background image

CAUTION: The conversion of the fan coil to downflow requires special procedures for the condensate drains on both

A-coil and Slope units. The vertical drains have an overflow hole between the primary and secondary drain holes. This hole
is plugged for all applications except downflow, but must be used for downflow. During the conversion process, remove the
plastic cap covering the vertical drains only and discard. Remove the plug from the overflow hole and discard. At completion
of the downflow installation, caulk around the vertical pan fitting to door joint to retain the low air leak performance of the
unit. Failur to follow this CAUTION could result in minor personal injury or product and property damage.

Units are equipped with primary and secondary 3/4-in. FPT drain connections. For proper condensate line installations see Fig. 1, 2, 4, 5, and 6.
To prevent property damage and achieve optimum drainage performance, BOTH primary and secondary drain lines should be installed and include
properly-sized condensate traps (See Fig. 18). Factory-approved condensate traps are available. It is recommended that PVC fittings be used on
the plastic condensate pan. Finger-tighten plus 1-1/2 turns. Do not over-tighten. Use pipe dope.

CAUTION: Shallow, running traps are inadequate and DO NOT allow proper condensate drainage. (See Fig. 19.)

Failure to follow this CAUTION could result in minor personal injury or product and property damage.

NOTE:

When connecting condensate drain lines, avoid blocking filter access panel, thus preventing filter removal. After connection, prime both

primary and secondary condensate traps.

Fig. 15—Transformer Connections

A94067

230

C

208

BRN
RED

YEL
BLK

SECONDARY

PRIMARY

Fig. 16—Fan Coil Relay and Speed Tap Terminal

A97529

INSULATING  CAP  (2)

MOTOR  SPEED

TAP  LEADS

COMMON  YELLOW

FAN  DECK

WRAPPER

SPEED  TAP
TERMINAL

PCB

FAN  RELAY

SINGLE SPADE

—11—

Summary of Contents for FA4B

Page 1: ...se of this the units need special attention in the condensate pan and drain connection area and when brazing tubing These units are available for systems of 18 000 through 60 000 Btuh nominal cooling...

Page 2: ...ith access panels facing up or down The FH4B003 and 004 size units equipped with accessory cooling coils are not approved for horizontal applications All other units are factory built for horizontal l...

Page 3: ...l on coil support rail on right side of unit 6 Convert air seal assembly for horizontal right a Remove air seal assembly from coil by removing 4 screws See Fig 5 b Remove air splitter B from coil seal...

Page 4: ...om Step 10 in the right side of the coil door making sure that the cap snaps and seats cleanly on the back side of the coil door Make sure no insulation interferes with seating of the cap Fig 3 Remova...

Page 5: ...vapor barrier Units equipped with 20 30kw electric heaters require a 1 in clearance to combustible materials for the first 36 in of supply duct Ductwork Acoustical Treatment Metal duct systems that d...

Page 6: ...h located within sight from and readily accessible from the unit Fig 6 A Coil in Horizontal Left Application Factory Ready A00072 A B C FACTORY SHIPPED HORIZONTAL LEFT APPLICATION AIR SEAL ASSEMBLY HO...

Page 7: ...voltage connections between the thermostat the unit and the outdoor equipment If the thermostat is located more than 100 ft from the unit as measured along the low voltage wire use No 16 AWG color co...

Page 8: ...d in control box E Minimum CFM and Motor Speed Selection Units with or without electric heaters require a minimum CFM Refer to the unit wiring label to ensure that the fan speed selected is not lower...

Page 9: ...nection first 1 Cut tubing to correct length 2 Insert tube into sweat connection on unit until it bottoms 3 Braze connection using silver bearing or non silver bearing brazing materials Do not use sol...

Page 10: ...x nut then tighten with wrench 1 2 turn Do not exceed 30 ft lbs PROCEDURE 7 CONDENSATE DRAINS To connect drains the cap openings must be removed Use a knife to start the opening near the tab and using...

Page 11: ...ee Fig 1 2 4 5 and 6 To prevent property damage and achieve optimum drainage performance BOTH primary and secondary drain lines should be installed and include properly sized condensate traps See Fig...

Page 12: ...l as possible See Fig 20 Make sure that the outlet of each trap is below its connection to the condensate pan to prevent condensate from overflowing the drain pan Prime all traps test for leaks and in...

Page 13: ...or W energizes electric heat relay s which completes circuit to heater element s When W is de energized electric heat relay s open turning off heater elements When G is de energized there is a 90 sec...

Page 14: ...d minimize possible equipment failure it is essential that periodic maintenance be performed on this equipment Consult your local dealer as to the proper frequency of maintenance contract Fig 21 Wirin...

Page 15: ...required if filter replacement or cleaning on a monthly basis Fig 23 Wiring Layout of Humidifier to Fan Coil with Electric Heat A95295 R G W Y THERMOSTAT R G W2 W3 E C FAN COIL CONTROL C Y AIR COND HU...

Page 16: ...2003 CAC BDP 7310 W Morris St Indianapolis IN 46231 imfa4b02 16 Book Tab 1 4 3d 2e Catalog No 63FA 4B1...

Reviews: