background image

hot water and detergent. Be careful not to disturb balance weights
(clips) on blower wheel vanes. Do not drop or bend wheel as
balance will be affected.

FG3A SERVICE AND TROUBLESHOOTING

Step 1—Service

MOTOR

Ball bearing oilers are provided on blower motor. Use electric
motor oil or SAE 10 or 20 nondetergent oil. Check motor mount
bracket and base bolts. Tighten as required.

BLOWER

Check ball bearings for wear. Ball bearings are self-aligning and
grease packed. Replace as required. Check thrust collars for end
play and alignment of wheel. Check blades for accumulation of
dirt. Clean as required. Check mounting brackets, base bolts, and
isolation material.

See Fig. 37 for diagram of internal wiring for blower coil
assembly. Control box (standard 4-in. junction box) is mounted on
refrigerant connection side of unit. All leads pass through strain
relief where they enter control box. Wiring inside cabinet is
located so it does not come in contact with moving parts or sharp
edges.

PULLEY AND BELTS

Check belt tension and pulley alignment. (See Fig. 38.) Belt
tension is adjusted by motor tailpiece bolt. A deflection of about
3/4 in. to 1 in. per foot of span should be obtained by pressing belt
firmly. Lock adjusting bolt in position after adjustment is made.
Align pulley grooves by locating motor pulley on motor shaft or by
moving entire motor along motor mounting bracket. Adjust blower
speed by loosening setscrew in outer (moveable) pulley face and
turning this face (half or full turns) so that adjusting setscrew is
positioned precisely over the flat on pulley hub. Speed is reduced
by adjusting pulley faces so they are further apart; speed is
increased with faces closer together. Check pulley setscrews and
bolts.

CLEANING OR REPLACING REFRIGERANT
FLOW-CONTROL DEVICE

Refer to Fig. 36 and instructions given in FD3A Service and
Troubleshooting section above.

Step 2—Maintenance

Disconnect electrical power to all circuits before servicing
unit. Failure to do so may result in personal injury from
electrical shock or moving parts.

As with any mechanical equipment, personal injury can result
from sharp metal edges. Be careful when removing parts.

RETURN-AIR FILTER

To clean or replace air filter, remove screws and filter access door.
Slide out filter. For washable type filters, clean with hot soapy
water. Rinse clean and let dry.

New filters are available from a local distributor. Place filter in slot
with filter arrow facing direction of airflow. Replace filter access
doors with screws previously removed.

Never operate unit without a filter or with filter access door
removed. Damage to blower motor may result.

COIL, DRAIN PAN, AND CONDENSATE DRAIN

Disconnect electrical power before removing any access
panels or electrical shock may result.

The coil is easily cleaned when dry. To check or clean coil, remove
coil access panel. If coil is coated with dirt or lint, vacuum with a
soft brush attachment.

Be careful not to bend fins. If coil is coated with oil or grease, it
may be cleaned with mild detergent and water solution. Rinse coil
with clean water. Be careful not to splash water on insulation or
filter.

Check drain pan and condensate drain at same time cooling coil is
checked. Clean drain pan and condensate drain by removing any
foreign matter from pan. Check for rust and holes. Flush pan and
drain tube with clear water. If drain is restricted, clean with
high-pressure water. If this does not work, use a plumber’s snake
or similar probe device. Repitch drain pan to promote proper
drainage.

FA4A, FB4A, FC4B, AND FX4A SMART HEAT

CIRCUIT BOARD FUNCTION AND TROUBLESHOOTING

Step 1—PCB Component Layout, Description,
and Function

NOTE:

All voltages are AC unless otherwise specified.

1. The low-voltage terminal board is used to connect indoor

thermostat to low, 24-v side of transformer and to serve as a
junction between indoor thermostat and outdoor section.

a. R terminal is used to connect secondary side of transformer

to thermostat and outdoor unit. R is fused.

b. C terminal is used to connect transformer secondary

common for thermostat and outdoor unit.

c. Y terminal provides input signal from thermostat signaling

heat pump operation.

Fig. 37—Wiring Schematic

A91151

BLOWER

MOTOR

GROUND

UTILITY

BOX

GROUND
LEAD

LINE

Fig. 38—Checking Pulley Alignment and Tightness

A91150

1

3

4

BELT  ADJUSTMENT

PULLEY  ALIGNMENT

MUST BE
PARALLEL
FOR PROPER
ALIGNMENT

46

Summary of Contents for FA4ANF

Page 1: ...ing FK4C FV4A 40FKA Motor and Controls 33 Accessories 35 THERMOSTATIC EXPANSION VALVES TXV 36 Problems Affecting TXV 36 PISTON BODY CLEANING OR REPLACEMENT 36 LIQUID TUBE STRAINER 37 FA FB FC FK COIL...

Page 2: ...1 The low voltage stripped leads are used to connect the 24 v side of transformer to indoor thermostat and outdoor section 2 A 5 amp fuse is used to protect the low voltage transformer secondary 3 The...

Page 3: ...w 2 Downflow 3 Horizontal 4 Multipoise 5 Upflow Downflow Airflow 018 1 1 2 Ton 024 2 Ton 001 Multi Tons 002 Multi Tons Etc Cooling Size 10th 11th 12th Positions Fan Coil 005 010 Etc Heating Size KW 6t...

Page 4: ...gether If independent staging is desired consult outdoor ther mostat installation instructions or corporate thermostat instruc tions Step 3 Troubleshooting the Printed Circuit Board Use wiring schemat...

Page 5: ...itch Black wire should be connected to pin number 7 of plug and to sequencer relay number 1 3 Check incoming high voltage power leads If these are not receiving power system cannot function If Transfo...

Page 6: ...de DC power for the fan relay and the first stage of electric heat W2 W3 or E Fig 3B FF1D Typical Wiring Diagram A98229 SEE NOTE 7 F 1 NO NC SPT OUTDOOR UNIT G PCB BLK C INDOOR THERMOSTAT BARRIER C T...

Page 7: ...primary or high side of the transformer The blue wire is connected to T3 for 208 v applications The red wire is connected to T3 for 230 v applications Units are factory wired at 230v The T2 terminal i...

Page 8: ...EWER ELEMENTS AND COMPONENTS 9 1 PHASE HEATERS ARE SHOWN WIRED FOR SINGLE SUPPLY CIRCUIT 10 USE 60 AMP CLASS K FUSES ONLY FOR REPLACEMENT 11 3 SPEED MOTOR SHOWN OPTIONAL 2 SPEED MOTOR USES HI BLK AND...

Page 9: ...4 Replace low voltage fuse with no greater than 5 amp fuse 5 Use 60 amp class K fuses only for replacement 6 3 speed motor shown Optional 2 speed motor uses HI BLK and LOW BLU or RED 7 Connect R to R...

Page 10: ...Fig 10 shows proper connection for latent capacity control kit Note that it is connected in the same manner as 2 speed fan relay kit but with relay connected to humidistat orange wires c Time delay of...

Page 11: ...ck sequencer number 1 and the plug s wiring the yellow wire should be connected to pin number 9 of the plug and the limit switch A black wire should be connected to pin number 7 of the plug and to seq...

Page 12: ...FUSE MAX FAN TDB YEL LS 5 HTR5 BLK BLK 10 9 YEL FU5 FU6 SEQ 3 LS 6 HTR6 BLK BLK 12 11 YEL LS 5 HTR5 BLK BLK 6 5 YEL FU3 FU4 SEQ 2 LS 4 HTR4 BLK BLK 8 7 YEL LS 1 HTR1 BLK BLK BLU MED BLU MED RED LO RED...

Page 13: ...G RED FR LOW MTR SPD HI MTR SPD FAN COMMON UNUSED LEAD BLK 208 240 VAC COM NO NC F3 F2 L2 F1 O Y R T R A N S F O R M E R A C L I N E T 1 T 2 C O M M O N C O M M O N D U M M Y T 3 L 2 L 1 F 1 F 2 F 3 F...

Page 14: ...LD POWER WIRING AUX 1 AUX 2 F4 24 VDC RED FR LOW MTR SPD HI MTR SPD FAN COMMON UNUSED LEAD BLK 208 240 VAC NO C HST ORG ORG COM NO NC F3 F2 L2 F1 O Y R T R A N S F O R M E R A C L I N E T 1 T 2 C O M...

Page 15: ...WIRING FIELD POWER WIRING AUX 1 AUX 2 F4 24 VDC TDR YEL FAN COMMON UNUSED LEAD UNUSED LEAD BLK 208 240 VAC COM NO NC F3 F2 L2 F1 O Y R T R A N S F O R M E R A C L I N E T 1 T 2 C O M M O N C O M M O...

