P49 – Shift between Cool and Heat in Auto change over mode
Range: 0...10°C / 0…20°F
Default: 2°C / 4°F
Shift between
P51 – Shift between Heating stages
Range: 0...10°C / 0…20°F
Default: 2°C / 4°F
P50 – Shift between Cooling stages (AC only!)
Range: 0...10°C / 0…20°F
Default: 2°C / 4°F
Shift between c
(°F)
(°C)
(°F)
(°C)
Shift between heating
(°F)
(°C)
P49
Shift between Cool and Heat
in Auto change over mode
(from cooling to heating)
Compressor / Valve
ON
OFF
Temp.
Setpoint
Cool differential
band
Heat differential
band
+0.5
-0.5
Shift between Cool and Heat
+0.5
-0.5
P49
Shift between Cool and Heat
in Auto change over mode
(from heating to cooling)
Compressor / Valve
ON
OFF
Temp.
Setpoint
Cool differential
band
Heat differential
band
+0.5
-0.5
Shift between Cool and Heat
+0.5
-0.5
- 50 -
Technician Settings (cont.)