13
95-8562
4.2
NOTES:
1.
FOR
INST
ALLA
TION
IN
NONINCENDIVE,
CLASS
I,
DIVISION
2,
GROUPS
A,
B,
C
&
D;
CLASS
II,
DIVISION
2,
GROUPS
F
&
G;
CLASS
III,
DIVISION
2
HAZARDOUS
(CLASSIFIED)
LOCA
TIONS,
OR
NON-
HAZARDOUS
LOCA
TIONS
ONL
Y.
W
IRING
METHODS
SHALL
BE
INST
ALLED
IN
ACCORDANCE
WITH
ANSI/NFP
A
70
(NEC)
AR
TICLE
501-4(b)
AND
ANSI/NFP
A
72.
2.
THIS
DRA
WING
SHOWS
THREE
SENSORS
CONNECTED
IN
ONE
ZONE
IN A
CLASS
A,
STYLE
D
CONFIGURA
TION
PER
NFP
A
72.
ADDITIONAL
SENSORS
CAN
BE
ADDED
BY
REPEA
TING
THE
WIRING
PA
TTERN
OF
THE
CENTRAL
SENSOR.
3.
PM-5MPX
INTERCONNECTS
VIA
FL
YING
LEAD.
4.
ELECTRICAL
REQUIREMENT
:
9 T
O
30
VDC
AND
10
MILLIAMPS
(MAX)
PER
SENSOR.
5.
THE
OUTGOING
AND
RETURN
(REDUNDANT)
CIRCUIT
CONDUCT
ORS
SHALL
NOT
BE
RUN
IN
THE
S
AME
CABLE
ASSEMBL
Y,
ENCLOSURE,
OR
RACEW
AY
PER
NFP
A
72.
PM-5MPX
ELECTRICAL
INTERF
ACE
W
ire
Color
Signal
Red
V+,
Input
Power
Orange
V+,
Input
Power
Black
Power
Return
Brown
Power
Return
Yellow
Alarm
+
Green
Alarm
+
Blue
Alarm
–
Vi
ole
t
Alarm
–
Gray
Trouble
+
White
Trouble
–
F
igur
e E1—Non-Incendiv
e Class
A, St
yle D
W
iring (Dr
awing No
. 420034)
APPENDIX E
NON-INCENDIVE
CLA
SS
A,
S
TYLE D
WIRING
Hazar
dous (Classifi
ed) Locations:
Class I,
Division 2,
Gr
oup
A,
B,
C,
D
Class II,
Division 2,
Gr
oup F
, G
Class III,
Division 2
Non-hazar
dous (Non-c
lassifi
ed) Locations