Page 16: ...NG AUX 1 AUX 2 F4 24 VDC TDR FR ORG ORG RED YEL FAN COMMON UNUSED LEAD LOW MTR SPD HI MTR SPD BLK 208 240 VAC COM NO NC F3 F2 L2 F1 O Y R COM NO NC T R A N S F O R M E R A C L I N E T 1 T 2 C O M M O...

Page 17: ...MAX AUX2 L1 EAC1 FAN R L G E C O Y W2 INDOOR THERMOSTAT YEL YEL BLK LS 3 HTR3 BLK BLK 6 5 YEL FU1 FU2 FU3 FU4 SEQ 2 LS 4 HTR4 BLK BLK 8 7 YEL LS 1 HTR1 BLK BLK 2 1 YEL SEQ 1 LS 2 HTR2 BLK BLK 4 3 SEQ...

Page 18: ...incoming high voltage power leads If these are not receiving power the system cannot function If the PCB has high voltage applied to it 1 Check the low voltage transformer leads R and C Make sure they...

Page 19: ...ensure that it is replaced with a limit switch of identical opening temperature and closing differential Limits switches are typically color coded to identify their range KFA AND KFB SEQUENCER The seq...

Page 20: ...ters or undersized duct 2 Check blower motor and wheel for proper operation Exces sive current draw of motor will cause internal overload to trip 3 The fan speed may be low FAN COIL DESCRIPTION AND TR...

Page 21: ...eed A circuit from R to Y1 is also required for 2 speed high The Y Y2 signal is sent directly to ICM2 COOLING MODE TWO SPEED LOW Thermostat closes circuits R to Y1 and R to O heat pump only The Y1 sig...

Page 22: ...or erratic motor operation can result TRANSFORMER MOTOR AND ELECTRIC HEATER POWER CONNECTIONS The high voltage 230 vac power input to board is provided through electric heater connector pins 7 and 9...

Page 23: ...or heat pump size is largest unit meant for application with model of fan coil purchased The installer needs to select air conditioner or heat pump size to ensure that airflow delivered falls within p...

Page 24: ...UX2 Low voltage output for auxiliary option 24 vdc 0 187 X 0 032 M1 Common connection to blower motor T1 Common connection for transformer RED Common to R screw terminal and SEC2 Table 4 Connections o...

Page 25: ...Blown Diodes If diodes are blown it is probable that electric heater plug is miswired Correct miswiring NOTE Board will need to be replaced if diode is bad If Traces Are Overheated on Back of PCB Usua...

Page 26: ...L RECP 3 RECP 4 ICM BRN YEL RED VIO RED ORN BRN VIO ORN GRY BLU BLK BLK 1 9 2 10 3 11 4 12 5 13 6 14 7 15 8 16 PLUG 2 BLK YEL ORN GRN RED BRN VIO SEE NOTE 3 SEE NOTE 2 HPTB E Y1 Y0 W2 O L R NOTES 1 Us...

Page 27: ...g and turn on power Check for 24v between pin 1 and pin 12 on the 16 pin plug See Fig 19 If no voltage is present replace wiring harness If voltage is present jumper screw terminal R Y Y2 on circuit b...

Page 28: ...uct Data for static pressure limits The ICM2 is pre programmed and contains airflow tables for all modes of operation Blower characteristics requested airflow torque and speed are known from laborator...

Page 29: ...let Wire AC HP Size Blue Wire Type Orange Wire AC HP CFM Adjust Black Wire AC HP Time Delay Grey Wire Continous Fan Yellow Wire Step 11 Sequence of Operation CONTINUOUS FAN MODE The thermostat closes...

Page 30: ...R to Y1 is also required for 2 speed high Y Y2 and Y1 signal is sent to ICM2 Thermidistat call for Comfort Heat will occur between 10 and 40 F outdoors and opens circuit from R to G ICM adjusts airfl...

Page 31: ...rness to motor The C side of low voltage control power circuit is connected by printed circuit runs to motor connector pins 9 10 and 11 then through motor control harness to motor LOW VOLTAGE CIRCUIT...

Page 32: ...urchased The installer needs to select air conditioner or heat pump size to ensure that airflow delivered falls within proper range for size of unit installed in all operational modes See Fig 24 SYSTE...

Page 33: ...When there is a high current drawn on transformer it is most likely because transformer has been shorted or system is trying to draw more va than transformer rating allows When fuse blows because of h...

Page 34: ...BLK WHT PLUG 3 230V 208V Com YEL BLK BLK YEL ICM RECP 4 RECP 3 GRY 1 BRN 12 11 10 9 8 7 6 5 4 3 2 1 5 4 3 2 1 G R N Y E L B L K W H T RED VIO V I O R E D B R N O R N BRN PLUG 1 G R Y 16 15 14 13 12 11...

Page 35: ...air cleaner when G or W are present See Fig 28 FK4C FV4A AND 40FKA DE HUMIDIFY MODE NOTE Humidistat must open on humidity rise Latent capacities for systems using the FK4C FV4A and 40FKA fan coils ar...

Page 36: ...m with which the pin carrier spring pressure closes valve The refrigerant flow is effectively stabilized to load demand with negligible change in superheat The bi flow TXV is used on split system heat...

Page 37: ...ndensate drain pan Remove fitting panel 7 Remove any shipping clips including horizontal pan clip and slide coil condensate pan assembly out of unit 8 Upflow or Horizontal Applications Only Remove hor...

Page 38: ...nditioners and Heat Pumps Service Manual for further information FX4A AND FV4A COIL CONDENSATE PAN REMOVAL AND REPLACEMENT PURON REFRIGERANT Step 1 A Coil Units If it is determined that system does no...

Page 39: ...12 Remove coil top seal See Fig 32 13 Install new coil into condensate pan using 2 original screws and 2 support columns NOTE Correct coil position in condensate pan is essential to reliable operatio...

Page 40: ...bolts Make sure mount or motor is grounded to blower housing 4 Locate blower wheel setscrew over flat on motor shaft Rotate wheel in housing It should not rub housing and should be centered in inlet o...

Page 41: ...LK BLK HTR LS YEL VIO BLK BLK RED BLU TRANS DISCONNECT SEE RATING PLATE FOR VOLTS HZ FIELD POWER SUPPLY CHASSIS GROUND RED VIO ORN BRN BRN CHASSIS GROUND RED ORN T A P2 B BRN BRN 5 6 SEQ CHASSIS GROUN...

Page 42: ...hanical equipment personal injury can result from sharp metal edges Be careful when removing parts AIR FILTER To clean or replace air filter grasp it at bottom and lift it out of unit Clean filter usi...

Page 43: ...n lead is yellow NOTE Unused fan speed leads must be tapped off to prevent direct short to cabinet surface The motor is turned on through 2 different routes The first occurs when thermostat calls for...

Page 44: ...SFORMER PIGTAILS BLUE 208V RED 230V INSULATE UNUSED LEAD 2 FAN MOTOR PIGTAILS RED LOW BLACK HIGH INSULATE UNUSED LEAD 3 FAN MOTOR THERMALLY PROTECTED 4 SUITABLE FOR USE WITH COPPER OR COPPER CLAD ALUM...

Page 45: ...edges Be careful when removing parts The minimum maintenance requirements for this equipment are as follows 1 Inspect and clean or replace field supplied air filter each month or as required 2 Inspec...

Page 46: ...can result from sharp metal edges Be careful when removing parts RETURN AIR FILTER To clean or replace air filter remove screws and filter access door Slide out filter For washable type filters clean...

Page 47: ...ally connected to equip ment ground Step 2 Unit Functions TRANSFORMER NOTE Terminals T1 T2 if used and T3 are wired to primary or high side of transformer The 208 v terminal or blue wire if transforme...

Page 48: ...elements For troubleshooting a service LED indicates condition of PCB See Table 11 for LED flash codes Step 4 Electrical Operating Sequences and Troubleshooting NOTE Refer to Table 12 for proper inpu...

Page 49: ...ergized control energizes fan motor It may run on high or low speed depending on its operation in previous cycle Compressor operation in current cycle is monitored by the smart control to determine wh...

Page 50: ...ircuit of sequencer relay place voltmeter leads across sequencer relay terminal 4 of sequencer relay 1 and terminal 4 of limit switch 3 The reading should be 208 230v and heater should be energized If...

Page 51: ...uld be designed to detect HFC refrigerant Puron R 410A as other HFC s is only compatible with POE oils Vacuum pumps will not remove moisture from oil Do not use liquid line filter driers with rated wo...

Page 52: ...YEL COM CAP BRN FM BRN GRN YEL GND BLK HI BLU MED BRN RED TRAN MOTOR SPEED AT 20 KW FAN COIL SIZE MINIMUM MOTOR LO SPEED TAP SELECTION NOTES LS2 LS1 RED SEQ3 SEQ2 SEQ 2 9 10 BLK 7 LS2 YEL 8 BLK HTR2...

Reviews: