Technician Settings P16 to P25
P16 – Enable/Disable Motion sensor
“00” - Disable
“01” - Enable
P17 – PIR (Motion sensor) delay time
before switching to unoccupied mode (ON delay)
Range: 0…900 minutes
Default: 20 minutes
P18 – Door switch or key tag configuration
“00” - Switch On/Off by door switch or key tag
“01” - Changing the setpoint temperature
“02” - Switching fan speed to Low
P19 – PIR (Motion sensor) polarity
“00” - Normally open
“01” - Normally closed
P25 – Economy setpoint for cooling
Range: 5…35°C / 41…95°F
Default: 30°C / 86°F