background image

5

between wall control and ERV/HRV connector following color
code. (See Fig. 5 and 10.) Replace top cover assembly.

NOTE

: ERV/HRV wall control and circuit board operate on

12VDC.

 YELLOW

Y

R

G B

 RED

 GREEN

 BLACK

A98383

Fig. 10 -- Typical Wall Control

Operation

The Standard and Latent wall controls have 4 basic modes of
operation, OFF, LOW, HIGH, and INTERMITTENT. Be sure that

all modes of operation are fully functional. See Table 1 indicating

standard control operation.

1. With switch off, ERV/HRV is inoperative and the LED is

out.

2. With switch on LOW, ERV/HRV continuously exchanges

air with outside. If control is satisfied, blower will run in

low speed, otherwise, blower will run on high speed. The
LED is illuminated all the time.

3. With switch on INTERMITTENT, the ERV/HRV ex-

changes air with outside on high--speed blower, and unit

shuts down when control is satisfied. The ON LED is illu-
minated all the time, and AIR EXCHANGE LED is illumi-
nated only when unit is running.

Humidity Selector

The humidity selector is a built--in control designed to properly
control the level of humidity in the house during the winter and

summer months. This control helps avoid condensation problems

in upper northern regions where indoor humidity is a problem
during the winter season.

NOTE

: This control is not to be confused with a dehumidistat

used during the summer months to control high relative indoor
humidity.
Table 2 recommends humidity levels to avoid condensation.

Table 2 – Recommended Humidity Levels

OUTSIDE

TEMPERATURE

DOUBLE---PANE

WINDOWS

TRIPLE---PANE

WINDOWS

50

°

F / 10

°

C

55%

65%

32

°

F / 0

°

C

45%

55%

14

°

F / ---10

°

C

35%

45%

---4

°

F / ---20

°

C

30%

45%

---22

°

F / ---30

°

C

25%

35%

OneTouch Control

The OneTouch Control can be used as the primary wall control for
the ERV/HRV. This control will step through the modes of

operation with consecutive presses of the button. The LED

indicates which mode is currently selected, Off, Intermittent, Low,
or High.

NOTE

: OneTouch Control does not have a humidity selector.

NOTE

: OneTouch Intermittent mode exchanges air on low speed

for 20 minutes per hour.

Latent Control

NOTE

: For Latent Controls used with ERV;s, to ensure highest

degree

of

humidity

control

in

cooling

season,

the

INTERMITTENT mode should be used.

Integrated Control

All units are equipped with an integrated control, located under the
unit, in front of the electrical compartment. Use the push button (1)

to control the unit. The LED (2) will then shows on which mode

the unit is in. Integrated Control overrides Wall Control function.
When LED is off, ventilator responds to Wall Control command.

See Fig. 11.

  WARNING 

Risk of electric shock. Before performing  

any maintenance or servicing, always  

disconnect the unit from its power source. 

 AVERTISSEMENT 

Danger d’électrocution. Débranchez  

toujours l’appareil avant d’entreprendre  
des travaux d’entretien ou de réparation. 

CAUTION 

Unscrew both screws to open the electrical 

compartment. To completely remove, detach 

 from its retention wire inside. 

  ATTENTION 

  Dévisser les deux vis pour ouvrir le compartiment 

 électrique. Pour retirer complètement, le 

détacher de son fil de rétention intérieur.  

No light            OFF or remote controled 
Amber light             LOW speed 
Green ligh              HIGH speed 
Blinking light       See User Manual 
Sans lumière       Arrêté ou contrôlé
                            par contrôle mural 
Lumière ambre        Basse vitesse 
Lumière verte          Haute vitesse 
Clignotant         Voir guide d’utilisation 

1 2

A07260

Fig. 11 -- Integrated Control

Refer to table below to see how to operate the unit using its
integrated control.

PRESS ON PUSH

BUTTON

LED COLOR

RESULTS

Once

Amber

Unit is on Low

Speed

Twice

Green

Unit is on High

Speed

Three Times

No Light

Unit is OFF

If a problem occurs during the unit operation, its integrated control
LED (2) will blink. The color of the blinking light depends on the

type of error detected. Refer to Troubleshooting for further details.

NOTE

: The ERV/HRV may be controlled using the Infinity

system control. The ERV/HRV may be connected using either a
NIM or a 4--Zone Damper Module. See the appropriate instructions
if using the NIM or a 4--Zone Damper Module for connection
instructions.
The Infinity system control will simultaneously control the

ERV/HRV and the indoor blower.
Push Button Timers may be used and are connected to the

ERV/HRV. However, the Infinity system should be set to

continuous fan to ensure that the fresh air is circulated in the home.
In a Zoned System, at least one zone should be set to continuous

fan.

ER

V

/HR

V

Summary of Contents for ERVCCSHB1100

Page 1: ...staller or agency must use factory authorized kits or accessories when modifying this product Refer to the individual instructions packaged with kits or accessories when installing Follow all safety codes Wear safety glasses protective clothing and work gloves Have a fire extinguisher available Read these instructions thoroughly and follow all warnings or cautions included in literature and attach...

Page 2: ...m unit should be located next to or close to the indoor equipment COMPONENT DESCRIPTION The following listed items are components of ERVCCSHA See Fig 4 1 Exhaust air connected to outdoor air exhaust hood 2 Fresh air intake connected to outdoor air inlet hood 3 Fresh air supply from ERV connected to return air duct of forced air system 4 Mechanical filters trap dust contained in the air 5 Energy re...

Page 3: ... heater WARNING Return air or stale air pickup registers are normally located to draw from kitchen bathroom basement or other rooms where stale air can exist Proper size and type of registers must be used to minimize pressure drop The velocity of airflow through register should not be above 400 ft 122m per minute Maximum length of duct for the system should be designed according to the highest spe...

Page 4: ... air pockets See Fig 7 Both intake and exhaust hoods must be 18 in 457mm from ground and at least 12 in 305mm above anticipated snow level After selecting proper hood locations make appropriate size hole through exterior wall pass flexible duct through hole and insert hood tube into duct Tape duct vapor barrier tightly around hood tube and insert assembly back into wall and fasten securely Condens...

Page 5: ...s to ensure highest degree of humidity control in cooling season the INTERMITTENT mode should be used Integrated Control All units are equipped with an integrated control located under the unit in front of the electrical compartment Use the push button 1 to control the unit The LED 2 will then shows on which mode the unit is in Integrated Control overrides Wall Control function When LED is off ven...

Page 6: ... electrical connections must comply with National and Local Electrical Codes or other ordinances that might apply ELECTRICAL SHOCK FIRE HAZARD Failure to follow this warning could result in personal injury death and or property damage Do not use an extension cord as a power source for operating the ERV HRV WARNING 12VDC Wiring The ERV HRV circuit board wall control and accessories operate on 12VDC...

Page 7: ...ve furnace air handler blower OFF If the outside temperature is below 32_F 0_C make sure the unit is not running in defrost while balancing By waiting 10 minutes after plugging the unit in you are assured that the unit is not in a defrost cycle Step 2 Magnehelic gauge placement Place the magnehelic gauge on a level surface and adjust it to zero Step 3 Connect tubing from gauge to EX HAUST air flow...

Page 8: ...opens contact on K5 relay which opens outside air damper Then 115VAC is applied between orange and gray wires on Molex plug pins 1 and 6 and blower motor runs in high speed operation Low Speed Air Exchange When low speed air exchange occurs K1 Relay is energized which closes the contacts K2 and K5 relays are de energized This keeps low speed contacts closed and high speed contacts open on K2 relay...

Page 9: ...all Control Board Operation and Care and Maintenance sections before continuing NOTE If there is a short circuit or an open circuit at thermistor CPU will go into a 5 minute defrost cycle every 20 minutes This feature is not there on older board versions with 3 pin jumpers Override Test To use override test function a thermistor must be connected to the control board Unit must not be in defrost mo...

Page 10: ...e dehumidistat does not work OR the 20 minute push button timer does not work OR its indicator light does not stay on S The wires may be in reverse position S Ensure that the color coded wires have been connected to their appropriate places S The dehumidified or push button may be defective S Jump the OL and OC terminals If the unit switch to high speed remove the dehumidistat or push button and t...

Page 11: ...12 16560 55 13 15900 57 14 15280 59 15 14690 61 16 14120 63 17 13580 64 18 13060 66 19 12560 68 20 12090 70 21 11630 72 22 11200 73 23 10780 75 24 10380 77 25 10000 79 26 9632 81 27 9281 82 28 8944 84 29 8622 86 30 8313 88 31 8014 90 32 7728 91 33 7454 93 34 7192 95 35 6940 97 36 6699 99 37 6467 100 38 6245 Table 7 Defrost Cycle HRV DEFROST CYCLES Outside Temp F C Defrosting minutes Operation time...

Page 12: ... ICP RED BLK 1 2 3 HI JU1 MED Ref 1 ORG YEL ORG PRP BLU 71V 64V 57V nc nc nc RED BLU BLU RED ORG PRP GRY BLK BLK WHT WHT BLK BLU BRN BLK BLK BLK BLU BRN BLK BLK GRN WHT BLK GRN BLK GRN RED YEL GRN 6 BLK K5 K2 K3 K1 MODE M1 Supply M2 Exhaust DAMPER 0 0 0 0 OFF OFF OFF Closed 1 0 1 1 Exchange low speed LO LO Opened 1 1 1 1 Exchange high speed HI HI Opened 1 1 1 0 Circulation high speed HI OFF Closed...

Page 13: ...12 4 J12 3 J2 3 J2 4 J2 5 Door interlock switch J11 2 J11 1 K1 K3 K5 J14 3 J14 1 J14 2 Furnace blower interlock optional see notes 3 5 J14 4 J14 5 J14 6 J14 7 J14 8 J14 9 J14 10 Override switch optional see notes 3 4 Field wiring remote control see notes 3 4 MED LO 1 2 3 HI MED JU1 Ref 1 9 5V class 2 YEL neutral YEL 24V class 2 ORG 120V 106V 81V GRY WHT RED BLK ORG ORG PRP BLU 71V 64V 57V 120V 106...

Page 14: ... when used in Canada S ERVCCSVB1100 S ERVCCSHB1100 S HRVCCSVB1100 S HRVCCSHB1100 Energy Star Canada Copyright 2010 Carrier Corp S 7310 W Morris St S Indianapolis IN 46231 Printed in U S A Edition Date 05 10 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No ERVHRV 3SI Replaces ERVHRV 2SI ERV HRV ...