5

Fig. 6 — Front Left View

Fig. 7 — Unit Wiring Harness

11.  Assemble the outside air hood per Fig. 9-11.

 a. Install filter supports (Item #1) to the upper end panel

using the screws provided.

 b. Install each deflector (Item #8) on to each filter support

(Item #1) using the screws provided.

 c. Apply seal strip to mating flanges on the side plates of

the hood (Item # 4 and #5).

 d. Secure  the  side  panels  (Item  #4  and  #5)  to  the  upper

panel using the screws provided.

 e. Apply the seal strip to the mating flange of the hood.

(See Fig. 10.)

 f. Secure hood top (Item #3) to the upper panel using the

screws  provided.  On  the  44  in.  chassis  remove  the

screws from across the top cover of the unit. The rear

flange of the hood top will slide behind the unit top over

the flange.

 g. Secure side retainers (Item #6) to side panels (Item #4

and #5) using the screws provided, screwing from the

outside of the hood.

 h. Secure each central retainer (Item #2) to the hood top

(Item #3). Align the central retainers to the holes located

on the filter support (Item #1), so the central retainer is

perpendicular to the hood and each filter support. Secure

using the screws provided.

 i. Apply seal strip to top diverters (Item #7).

 j. Secure top diverters (Item #7) to the hood top (Item #3).

 k. Install outdoor air screens by sliding them into each of

the four spaces created by the hood, filter support and,

central  retainers.  First  insert  the  air  screens  into  the

pocket  created  at  the  end  of  the  hood (Item #3), then

fully put the air screen into place. Slide the air screens

back  into  the  pocket  created  in  the  filter  support

(Item  #1).  Repeat  this  step  for  each  air  screen.  (See

Fig. 11.) See Fig. 12 for complete hood assembly.

12. Install  the  hood  screens  and  other  approved  EconoMi$er2

accessories.

Economizer Outside
Air Damper

Insert 
Screw

Left Front
Corner Post

Insert 
Screw

HARNESS/PLUG
FROM HVAC

JUMPER PLUG
(REMOVE)

HARNESS/PLUG
FROM ECONOMIZER

Summary of Contents for CRECOMZR054B00

Page 1: ...DANGER WARNING CAUTION and NOTE These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies haz...

Page 2: ...rator box used for duct mounted CO2 room sensor c 33ZCT55CO2 Space temperature and CO2 room with over ride d 33ZCT56CO2 Space temperature and CO2 room sensor with override and setpoint 2 All units inc...

Page 3: ...de corner post on to the unit NOTE The corner post will sit behind the economizer flange See Fig 5 Screw through the corner post and through the economizer See Fig 5 and 6 7 Insert provided screw thro...

Page 4: ...e bottom screw holding the relief blade closed 10 Install the upper end economizer panel over the economizer s outside air damper and above the bottom panel Screw panel in place and screw panel into e...

Page 5: ...g from the outside of the hood h Secure each central retainer Item 2 to the hood top Item 3 Align the central retainers to the holes located on the filter support Item 1 so the central retainer is per...

Page 6: ...el with Relief Relief Damper Remove Shipping Screw APPLY SEAL STRIP TO THE FRONT OF THIS FLANGE APPLY SEAL STRIP TO THE BACK OF THIS FLANGE APPLY SEAL STRIP TO THE BACK OF THIS FLANGE APPLY SEAL STRIP...

Page 7: ...7 Fig 10 Air Screen Installation Fig 11 Completed Hood Assembly 1 INSERT AIR SCREEN 2 SLIDE INTO POSITION...

Page 8: ...e the side panels located in the hood parts box see Fig 15 3 Install parts as shown in the following exploded view see Fig 16 using the seal strip and screws provided in the parts box Figure 17 illust...

Page 9: ...9 Fig 13 Barometric Hood Parts Fig 14 Shipping Location Vertical Units Fig 15 Barometric Hood Box Parts Location...

Page 10: ...er See Fig 18 3 On the field installed economizer CRECOMZR0 B00 a birdscreen or hardware cloth is shipped attached to the bottom panel used for vertical applications NOTE This panel is not used for ho...

Page 11: ...amper Fig 20 CRBARHOD001A00 Hood Sides and Top Unit Outside Air Hood Min 19 1 2 Relief Opening Return Duct 16 1 18 3 8 OUTDOOR AIR HOOD CRBARHOD001A00 RELIEF HOOD ORDERED SEPARATELY FIELD SUPPLIED RET...

Page 12: ...ening on the unit See Fig 22 Screw panel in place 10 Install the upper end economizer panel in place over the economizer s outside air damper and above the bottom panel Screw panel in place and screw...

Page 13: ...Panel Fig 22 Install Bottom Panel w Horizontal Duct Opening Fig 23 Reinstall Hinges and Damper on Return Duct UNIT S LEFT SIDE PANEL WITH DUCT OPENING LEFT FRONT CORNER POST Bottom Panel with Return D...

Page 14: ...on 140 4 b Air Economizer High Limit Shut Off Control Requirements Table 2 California Title 24 Regional High Limit Dry Bulb Temperature Settings DEVICE TYPE CLIMATE ZONES REQUIRED HIGH LIMIT ECONOMIZ...

Page 15: ...osition Make sure the switch is turned all the way left or right Actuator will move to its Control Signal position Actuator operates properly Step 8 Does not drive toward Control Signal Position Step...

Page 16: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53480312 01 Printed in U S A Form IIK CRECOMZR54 04 Pg 16 7 21 Replaces...

Reviews: