background image

20

A07218

Fig. 13 -- Cover on Equipment Control Module

14. Turn on power to equipment. On power up, all display segments will

light for 5 sec. For the next 5 sec a 2--digit code appears on large display

which identifies Thermidistat Control configuration. Refer to Option 33.

a. AC — 1--stage air conditioner

b. HP — 1--stage heat pump

c. A2 — 2--stage air conditioner

d. H2 — 2--stage heat pump

e. hh — Hybrid Heat system with 1--stage heat pump

f. h2 — Hybrid Heat system with 2--stage heat pump

g. H

— heating only system

h. C

— cooling only system

Summary of Contents for Edge TP-PRH

Page 1: ... TP NRH PerformancetSeries Thermidistatt Control Installation Instructions A07049 A07048 Programmable Control Non Programmable Control NOTE Read the entire instruction manual before starting the installation ...

Page 2: ...distat Control Recognize safety information This is the safety alert symbol When you see this symbol on the equipment and in the instruction manual be alert to the potential for personal injury Understand the signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNI...

Page 3: ...arate setpoints for heating and cooling in addition to humidification and dehumidification In the Edge Thermidistat Control s programmable configuration different heating and cooling setpoints and times are programmable for 4 periods per day or 2 periods per day Programming can be done for 7 days per week 5 2 days per week or 1 day The programmable Thermidistat Control can also be user configured ...

Page 4: ...he outdoor unit to the Rc terminal Then break jumper on the circuit board The W and HUM signals are taken from the Rh power and the G signal is taken from the Rc power If Thermidistat Control has been installed in a two transformer application that is later changed to a single transformer installation installer must install a field supplied jumper between Rc and Rh Depending on the installation up...

Page 5: ...brid Heatt installations allowing it to be used in place of all Carrier thermostats Programmable Thermidistat Controls may be configured as non programmable if user desires Humidify Equipment and Connections The humidify output connects directly to 24VAC operated humidifiers No other connection or interlock is required Any of several installer selectable operating modes are available ...

Page 6: ... available The dry contact must be configured for dehumidification in setup Option 19 See Wiring Diagrams for more information Outdoor Temperature Sensor Outdoor air temperature sensor is included in the box with the Thermidistat Control Optimum performance is obtained when an outdoor temperature sensor is used with the Thermidistat Control Plan installation so that 2 wires can be run from Equipme...

Page 7: ...may be split into two pieces and mounted in separate locations As a single piece unit all required wiring must be brought to the Equipment Control Module for connection to the terminal strip In two piece configuration the Display Module can be mounted in the living space while the Equipment Control Module may be mounted near the indoor furnace or fan coil Connection from the Display Module to the ...

Page 8: ... following components See Fig 2 for TP PRH or Fig 3 for TP NRH A07685 Fig 2 TP PRH Carton Contents 1 Display Module 2 Stand off for Equipment Control Module 3 Outside Air Temperature Sensor screws and pigtail 4 Equipment Control Module ...

Page 9: ... Module Thermidistat Control Location Thermidistat Control should be mounted S Approximately 5 ft 1 5m from floor S Close to or in a frequently used room preferably on an inside parti tioning wall S On a section of wall without pipes or duct work Thermidistat Control should NOT be mounted S Close to a window on an outside wall or next to a door leading to the outside ...

Page 10: ...control will be installed as single piece or two piece In single piece configuration as many as 14 wires may need to run to wall mounting location for connection to the control In two piece configuration the Display Module and Equipment Control Module are connected by two wires Install Thermidistat Control ELECTRICAL OPERATION HAZARD Failure to follow this warning could result in personal injury o...

Page 11: ...g with installation or turning on power CAUTION 1 Turn off all power to equipment 2 If an existing Thermidistat Control or thermostat is being replaced a Remove existing control from wall b Disconnect wires from existing thermostat 1 at a time c As each wire is disconnected record wire color and terminal marking d New or additional wires may be needed to accommodate added hu midity outputs e Disca...

Page 12: ...ce Installation The following steps should be followed for the installation of the two piece configuration NOTE The 2 wire pigtail is not intended to support the weight of the User Interface Do not hang the User Interface from the Equipment Control Module screw terminals 1 Remove mounting plate from back of Display Module by pressing the two tabs on the bottom edge and pulling away See Fig 4 and 5...

Page 13: ...13 A07225 Fig 4 Press Tabs to Remove Backplate A07226 Fig 5 Take Apart ...

Page 14: ...ed Thermidistat Control may be mounted to a standard junction box if desired Hole pat tern on Thermidistat Control mounting base matches junction box mount ing holes 4 Secure rear plastic mounting base to wall with 2 screws and anchors pro vided Additional mounting holes are available for more secure mounting if needed Make sure all wires extend through hole in mounting base 5 Adjust length and ro...

Page 15: ... Fig 7 8 and 9 Relays OAT RRS SRTN HUM D1 D2 V Vg Rc Rh W W1 G Y Y2 Y used for single stage cooling C O W2 B Y1 Y1 used for multi speed cooling Y1 stage 1 Y2 stage 2 Control Module Wiring Guide connect to user interface dry contact OAT RRS return Relays OAT RRS SRTN HUM D1 D2 V Vg Rc Rh W W1 G Y Y2 Y used for single stage cooling C O W2 B Y1 Y1 used for multi speed cooling Y1 stage 1 Y2 stage 2 Co...

Page 16: ...16 A07166 Fig 8 Secure Wires to Terminal Strip A07167 Fig 9 Connect Pigtail Wires to Display Module ...

Page 17: ... air leaks Leaks can affect operation and cause incorrect temperature and or humidity measurement 8 Make sure to attach 2 wire pigtail to Display Module mounting base It is packed loose in the box from the factory Then attach 2 wire pigtail to the back of the Display Module via 2 pin keyed connector 9 Reattach Display Module body to mounting base by first setting on at top of mounting base and the...

Page 18: ...IMPORTANT NOTE Equipment Control Module should not be mounted to duct work or below any other controls or equipment i e humidistat humidifier etc A07217 Fig 11 Equipment Control Module on Equipment 11 Route wires through rear of Equipment Control Module using either a clearance hole or supplied standoff See Fig 12 ...

Page 19: ...to proper terminals of each connector block being careful not to over tighten the screws Correct polarity must be observed when connecting the two wires from the Equipment Control Module to the Thermidistat Control mounting base If wires are con nected incorrectly the Display Module will not operate See Fig 7 8 and 9 13 Snap cover over top of Equipment Control Module See Fig 13 ...

Page 20: ...a 2 digit code appears on large display which identifies Thermidistat Control configuration Refer to Option 33 a AC 1 stage air conditioner b HP 1 stage heat pump c A2 2 stage air conditioner d H2 2 stage heat pump e hh Hybrid Heat system with 1 stage heat pump f h2 Hybrid Heat system with 2 stage heat pump g H heating only system h C cooling only system ...

Page 21: ... mark wall through 2 mounting holes 2 Drill two 3 16 in mounting holes in wall where marked Thermidistat Control may be mounted to a standard junction box if desired Hole pat tern on Equipment Control Module matches junction box mounting holes 3 Secure rear plastic Equipment Control Module to wall with 2 screws and anchors provided Additional mounting holes are available for more se cure mounting ...

Page 22: ...event air leaks Leaks can affect operation and cause incorrect temperature and or humidity measurement 7 Attach 2 wire pigtail to Equipment Control Module terminal block ter minals V and Vg Attach 2 wire pigtail to the back of the Display Module via 2 pin keyed connector 8 Reattach Display Module body to Equipment Control Module by first setting on at top and then push bottom corners to snap into ...

Page 23: ...git code appears on large display which identifies Thermidistat Control configuration Refer to Option 33 a AC 1 stage air conditioner b HP 1 stage heat pump c A2 2 stage air conditioner d H2 2 stage heat pump e hh Hybrid Heat system with 1 stage heat pump f h2 Hybrid Heat system with 2 stage heat pump g H heating only system h C cooling only system ...

Page 24: ...de up to 33 selections can be made Description of each selection and how to use the configuration mode follows CONFIGURATION OPTIONS SUMMARY Option 01 Equipment Type Option 02 Clean Filter Timer Adjustment Option 03 Fahrenheit Centigrade Selection Option 04 Fan G on with W W1 Selection Option 05 Room Air Temperature Sensing programmable models only Option 06 Cooling Lockout Below 55_F Selection on...

Page 25: ...cklight Configuration Option 19 Dry Contact Option 20 Outdoor Air Temperature Offset Adjustment Option 21 Keypad Lockout Option 22 High Cool Latch Temperature Option 23 High Heat Latch Temperature Option 24 Programmable Non Programmable programmable models only Option 25 Number of Programmable Periods per Day programmable models only Option 26 Minimum Cooling Setpoint Option 27 Maximum heating Set...

Page 26: ... the TP PRH programmable model a box will surround the option number The mode button is used to move the box between the two displayed values The soft keys below the listed values may also be used to move the box between selected values The value inside the box is changed by using the UP DOWN buttons On the TP NRH non programmable model one of the values will be flashing The mode button is used to...

Page 27: ...con is displayed With OF selected icon will never come on disabling this feature Time selection can range from 800 to 7200 hr by selecting numbers 1 through 9 Time is 800 X number selected Default is 4 3200 hr Recommended selections are disposable filter 800 to 2400 hr media filter 2400 to 3200 hr or electronic air cleaner 1600 to 2400 hr of blower operation For higher efficiency filter please con...

Page 28: ...t Below 55_F This selection disables cooling when outdoor temperature is below 55_F It requires an outdoor temperature sensor Setting is not available if valid outdoor sensor is not connected Set to OF off to allow cooling below 55_F Set to On to prevent cooling below 55_F Factory default is OF off Option 07 Zoning This selection should be set to On when the Thermidistat Control is to be used as p...

Page 29: ...lways start with heat pump heating 5 55_F the outdoor temperature below which heat pump operation is not allowed When emergency heat mode is selected only auxiliary heat will operate Default is OF off Option 10 Reversing Valve This selection is only available on heat pump systems O terminal can be configured to be energized in either heating mode or in cooling mode depending on heat pump operation...

Page 30: ...is programmed Not available with non programmable Thermidistat Controls or when Thermidistat Control is configured as non programmable Default is 90 Option 13 Room Air Temperature Offset Adjust The number of _F to be added to the displayed temperature to calibrate or deliberately miscalibrate the measured room temperature 5 to 5_F Default is 0 Option 14 Humidity Display Offset Adjust The percentag...

Page 31: ...tputs will be energized no more than 4 times per hour When an output is energized it will not be energized again for 15 minutes 6 The heating and cooling outputs will be energized no more than 6 times per hour When an output is energized it will not be energized again for 10 minutes Default is 4 Option 17 Time Between Equipment Stages This selection is only available for heat pump systems This det...

Page 32: ...ection is changed from OF to 1 the period icons are shown and the minute segments of the clock display are shown The triangle icon next to the WAKE period will be on and a value between 0 and 60 will be shown in the minutes display See Operational Information and Wiring Diagrams for further explanation of dry contact configuration and use To change the period or minutes press the soft key below th...

Page 33: ...ut When configured for dehumidification the Rc terminal must be connected to one of the dry contact terminals This provides power to energize the dehumidify terminal on the cooling equipment when the dry contact is closed See Wiring Diagrams for more information Default is OF off Option 20 Outdoor Air Temperature Offset Adjustment This selection allows the calibration or deliberate miscalibration ...

Page 34: ... Lockout non programmable models only This selection allows the installer to limit access to the keypad Selections are OF off 1 2 OF off The user has full access to the keypad 1 The user has access to change the setpoints 2 The entire keypad is locked When a button is pressed the backlight will turn on but none of the operating parameters will be changed When the keypad lock selection is turned on...

Page 35: ...ing cycle on high stage If the cooling equipment is energized to satisfy a dehumidify demand only no cooling demand the latch will not be applied On The Y1 and Y Y2 outputs are simultaneously energized to satisfy all cooling demands Default is OF off Option 23 High Heat Latch Temperature This selection is only available when Option 1 is set to H2 or h2 and Option 7 zoning is set to OF off Configur...

Page 36: ... Two periods is a common commercial application and four periods is more common for residential This selection is not available if Option 24 has been set to nP to configure the Thermidistat Control for non programmable operation 2 Periods DAY and SLEEP are available 4 Periods WAKE DAY EVE and SLEEP are available Default is 4 Option 26 Minimum Cooling Setpoint This selection allows the installer to...

Page 37: ...e to the homeowner that it is time to call the dealer to have the UV Lights replaced Selections available are OF off 6 12 18 24 30 36 42 48 OF off The UV Light reminder is turned off and will never be displayed 6 48 The number of months after which the UV Light reminder will be displayed CHECK UV LIGHT Default is OF off Option 29 Humidifier Pad Reminder This selects the number of months after whic...

Page 38: ...ed period time Default is OF off Option 31 Daylight Savings Time Configuration programmable models only This selection allows the installer to set the Thermidistat Control to automatically change by one hour on the specified day month and week specified OF off Daylight Savings Time Function disabled 1 2 On The first time the UP DOWN button is pressed the value of this selection changes from OF off...

Page 39: ...tion This configuration allows the Thermidistat Control to compensate for the amount of heat generated by the Thermidistat Control electronics to allow more accurate sensing of the temperature sensor The amount of heat compensation will be different between single installation and two piece installation Range 1P or 2P 1P The installation is single piece 2P The installation is two separate pieces D...

Page 40: ... mode press and hold the fan button for 15 seconds After 10 seconds the Thermidistat Control will enter Configuration Mode Continuing to hold the Fan button through 15 seconds will cause the Thermidistat Control to enter Installer Test Mode Pressing the Mode button will change the system operating mode to test the heating and cooling equipment Auto Mode is not available during Installer Test Mode ...

Page 41: ...mmable models pressing the button below the dehumidify icon shall toggle the state of the dry contact output On the non programmable models pressing the features button shall toggle the state of the dry contact In a heat pump application when the mode is set to em heat the auxiliary heat will turn on for 3 minutes The clock display will count down from 180 to 0 during this test TO TEST FAN Fan but...

Page 42: ... icon through the FOLLOW SCHEDULE HOLD and VACATION selections If fixed temperatures are desired use SCHEDULE button to turn on arrow icon next to HOLD This will maintain setpoints not allowing them to change with programmed schedule The FAN button may be used to select between AUTO fan on only with equipment and On fan on continuously fan modes For further information on temperature selection and...

Page 43: ...election to be adjusted and the UP DOWN buttons are used to change the setting Humidify setting may only be changed when heat mode is selected and Dehumidify setting may only be changed when cool mode is selected Humidity Control Features The various humidity control features of the Thermidistat Control are explained below They are grouped into 2 sections humidification and dehumidification Instru...

Page 44: ... the outdoor temperature de creases the humidity setpoint also decreases Settings ranging from 1 to 9 1 being the lowest and 9 the highest will be visible to the homeowner See Fig 16 for outdoor temperature indoor humidity relationship in auto humidify mode 3 Humidify Off The humidify function can be turned off completely This does not re quire changing existing setpoints To Select Humidification ...

Page 45: ...eed blower speed setpoint adjustment and equipment cycling are modified to provide added dehumidification A dehumidification setpoint separate from humidification setpoint is available to the homeowner It can range from 46 to 66 relative humidity When actual humidity is higher than setpoint a dehumidification demand exists The Thermidistat Control responds by activating the dry contact when enable...

Page 46: ...its when there is a dehumidify demand even if there is no cooling demand The limits are that the system may overcool up to 3_F but no more while attempting to satisfy a dehumidify demand Within this 3_F range there is an additional balance between overcooling and humidity satisfaction When overcooling must occur the dehumidify set point is adjusted upward by 2 per degree of overcooling For example...

Page 47: ...completely This can be done without changing existing setpoints To Select Dehumidification programmable between NORMAL COOL TO and OFF Press the soft key below the dehumidify icon button to bring up dehumidify selections Dehumidify options are only available when in Cooling mode When ...

Page 48: ...n coils have the capability of removing this off delay On FK or FV Fan Coils set delay tap to 0 0 On standard fan coils a jumper can be cut to disable off delay Refer to fan coil Installation Instructions for details If FAN is set for continuous operation fan On icon displayed G output is turned off for 5 minutes at the end of each cooling cycle as long as dehumidify demand exists Like humidify de...

Page 49: ... which would occur during the normal 90 sec blower off delay See fan coil installation instructions for more information See Wiring Diagram Reference Chart and Fig 2 through 20 in Wiring Diagram section at the back of this piece literature The furnace dehumidify input acts differently depending on which style of variable speed select single stage or multi stage furnace control you have Vacation pr...

Page 50: ...door temperature the same as when occupied Vacation humidification can be turned off independently of occupied humidification While setting the Vacation setpoints the Vacation humidify setpoint is accessible by pressing the soft key below the humidify icon when the box is around the heating setpoint Vacation Dehumidification Normal Dehumidify Cool to Dehumidify and Dehumidify OFF are all available...

Page 51: ...eceding stage has been on for 10 minutes When staging between compressor and electric heat or between compressor and furnace heat the time is configurable The timer is configurable via Option 17 This timer is overridden if temperature error is greater than 5_F usually due to a large change in desired temperature and equipment stages up in 60 second intervals Defrost When defrost occurs in a Hybrid...

Page 52: ...canceled allowing the equipment to turn off immediately when the demand is removed Heat Cool Setpoints Desired Temperature A minimum difference of 1_F and maximum of 6_F is enforced between heating and cooling desired temperatures This is done by allowing 1 setting to push the other to maintain this difference This difference is adjustable via Configuration Option 11 Equipment On Indicators When c...

Page 53: ...e fan output can be programmed based on period of the day When programming for each day and period the fan can be set to On or AUTO Dry Contact On the programmable models the dry contact that can be used for control of an auxiliary device The dry contact may be configured to be closed for a specific number of minutes per hour for each period of the program schedule This can be used to operate a ve...

Page 54: ... as programmable fan Option 30 See Wiring Diagrams for more information TROUBLESHOOTING If the display module doesn t power up after power is applied check the Rc Rh and C terminals for 24VAC If 24VAC is present check the voltage between Vg and V This voltage will be approximately 12 20VDC If voltage is present check the polarity to make sure it is wired correctly The display will not power up if ...

Page 55: ...l indicate in the outdoor temperature location E4 If Thermidistat Control s internal memory fails E4 will be displayed Replace Thermidistat Control E5 If Thermidistat Control cannot properly read humidity E5 will be displayed Replace Thermidistat Control If both Humidify and Dehumidify have been set to OF the humidity value will be shown as when viewed from the humidity menu but no E5 will be show...

Page 56: ... Single stage HP RVS H HP Y Y2 Y Y2 O W2 B Y Y2 W W1 O W2 B W W1 Single stage HP RVS C 2S Y Y2 O W2 B Y Y2 Y Y2 W W1 W W1 Single stage HP RVS H 2S Y Y2 Y Y2 O W2 B Y Y2 W W1 O W2 B W W1 Two stage AC 2S Y1 Y Y2 Y1 W W1 W W1 O W2 B Two stage HP RVS C 2S Y1 O W2 B Y1 Y Y2 O W2 B Y1 Y1 Y Y2 Y1 Y Y2 W W1 W W1 Two stage HP RVS H 2S Y1 Y1 Y Y2 Y1 O W2 B Y1 Y Y2 O W2 B Y1 Y Y2 O W2 B W W1 W W1 Single stag...

Page 57: ...TAGE 1 COOL STAGE 2 HEAT STAGE 1 HEAT STAGE 2 HEAT STAGE 3 EM HEAT STAGE 1 Two stage Hybrid Heat RVS C 2S Y1 O W2 B Y1 Y Y2 O W2 B Y1 Y1 Y Y2 W W1 W W1 Two stage Hybrid Heat RVS H 2S Y1 Y1 Y Y2 Y1 O W2 B Y1 Y Y2 O W2 B W W1 W W1 Heat Only Unit AC HP 2S W W1 Cool Only Unit 2S Y1 Y1 Y Y2 Cool Only Unit AC HP Y Y2 ...

Page 58: ...age 1 W W1 W2 Compressor Y Y2 Y Y Not Used Y1 Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Remote Room Sensor A07164 Fig 17 Display to Equipment Control Module Connection Indicates connection may not be required available ...

Page 59: ...G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06573 Fig 18 FV FK Fan Coil w 2 Stage Heat Pump Indicates connection may not be required available ...

Page 60: ...2 Y Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06574 Fig 19 Typical Fan Coil w Heat Pump Indicates connection may not be required available ...

Page 61: ...Rc Dry Contact 1 D1 Dry Contact 2 D2 Aux Connection 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06575 Fig 20 Fan Coil Shown w Aux Connection 1 Heat Pump Air Conditioner removed for clarity Indicates connection may not be required available ...

Page 62: ... 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06576 Fig 21 FV FK Fan Coil w 2 Stage Air Conditioner Indicates connection may not be required available ...

Page 63: ... Y Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06577 Fig 22 Typical Fan Coil w Air Conditioner Indicates connection may not be required available ...

Page 64: ...ing Rc Dry Contact 1 D1 Dry Contact 2 D2 Aux Connection 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06578 Fig 23 Fan Coil Shown w Aux Connection 2 Heat Pump Air Conditioner removed for clarity Indicates connection may not be required available ...

Page 65: ... 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06579 Fig 24 FV FK Fan Coil w 1 Stage Heat Pump Indicates connection may not be required available ...

Page 66: ...24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06580 Fig 25 Typical Fan Coil Heating Only Indicates connection may not be required available ...

Page 67: ...G G 24VAC Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C C Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS A06581 Fig 26 Thermidistat Control w Dry Contact Control for Fan Run Time Indicates connection may not be required available ...

Page 68: ...VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06582 Fig 27 FV FK Fan Coil w 1 Stage Air Conditioner Indicates connection may not be required available ...

Page 69: ... Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06583 Fig 28 Typical Fan Coil Cooling Only Indicates connection may not be required available ...

Page 70: ...ot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06584 Fig 29 Variable Speed Multi Stage Furnace w 2 Stage Heat Pump Indicates connection may not be required available ...

Page 71: ...Fan G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A006585 Fig 30 Single Stage Furnace w Heat Pump Indicates connection may not be required available ...

Page 72: ...Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06586 Fig 31 Variable Speed Multi Stage Furnace w 2 Stage Air Conditioner Indicates connection may not be required available ...

Page 73: ...n G G 24VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06587 Fig 32 Single Stage Furnace w Air Conditioner Indicates connection may not be required available ...

Page 74: ...ting Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06588 Fig 33 Variable Speed Multi Stage Furnace w Single Stage Heat Pump Indicates connection may not be required available ...

Page 75: ... Hot Heating Rh R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06589 Fig 34 Single Stage Furnace Heating Only Indicates connection may not be required available ...

Page 76: ...VAC Hot Heating Rh R R 24VAC Hot Cooling Rc Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A06590 Fig 35 Variable Speed Multi Stage Furnace w Single Stage Air Conditioner Indicates connection may not be required available ...

Page 77: ... Cooling Rc R Dry Contact 1 D1 Dry Contact 2 D2 DEHUM 24VAC Common C COM COM Humidify HUM Outdoor Air Temp OAT Remote Room Sensor RRS OAT RRS Com OAT RRS Outdoor Sensor Humidifier Solenoid Valve Remote Room Sensor A07760 Fig 36 Single stage Furnace with Air Conditioner and Split Power Indicates connection may not be required available NOTE Rc Rh jumper is cut on the Equipment Control Module ...

Page 78: ...alue __________ Cooling Setpoint Value __________ Fan Auto or On C Home Away Sleep Settings Heat Cool Home ____ ____ Away ____ ____ Sleep ____ ____ D Schedule For Programmable Thermidistat Controls Period 1 Period 2 Period 3 Period 4 Time Heat Cool Time Heat Cool Time Heat Cool Time Heat Cool All Days ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ ____ Weekdays ____ ____ ____ ____ ____ ___...

Page 79: ...____ Auxiliary Heat Lockout Temperature Setting only available when heat pump is used and when outdoor air temperature sensor is present Option 09 _____ Heat Pump Lockout Temperature Option 10 _____ Reversing Valve Option 11 _____ Adjustable Setpoint Deadband not available on Heat Only and Cool Only systems Option 12 _____ Smart Recovery programmable models only Option 13 _____ Room Air Temperatur...

Page 80: ...27 _____ Maximum Heating Setpoint Option 28 _____ UV Light Reminder Option 29 _____ Humidifier Pad Reminder Option 30 _____ Programmable Fan programmable models only Option 31 _____ Daylight Savings Time Configuration programmable models only Option 32 _____ Furnace Heat Staging Option 33 _____ Single or Two Piece Installation Options with an asterisk can also be set changed by the homeowner Copyr...

Reviews: