TEST RUNNING
(Cont.)
20.3 STEPS FOR COOLING TEST RUNNING
a.
Move circuit breaker to ON position.
b.
Operate the system for cooling operation
at high fan speed by using wireless remote control.
c.
After system operation becomes stabilized:
-
Measure low pressure to check correct
refrigerant charge. (See figure & table )
-
Measure total Amps consumed by the system.
-
Measure System working voltage.
Hi Wall Split System – Cool Only
SYSTEM MODEL
53KHET30-708F
53KHET36-708F
AMBIENT TEMP ºC
35
46
52
35
46
52
LOW PRESSURE PSI
70 74 76 75 80 83
TOTAL AMPS
15 17.9 19.5 21.1 25.1 27.3
Hi Wall Split System – Heat Pump
SYSTEM MODEL
53QHET30-708F
53QHET36-708F
AMBIENT TEMP ºC
35
46
52
35
46
52
LOW PRESSURE PSI
66 70 72 71 75 77
TOTAL AMPS
15.3 18.4 20.1 21 24.9 27
NOTE:
Readings at 220 volt and 27ºC return air to indoor unit and high speed of indoor unit motor.
20.4 STEPS FOR HEATING TEST RUNNING
a.
Move circuit breaker to ON position.
b.
Operate the system for heating operation
at high fan speed by using wireless remote control.
c.
After system operation becomes stabilized:
-
Measure high pressure to check correct
refrigerant charge. (See figure)
-
Measure total Amps consumed by the system.
-
Measure system-working voltage.
Hi Wall Split System – Heat Pump
SYSTEM MODEL
53QHET30-708F
53QHET36-708F
AMBIENT TEMP ºC
7
7
HIGH PRESSURE PSI
230 230
TOTAL AMPS
12.8 17.2
NOTE:
Readings at 220 volt and 20ºC return air to indoor unit and high speed of indoor unit motor.
(1) Low Pressure Measuring.
(1)
Outdoor Unit
Details
(1) High Pressure Measuring.
(1)
Outdoor Unit
Details