background image

Cancels: IIK 548-36-17

IIK 548-36-26

9/15/95

Installation and Start-Up Instructions

Part Numbers CRECOMZR001A02 and CRECOMZR002A02

PACKAGE USAGE AND CONTENTS

UNIT

PACKAGE

NO.

CONTENTS

3 to 6

Tons

CRECOMZR

001A02

1 — Barometric Relief Damper Hood
2 — Hood Sides
1 — Hood Top
1 — Outdoor-Air Inlet Screen
1 — Screen Retainer Cap
2 — Spacers
1 — Horizontal Block-Off Plate

30 —

5

8

-in. no. 10 Screws

2 —

3

4

-in. no. 10 Screws

1 — Economizer with Control Board

Attached

1 — Outdoor-Air Thermostat (OAT)
1 — Knob
1 — Supply-Air Thermostat (SAT)
2 — Wirenuts
1 — Wire Tie
3 — Seal Strips
1 — Outdoor-Air Opening Panel

7

1

2

to

12

1

2

Tons

CRECOMZR

002A02

1 — Barometric Relief Damper Hood
2 — Hood Sides
1 — Hood Top
2 — Outdoor-Air Inlet Screens
1 — Screen Retainer Cap
3 — Spacers
1 — Horizontal Block-Off Plate
1 — Vertical Discharge Block-Off

Plate

40 —

5

8

-in. no. 10 Screws

3 —

3

4

-in. no. 10 Screws

1 — Economizer with Control Board

Attached

1 — Outdoor-Air Thermostat (OAT)
1 — Knob
1 — Supply-Air Thermostat (SAT)
2 — Wirenuts
1 — Wire Tie
1 — Screen Clasp
1 — Bottom Stop
3 — Seal Strips
1 — Outdoor-Air Opening Panel

GENERAL

Accessory economizer package utilizes cool outdoor air

to satisfy cooling load and minimize energy consumption.
Economizer cooling can be used alone or in conjunction with
mechanical cooling.

A standard economizer uses a dry bulb thermostat to sense

outdoor-air temperature. For a more efficient system, an ac-
cessory solid-state enthalpy control can be substituted for
the dry bulb thermostat.

Also available as an economizer accessory is the differ-

ential enthalpy control. This system compares the tempera-
ture and humidity of outdoor air and return air and then ad-
justs the economizer position to ensure the lowest enthalpy
air is used for cooling.

IMPORTANT: Read these instructions completely
before attempting to install the accessory economizer.

INSTALLATION

Turn off unit power! Electrical shock and personal in-
jury could result.

1. Determine quantity of ventilation air required. Record

amount of air for use in Step 10.

2. Remove filter access panel by raising panel and swing-

ing panel outward. Panel is now disengaged from track
and can be removed. No tools are required to remove
filter access panel. Remove indoor coil access panel. Dis-
card panel and save screws. See Fig. 1.

3. Assemble outdoor-air hood top and side plates as shown

in Fig. 2. Install seal strips on hood top and sides. Put
aside screen retainer and screws for later assembly. Do
not attach hood to unit at this time.

4. On all 10 and 12

1

2

ton units, install vertical discharge

block-off plate over duct openings. See Fig. 3.

5. Slide economizer into unit and secure with screws. See

Fig. 4.

6. If barometric pressure relief is required, remove the hold-

down screw from the barometric relief damper and mount
the barometric relief damper hood around the damper
with the 4 screws supplied. The longest part of the hood
should be above the top of the damper.

7. To install the economizer for a horizontal discharge

application:
a. Install the economizer so that the motor faces the

outdoor-air section and secure with screws. See
Fig. 5.

b. If barometric pressure relief is required, rotate baro-

metric relief damper 90 degrees so that it opens and
closes vertically. Mount the barometric damper hood
around the damper with the supplied screws. The long-
est part of the hood should be above the top of the
damper.

c. Install horizontal discharge block-off plate over open-

ing on the access panel. Block-off plate MUST be
installed before installing hood assembly. See Fig. 6.
NOTE: Install spacers at the same time as the hori-
zontal block-off plate using same screws. The spac-
ers are used to cover gaps between the economizer
assembly and the unit.

Small Rooftop Units

Gas Heating/Electric Cooling, Electric Cooling, and

Heat Pump Units

3 to 12

1

2

Tons (50/60 Hz)

Accessory Economizer Package

Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Book 1

1

1

4

4

4

Tab

1a 1b 5a 5a 6a 6b

PC 111

Catalog No. 534-892

Printed in U.S.A.

Form 48/50-39SI

Pg 1

9-95

Replaces: 48/50-31SI

Summary of Contents for CRECOMZR001A02

Page 1: ...red Record amount of air for use in Step 10 2 Remove filter access panel by raising panel and swing ing panel outward Panel is now disengaged from track and can be removed No tools are required to remove filter access panel Remove indoor coil access panel Dis card panel and save screws See Fig 1 3 Assemble outdoor air hood top and side plates as shown in Fig 2 Install seal strips on hood top and s...

Page 2: ...ting bracket until the top screw is in the position determined by Fig 9 or 10 Tighten screws 11 Install outdoor air opening panel with screws from Step 2 12 Fasten hood top and side plate assembly and bottom stop on 71 2 to 121 2 ton units to unit with screws provided See Fig 2 FILTER ACCESS PANEL INDOOR COIL ACCESS PANEL Fig 1 Typical Access Panel Locations Fig 2 Outdoor Air Hood Details Fig 3 Ve...

Page 3: ...lamp screens to gether using clasp provided While holding screen s in place fasten screen retainer to hood using screws provided NOTE Only 1 screen is provided with 3 to 6 ton units EXAMPLE Given Negative Pressure 0 2 in wg Outdoor Air 1100 cfm Determine Setting 6 in Fig 9 Economizer Minimum Position Setting 3 to 6 Ton Units EXAMPLE Given Negative Pressure 0 1 in wg Outdoor Air 1100 cfm Determine ...

Page 4: ... 9 19 Replace filter access panel 20 Turn on base unit power 21 Barometric relief damper characteristics are shown in Fig 15 and 16 4 3 2 1 0 5 6 7 8 9 POSITION SETTING BRACKET TOP SCREW Fig 11 Minimum Position Setting Bracket MINIMUM POSITIO N OPEN 3 1 T P P1 T1 4 2 5 S S O D C TR B REV B 1 9 8 8 1 8 A H U M I D I T Y 90 70 60 30 10 D C B A 60 65 70 75 55 50 85 80 DAMPER DAMPER CLOSED OPEN OUTDOO...

Page 5: ...to remain in an intermediate open position If the supply air temperature falls below 52 F a switch on the supply air thermostat is closed between the T1 terminal and the 24 vac terminal This causes the damper to modulate closed until the supply air temperature rises above 55 F or the damper reaches the minimum position When the supply air temperature is between 55 F and 57 F the supply air thermos...

Page 6: ...ween the T1 terminal and the 24 vac terminal This causes the damper to modulate closed until the supply air temperature rises above 55 F or the damper reaches the minimum position When the supply air temperature is between 55 F and 57 F the supply air thermostat has open switches between theT2 and 24 vac terminals This causes the economizer damper to remain in an intermediate open position If the ...

Page 7: ... and the economizer control board wiring are correct check to ensure that the 24 vac terminal of the SAT has 24 vac white wire If OAT EC and control board are functioning and wired properly and no 24 vac exists check wiring see unit label diagram 2 If supply air temperature is greater than 57 F 24 vac should be found at ter minal T2 on the SAT pink wire If 24 vac is not present replace SAT Damper ...

Page 8: ...rves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 1 1 4 4 4 Tab 1a 1b 5a 5a 6a 6b PC 111 Catalog No 534 892 Printed in U S A Form 48 50 39SI Pg 8 9 95 Replaces 48 50 31SI ...

Reviews: