9. Cut the vaporizer refrigerant return line as shown (see
Fig. 17, item 13, or Fig. 18, item 8).
10. Disconnect all sensors with cables that cross from
the condenser side of the machine to the cooler side
including:
a. Evaporator refrigerant liquid temperature sensor.
b. Entering and leaving chiller liquid temperature
sensors. See Fig. 20.
c. Evaporator pressure sensor (not shown).
11. Disconnect the tubesheet mounting brackets from the
vessel connectors on the tube cooler tubesheet.
12. Cover all openings.
13. Rig the cooler away from the condenser/compressor.
NOTE: To reassemble, follow steps in reverse order. Connect
sensors and cables after major components have been secured
to reduce the risk of damaging them.
19
18
17
16
15
14
5
13
12
11
10
9
8
7
5
6
5
4
3
2
1
1 — Suction Elbow (Unbolt)
11 — VFD Cooling Drain Line
2 — Vaporizer Vent Line (Unbolt)
12 — Oil Reclaim Line (Cut)
3 — Motor Cooling Line (Unbolt)
13 — Vaporizer Hot Gas Return Line (Cut)
4 — Motor Cooling Drain Line (Cut)
14 — Discharge Isolation Valve (Optional)
5 — Tubesheet Mounting Bracket
15 — Condenser Relief Valves
6 — Bearing Oil Drain Line
16 — Discharge Temperature Sensor
7 — Support Plate
17 — Discharge Pipe Assembly Relief Valve (Unscrew)
8 — In-Line Economizer Orifice Plate
18 — Discharge Pressure Sensor
9 — Cooler Liquid Feed LIne (Unbolt)
19 — Discharge Pressure Switch
10 — Hot Gas Bypass Line (Cut)
Fig. 17 — Cooler/Discharge Pipe Assembly Removal (Unit with R Compressor Shown)
a23-1560
Summary of Contents for EVERGREEN 23XRV
Page 53: ...53 Fig 60 Typical Field Wiring Schematic LF 2 VFD Shown NOTE See Notes for Fig 60 on page 56 ...
Page 54: ...54 Fig 60 Typical Field Wiring Schematic LF 2 VFD Shown cont a23 1585 ...
Page 55: ...55 Fig 60 Typical Field Wiring Schematic LF 2 VFD Shown cont a23 1586 ...
Page 60: ...60 Fig 63 23XRV Controls Schematic LF 2 ...
Page 64: ...64 FROM PREVIOUS PAGE Fig 67 23XRV Controls Schematic Rockwell Standard Tier VFD Shown cont ...