2

Power Wiring  — 

Power exhaust accessory package

CRPWREXH008B00 is shipped with power wiring connected
to motor for 460-v operation, but may be rewired for 208/230-v
operation.

208/230 V, 60 Hz —   Remove  the  no.  10AB  x 

1

/

2

-in. lg

screws from the perimeter of power exhaust front panel. Re-
move front panel containing fan and fan motor.

Referring to Fig. 6-8, change connection at power exhaust

motor as follows:

1. Remove splice between leads 1 and 2.
2. Remove cap from lead 5.
3. Remove yellow wire from lead 4.
4. Remove red wire from lead 3.
5. Connect red wire to lead 1.
6. Connect yellow wire to leads 2 and 4.
7. Splice leads 3 and 5.

Replace front panel containing fan and fan motor. Proceed

as described below.

ALL UNITS — Feed the red and blue power wires from rear
of power exhaust box through conduit assembly. Route conduit
assembly through hole in partition to main control box (see
Fig. 5). Secure conduit assembly to bottom of main control box
and at rear of power exhaust box.

Route the red and blue power wires from conduit termina-

tion to main control box components: per Fig. 6 for 15 ton
standard-efficiency electric heat/electric cool and gas heat/
electric cool units and 12 ton high-efficiency electric heat/
electric cool and gas heat/electric cool units; per Fig. 7 for 18 to
25 ton standard-efficiency electric heat/electric cool and gas
heat/electric cool units, 15 and 20 ton high-efficiency electric
heat/electric cool and gas heat/electric cool units, and 15 ton
high-efficiency heat pump units; and per Fig. 8 for 13 ton high-
efficiency heat pump units.

Lock open and tag power disconnect before working on any
electrical components.

ALTERNATE
RETURN-AIR
OPENING

CENTER POST

INSULATED
PANEL

Fig. 3 — Panel and Center Post Installation

Fig. 4 — Low-Voltage Control Box Connections

LEGEND

IFC —

 Indoor Fan Contactor

NOTE: Dashed lines indicate field-installed control wiring.

Fig. 5 — Control Wiring Installation

Summary of Contents for CRPWREXH008B00

Page 1: ...y Power Exhaust Usage Power exhaust motor is wired for 460 v PACKAGE CONTENTS INSTALLATION 1 Unpack accessory package See Fig 1 2 Disconnect power to unit Remove the control box access panel main cont...

Page 2: ...o main control box see Fig 5 Secure conduit assembly to bottom of main control box and at rear of power exhaust box Route the red and blue power wires from conduit termina tion to main control box com...

Page 3: ...OOTH OR BRN FU8 FU9 CAP YEL EMC RED RED BLU BLU BLK NEUTRAL TB 21 11 IFC BLK POWER EXHAUST MAIN CONTROL BOX 460 V 60 Hz PART NO CRPWREXH008B00 208 230 V 60 Hz PART NO CRPWREXH008B00 575 V 60 Hz PART N...

Page 4: ...AP YEL EMC RED RED BLU BLU NEUTRAL TB POWER EXHAUST MAIN CONTROL BOX BLK BLK 21 11 IFCB 460 V 60 Hz PART NO CRPWREXH008B00 208 230 V 60 Hz PART NO CRPWREXH008B00 575 V 60 Hz PART NO CRPWREXH010B00 220...

Page 5: ...YEL YEL BLK RED BLU EFM FU8 FU9 EMC YEL RED BLU CAP RED BLU MAIN CONTROL BOX POWER EXHAUST BOX BLK RIBBED OR WHT EFM SMOOTH OR BRN BLK FU1 BLK FU2 YEL YEL 460 V 60 Hz PART NO CRPWREXH008B00 208 230 V...

Page 6: ...ge control box Connect brown wire to terminal C on low voltage terminal strip see Fig 9 4 Replace access panels and return power to unit Figure 10 shows the unit with accessory power exhaust package i...

Page 7: ......

Page 8: ...at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 534 80153 Printed in U S A Form 48 50H T 30SI Pg 8 9 03 Replaces 48 50H T 14SI Book 1 1 1 4 4 4...

Reviews: