2 6 6 8 8 8 6 10 10 10 10 100 110 60 60 50 50 85 109 78 80 59 5...

Page 14: ...are used in downflow applications 4 Single Point Wiring Kit The single point wiring kit acts as a jumper between L1 and L3 lugs and between the L2 and L4 lugs This allows the installer to run two heav...