Step 6 — Trap Condensate Drain —

See Fig. 10

for drain location. One 

3

/

4

-in. half coupling is provided outside

unit evaporator section for condensate drain connection. A trap
at least 4-in. deep must be used. See Fig. 11.

Step 7 — Make Electrical Connections

FIELD POWER SUPPLY — Unit is factory wired for volt-
age shown on unit nameplate.

When installing units, provide disconnect per NEC (Nation-

al Electrical Code) of adequate size (MOCP [Maximum
Overcurrent protection] of unit is on the informative plate). See
Tables 2A and 2B. All field wiring must comply with NEC and
local codes. Size wire based on MCA (Minimum Circuit
Amps) on the unit informative plate. See Fig. 12 for power
wiring connections to the unit power terminal block and
equipment grounds.

Route power and ground lines through control box end pan-

el or unit basepan (see Fig. 4) to connections as shown on unit
wiring diagram and Fig. 12.

Field wiring must conform to temperature limitations for

type  ‘‘T’’ wire. All field wiring must comply with NEC and
local requirements.

Operating voltage to compressor must be within voltage

range indicated on unit nameplate. On 3-phase units, voltages
between phases must be balanced within 2%.

Unit failure as a result of operation on improper line voltage

or excessive phase imbalance constitutes abuse and may cause
damage to electrical components.
FIELD CONTROL WIRING — Unit can be controlled with
either a Carrier-approved accessory thermostat or a Carrier-
approved space temperature sensor. Install thermostat accord-
ing to the installation instructions included with accessory.
Locate thermostat assembly or space temperature sensor on a
solid interior wall in the conditioned space to sense average
temperature.

Route thermostat or space temperature sensor cable or

equivalent single leads of colored wire from subbase terminals
through conduit into unit to low-voltage connections as shown
on unit label wiring diagram and in Fig. 13 or 14.
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gage) insulated wire (35 C minimum). For 50 to 75 ft,
use no. 16 AWG insulated wire (35 C minimum). For over
75 ft, use no. 14 AWG insulated wire (35 C Minimum). All
wire larger than no. 18 AWG cannot be directly connected at
the thermostat and will require a junction box and splice at the
thermostat.

The correct power phasing is critical to the operation of the
scroll compressors. An incorrect phasing will result in an
alarm being generated and compressor operation lockout.
Should this occur, power phase correction must be made to
the incoming power.

The unit must be electrically grounded in accordance with
local codes and NEC ANSI/NFPA 70 (American National
Standards Institute/National Fire Protection Association).

NOTE: Dimensions A, A

, B, and B

 

are obtained from field-supplied

ceiling diffuser.

Shaded areas indicate block-off pans.

Fig. 9 — Concentric Duct Details

Fig. 10 — Condensate Drain Details

NOTE: Dimensions in [] are in millimeters.

Fig. 11 — Condensate Drain Piping Details

Summary of Contents for COMFORTLINK 50HG014

Page 1: ...ses and work gloves Use quenching cloth for unbrazing operations Have fire extinguishers available for all brazing operations INSTALLATION Step 1 Provide Unit Support ROOF CURB Assemble or install accessory roof curb in accordance with instructions shipped with this accessory See Fig 1 Install insulation cant strips roofing and counter flash ing as shown Ductwork can be installed to roof curb befo...

Page 2: ...2 Fig 1 Roof Curb Details ...

Page 3: ...xhaust vents or other sources of contaminated air Although unit is weatherproof guard against water from higher level runoff and overhangs ROOF MOUNT Check building codes for weight distribu tion requirements Unit operating weight is shown in Table 1 INSTALLATION ONTO CURB The 50HG units are designed to fit on either the accessory full perimeter curb or onto existing 48 50TJ HJ or 48 50DP DR curbs...

Page 4: ...4 Fig 3 Rigging Details ...

Page 5: ...5 Fig 4 Base Unit Dimensions ...

Page 6: ...ve 485 613 472 619 618 789 609 778 658 808 658 808 Std motor Alt drive 618 789 609 778 485 613 472 619 794 974 794 974 Alt motor Std drive 778 1021 778 1021 778 1021 778 1021 949 1145 949 1145 Alt motor Alt drive 1000 1227 1000 1227 1000 1227 1000 1227 1126 1328 1126 1328 Motor Bearing Type Ball Ball Ball Ball Ball Ball Maximum Allowable Rpm 1400 1400 1400 1400 1400 1400 Motor Pulley Pitch Diamete...

Page 7: ... Rpm Range Std motor Std drive 658 808 658 808 799 965 Std motor Alt drive 794 974 794 974 939 1152 Alt motor Std drive 949 1145 949 1145 945 1187 Alt motor Alt drive 1126 1328 1126 1328 1152 1366 Motor Bearing Type Ball Ball Ball Maximum Allowable Rpm 1400 1400 1400 Motor Pulley Pitch Diameter Std motor Std drive 4 3 5 3 4 3 5 3 5 4 6 6 Std motor Alt drive 4 3 5 3 4 3 5 3 4 2 5 2 Alt motor Std dr...

Page 8: ...he factory ready for side supply installation If the horizontal option was not specified at time of ordering the unit a field installed accessory kit is required to convert the vertical unit into a horizontal supply configuration Installation of the duct block off covers should be complet ed prior to placing the unit unless sufficient side clearance is available A minimum of 66 in is required betw...

Page 9: ...with either a Carrier approved accessory thermostat or a Carrier approved space temperature sensor Install thermostat accord ing to the installation instructions included with accessory Locate thermostat assembly or space temperature sensor on a solid interior wall in the conditioned space to sense average temperature Route thermostat or space temperature sensor cable or equivalent single leads of...

Page 10: ...ECTRIC HEAT IFM POWER EXHAUST POWER SUPPLY DISCONNECT SIZE No 1 No 2 No 3 Min Max RLA LRA RLA LRA RLA LRA Qty Hp FLA ea kW FLA Hp FLA Qty Hp FLA ea MCA MOCP FLA 014 208 230 187 253 19 2 146 0 19 2 146 0 4 0 1 4 1 5 3 7 10 6 9 6 60 59 70 70 70 70 2 1 0 5 9 72 71 90 80 80 80 5 0 16 7 15 2 66 64 80 80 80 70 2 1 0 5 9 78 76 90 90 90 90 12 16 33 38 3 7 10 6 9 6 60 60 70 70 70 70 2 1 0 5 9 72 74 90 80 8...

Page 11: ...46 50 60 25 30 3 7 4 8 44 45 45 2 1 0 3 1 51 60 50 5 0 7 6 47 50 45 2 1 0 3 1 55 60 60 50 60 3 7 4 8 66 80 80 2 1 0 3 1 74 80 90 5 0 7 6 70 80 80 2 1 0 3 1 77 80 90 75 90 3 7 4 8 96 110 110 2 1 0 3 1 104 110 125 5 0 7 6 100 110 125 2 1 0 3 1 107 125 125 575 518 633 7 0 55 0 7 0 55 0 7 0 55 0 4 0 1 4 0 7 3 0 3 9 29 35 35 2 1 0 3 1 36 40 40 5 0 6 1 32 35 35 2 1 0 3 1 38 40 45 25 24 3 0 3 9 35 35 35 ...

Page 12: ...50 50 2 1 0 3 1 51 60 60 25 30 5 0 7 6 47 50 45 2 1 0 3 1 55 60 60 7 5 11 0 51 60 50 2 1 0 3 1 59 60 60 50 60 5 0 7 6 70 80 80 2 1 0 3 1 77 80 90 7 5 11 0 74 80 90 2 1 0 3 1 82 90 90 75 90 5 0 7 6 100 110 125 2 1 0 3 1 107 125 125 7 5 11 0 104 125 125 2 1 0 3 1 112 125 125 575 518 633 7 0 55 0 7 0 55 0 9 3 73 0 4 0 1 4 0 7 5 0 6 1 35 40 40 2 1 0 3 1 41 50 45 7 5 9 0 37 45 45 2 1 0 3 1 44 50 50 25 ...

Page 13: ...11 0 49 50 60 2 1 0 3 1 55 60 60 25 30 5 0 7 6 47 50 50 2 1 0 3 1 55 60 60 7 5 11 0 51 60 60 2 1 0 3 1 59 60 60 50 60 5 0 7 6 70 80 80 2 1 0 3 1 77 80 90 7 5 11 0 74 80 90 2 1 0 3 1 82 90 90 75 90 5 0 7 6 100 110 125 2 1 0 3 1 107 125 125 7 5 11 0 104 125 125 2 1 0 3 1 112 125 125 575 518 633 9 3 73 0 9 3 73 0 9 3 73 0 4 0 1 4 0 7 5 0 6 1 39 45 45 2 1 0 3 1 45 50 50 7 5 9 0 42 50 50 2 1 0 3 1 48 5...

Page 14: ...62 80 70 2 1 0 3 1 69 80 80 25 30 7 5 11 0 59 70 70 2 1 0 3 1 66 80 70 10 0 14 0 62 80 70 2 1 0 3 1 69 80 80 50 60 7 5 11 0 74 80 90 2 1 0 3 1 82 90 90 10 0 14 0 78 90 90 2 1 0 3 1 85 90 100 75 90 7 5 11 0 104 125 125 2 1 0 3 1 112 125 125 10 0 14 0 108 125 125 2 1 0 3 1 115 125 150 575 518 633 15 8 100 0 15 8 100 0 6 0 1 4 0 7 7 5 9 0 49 60 60 2 1 0 3 1 55 70 60 10 0 11 0 51 60 60 2 1 0 3 1 57 70...

Page 15: ... 0 16 7 15 2 92 100 100 110 80 90 2 1 0 5 9 107 115 110 125 100 110 38 50 104 120 3 7 10 6 9 6 150 138 150 150 150 150 2 1 0 5 9 164 153 175 175 150 175 5 0 16 7 15 2 157 145 175 150 150 175 2 1 0 5 9 172 160 175 175 175 175 460 414 506 9 5 73 0 9 5 73 0 4 0 1 4 0 7 3 7 4 8 32 40 35 2 1 0 3 1 38 45 40 5 0 7 6 35 40 35 2 1 0 3 1 41 50 45 15 18 3 7 4 8 32 40 35 2 1 0 3 1 40 45 40 5 0 7 6 36 40 35 2 ...

Page 16: ... 49 50 60 25 30 3 7 4 8 47 50 45 2 1 0 3 1 55 60 50 5 0 7 6 51 60 45 2 1 0 3 1 59 60 60 50 60 3 7 4 8 70 80 80 2 1 0 3 1 78 80 90 5 0 7 6 73 80 80 2 1 0 3 1 81 90 90 75 90 3 7 4 8 100 110 110 2 1 0 3 1 108 125 125 5 0 7 6 103 125 125 2 1 0 3 1 111 125 125 575 518 633 7 0 55 0 7 0 55 0 7 0 55 0 4 0 1 4 0 7 3 0 3 9 32 35 35 2 1 0 3 1 39 45 40 5 0 6 1 35 40 35 2 1 0 3 1 41 50 45 25 24 3 0 3 9 39 40 3...

Page 17: ...50 50 2 1 0 3 1 54 60 60 25 30 5 0 7 6 51 60 45 2 1 0 3 1 59 60 60 7 5 11 0 55 60 50 2 1 0 3 1 63 70 60 50 60 5 0 7 6 73 80 80 2 1 0 3 1 81 90 90 7 5 11 0 78 80 90 2 1 0 3 1 85 90 90 75 90 5 0 7 6 103 125 125 2 1 0 3 1 111 125 125 7 5 11 0 108 125 125 2 1 0 3 1 115 125 125 575 518 633 7 0 55 0 7 0 55 0 9 3 73 0 4 0 1 4 0 7 5 0 6 1 38 45 40 2 1 0 3 1 44 50 45 7 5 9 0 40 45 45 2 1 0 3 1 47 50 50 25 ...

Page 18: ...1 0 52 60 60 2 1 0 3 1 58 60 60 25 30 5 0 7 6 51 60 50 2 1 0 3 1 59 60 60 7 5 11 0 55 60 60 2 1 0 3 1 63 70 60 50 60 5 0 7 6 73 80 80 2 1 0 3 1 81 90 90 7 5 11 0 78 80 90 2 1 0 3 1 85 90 90 75 90 5 0 7 6 103 125 125 2 1 0 3 1 111 125 125 7 5 11 0 108 125 125 2 1 0 3 1 115 125 125 575 518 633 9 3 73 0 9 3 73 0 9 3 73 0 4 0 1 4 0 7 5 0 6 1 42 50 45 2 1 0 3 1 48 50 50 7 5 9 0 45 50 50 2 1 0 3 1 51 60...

Page 19: ...80 70 2 1 0 3 1 72 90 80 25 30 7 5 11 0 62 80 70 2 1 0 3 1 69 80 70 10 0 14 0 65 80 70 2 1 0 3 1 72 90 80 50 60 7 5 11 0 78 80 90 2 1 0 3 1 85 90 90 10 0 14 0 81 90 90 2 1 0 3 1 89 100 100 75 90 7 5 11 0 108 125 125 2 1 0 3 1 115 125 125 10 0 14 0 111 125 125 2 1 0 3 1 119 125 150 575 518 633 15 8 100 0 15 8 100 0 6 0 1 4 0 7 7 5 9 0 52 60 60 2 1 0 3 1 58 70 60 10 0 11 0 54 60 60 2 1 0 3 1 60 70 7...

Page 20: ...the last filter into the center of the filter track NOTE For units with manual dampers replace the end filters with the manual dampers Install the filter in the center between the manual dampers 11 Install the filter retainer track along the bottom edge of the outdoor air hood using 4 screws provided See Fig 16 12 Install top section of the outdoor air hood using 9 screws provided See Fig 16 See F...

Page 21: ...D SIDE INNER FILTER TRACK ADD SEAL STRIP ADD SEAL STRIP UNIT BACK PANEL FILTER RETAINER FILTER MANUAL DAMPER IF EQUIPPED MOVEABLE DAMPER AIR FILTER POSITION LOCKING SCREW MOVEABLE DAMPER NOTE Units with manual damper only use one filter Fig 16 Outdoor Air Hood Details Fig 17 Outdoor Air Hood Assembled Fig 18 Manual Damper Details ...

Page 22: ...ndle 1 Open the control box access door 2 Remove the small cover plate located on the unit corner post near the control section 3 Remove the inner control box cover The handle and shaft are located in a plastic bag at the bottom of the control box 4 Insert the square shaft into the disconnect with the pins vertical On the 100 amp disconnect the shaft is keyed into the disconnect and can only be in...

Page 23: ... numbers for particular applications The available field installed accessories for the Centurion units are economizer power exhaust barometric relief damper 14 in roof curb 24 in roof curb electric heaters enthalpy control differential enthalpy control plugged filter indicator carbon dioxide detector smoke detector filter status switch fan status switch condenser hail guard horizontal duct accesso...

Page 24: ...inue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 535 00092 Printed in U S A Form 50HG 7SI Pg 24 11 03 Replaces 50HG 3SI Book 1 4 Tab 1b 6b Copyright 2003 Carrier Corporation ...

Reviews: