CRTWOPOS010A00

CRTWOPOS011A00

Installation Instructions

SMALL ROOFTOP PRODUCTS

GAS/ELECTRIC HEAT AND HEAT PUMP UNITS

2 to 12---1/2 TONS (50/60 Hz) ACCESSORY

ADJUSTABLE TWO POSITION OUTDOOR AIR DAMPER

Read these instructions completely before attempting to install the
accessory outdoor air damper.

SAFETY CONSIDERATIONS

Installation and servicing of air--conditioning equipment can be
hazardous due to system pressure and electrical components. Only

trained and qualified service personnel should install, repair, or

service air--conditioning equipment.
Untrained personnel can perform basic maintenance functions of

cleaning coils and filters and replacing filters. All other operations
should be performed by trained service personnel. When working

on air--conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety

precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguishers

available for all brazing operations.

Recognize safety information. This is the safety--alert symbol

.

When you see this symbol on the unit and in instructions or

manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and

CAUTION. These words are used with the safety--alert symbol.

DANGER identifies the most serious hazards which

will

result in

severe personal injury or death. WARNING signifies a hazard

which

could

result in personal injury or death. CAUTION is used

to identify unsafe practices which

may

result in minor personal

injury or product and property damage. NOTE is used to highlight

suggestions which

will

result in enhanced installation, reliability, or

operation.

GENERAL

These 2 position outdoor air packages can be used in either a
vertical or horizontal airflow configuration. The damper assembly

travel can be adjusted to allow from 25% to 100% outdoor air for
the applicable rooftop unit.

PACKAGE USAGE AND CONTENTS

UNIT SIZE

PART NUMBER

PACKAGE CONTENTS

2 to 6 Tons

CRTWOPOS010A00

2 --- Hood side

1 --- Hood top

1 --- Hood divider

1 --- Aluminum filter

1 --- Bottom panel

1 --- Damper assembly

1 --- Hardware bag

7---1/2 to 12---1/2

Tons

CRTWOPOS011A00

2 --- Hood side

1 --- Hood top

1 --- Hood divider

1 --- Aluminum filter

1 --- Bottom panel

1 --- Damper assembly

1 --- Hardware bag

INSTALLATION

To install the outdoor damper, perform the following:

IMPORTANT

: Follow all applicable local and national electrical

codes when installing this accessory.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing accessory, disconnect power supply and

install lockout tag.

!

WARNING

1. Turn off unit power supply and install lockout tag. For gas

units, turn off the gas supply.

2. Determine quantity of ventilation air required for building.

Record amount of air for use in Step 10.

3. Remove filter access panel by raising panel and swinging

panel outward. Panel is now disengaged from track and can
be removed. No tools are required to remove filter access
panel. Remove the outdoor--air opening/indoor coil access

panel. (See Fig. 1.)

C07340

Fig. 1 -- Rooftop Unit Panels

(2--6 ton unit shown)

4. Assemble outside--air hood top, sides and divider as shown

in Fig. 2. Do not install hood at this time.

5. Install galvanized, insulated bottom panel per Fig. 3, with

the slot at the top of the panel. The lip of the slot should fit
behind the corner post as shown. Screw in place.