3

SEQUENCE OF OPERATION

The electric heat in this unit has an on--delay of 1--30 seconds and
an off--delay of 30--60 seconds. The on--delay will delay the start of

the electric heater and blower 1--30 seconds after a W1 call.
The off--delay is 30--60 seconds and will keep the heater and

blower running after the W1 call ends. The blower will energize

with electric heater if not already running.

VERIFY INSTALLATION

After completion of heater installation, check wiring to ensure
tightness and that proper connections and routings have been

made. Ensure all electrical covers are in place. Reinstall blower
access panel before turning unit power on.

240

COM

208

BLK
YEL

BLK
RED

SECONDARY

PRIMARY

A13092

Fig. 3 -- Connection of Transformer

Table 4 – Electric Heater Electrical Data

Heat

Kit

Model

Used

on

Size

Nominal

Heat

Capacity

@ 240V

Shipping

Weight

Heater

Capacity

(MBH)

MIN. Circuit

Ampacity

MAX. Fuse

or Breaker

Ampacity

(HACR)

Min Wire Size

(AWG) ††

Min Ground

Wire Size

Max Wire

Length (Ft) ‡‡

kW

lbs. (kg)

208V

240V

208V

240V

208V

240V

208V

240V

208V

240V

208V

240V

EHK2-

05B

18/24/

30/36

5

5.1 (2.3)

14.8

17.1

24.9

28.3

30

30

10

10

12

12

66

66

EHK2-

08B

18/24/

30/36

7.5

5.1 (2.3)

22.2

25.6

36.2

41.4

50

50

8

8

10

10

59

60

EHK2-

10B

18/24/

30/36

10

5.1 (2.3)

29.6

34.1

47.4

54.4

60

60

6

6

10

10

78

80

* †† Copper wire must be used. If other than uncoated (non---plated), 75

_

C ambient, copper wire (solid wire for 10 AWG and smaller, stranded wire for larger

than 10 AWG) is used, consult applicable tables of the National electric Code (ANSI/NGPA 70).

* ‡‡ Length shown is as measured 1 way along wire path between unit and service panel for a voltage drop not to exceed 2%.