Installation Instructions

CONTENTS

Page

SAFETY CONSIDERATIONS

. . . . . . . . . . . . . . . . . . . . . . 1

INSTALLATION

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-23

Step 1 — Provide Unit Support

. . . . . . . . . . . . . . . . . . . 1

• ROOF  CURB
• ALTERNATE UNIT SUPPORT

Step 2 — Remove Shipping Rails

 . . . . . . . . . . . . . . . . 3

Step 3 — Rig and Place Unit

 . . . . . . . . . . . . . . . . . . . . .  3

• POSITIONING
• ROOF MOUNT
• INSTALLATION ONTO CURB

Step 4 — Field Fabricate Ductwork

. . . . . . . . . . . . . . . 8

Step 5 — Make Unit Duct Connections

 . . . . . . . . . . . 8

Step 6 — Trap Condensate Drain

. . . . . . . . . . . . . . . . . 9

Step 7 — Make Electrical Connections

 . . . . . . . . . . . 9

• FIELD POWER SUPPLY
• FIELD CONTROL WIRING

Step 8 — Install Outdoor-Air Hood

 . . . . . . . . . . . . . . 20

Step 9 — Position Optional Power Exhaust

or Barometric Relief Damper Hood

. . . . . . . . . . . . 22

Step 10 — Non-Fused Disconnect

. . . . . . . . . . . . . . . 22

Step 11 — Install All Accessories

 . . . . . . . . . . . . . . . 23

SAFETY CONSIDERATIONS

Installation and servicing of air-conditioning equipment can

be hazardous due to system pressure and electrical compo-
nents. Only trained and qualified service personnel should
install, repair, or service air-conditioning equipment.

Untrained personnel can perform the basic maintenance

functions of replacing filters. All other operations should
be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety
precautions that may apply.

Follow all safety codes. Wear safety glasses and work

gloves. Use quenching cloth for unbrazing operations. Have
fire extinguishers available for all brazing operations. 

   

INSTALLATION

Step 1 — Provide Unit Support

ROOF CURB — Assemble or install accessory roof curb in
accordance with instructions shipped with this accessory. See
Fig. 1. Install insulation, cant strips, roofing, and counter flash-
ing as shown. Ductwork can be installed to roof curb before
unit is set in place. Curb must be level. This is necessary to
permit unit drain to function properly. Unit leveling tolerance is
± 

1

/

16

 in. per linear ft in any direction. Refer to Accessory

Roof Curb Installation Instructions for additional information
as required. When accessory roof curb is used, unit may be
installed on class A, B, or C roof covering material.

ALTERNATE UNIT SUPPORT — When a curb cannot be
used, install unit on a noncombustible surface. Support unit
with sleepers, using unit curb support area. If sleepers cannot
be used, support long sides of unit with a minimum of 3 equal-
ly spaced 4-in. x 4-in. pads on each side.

Before performing service or maintenance operations on
unit, turn off main power switch to unit. Electrical shock
could cause personal injury.

IMPORTANT: Units have high ambient operating lim-
its. If limits are exceeded, the units will automatically
lock the compressor out of operation. Manual reset will
be required to restart the compressor.

IMPORTANT: The gasketing of the unit to the roof curb
is critical for a watertight seal. Install gasket with the
roof curb as shown in Fig. 1. Improperly applied gasket
can also result in air leaks and poor unit performance.

50HG014-028

Single Package Rooftop Units

Electric Cooling with Electric Heat Option

Summary of Contents for COMFORTLINK 50HG014

Page 1: ...ses and work gloves Use quenching cloth for unbrazing operations Have fire extinguishers available for all brazing operations INSTALLATION Step 1 Provide Unit Support ROOF CURB Assemble or install accessory roof curb in accordance with instructions shipped with this accessory See Fig 1 Install insulation cant strips roofing and counter flash ing as shown Ductwork can be installed to roof curb befo...

Page 2: ...2 Fig 1 Roof Curb Details ...

Page 3: ...xhaust vents or other sources of contaminated air Although unit is weatherproof guard against water from higher level runoff and overhangs ROOF MOUNT Check building codes for weight distribu tion requirements Unit operating weight is shown in Table 1 INSTALLATION ONTO CURB The 50HG units are designed to fit on either the accessory full perimeter curb or onto existing 48 50TJ HJ or 48 50DP DR curbs...

Page 4: ...4 Fig 3 Rigging Details ...

Page 5: ...5 Fig 4 Base Unit Dimensions ...

Page 6: ...ve 485 613 472 619 618 789 609 778 658 808 658 808 Std motor Alt drive 618 789 609 778 485 613 472 619 794 974 794 974 Alt motor Std drive 778 1021 778 1021 778 1021 778 1021 949 1145 949 1145 Alt motor Alt drive 1000 1227 1000 1227 1000 1227 1000 1227 1126 1328 1126 1328 Motor Bearing Type Ball Ball Ball Ball Ball Ball Maximum Allowable Rpm 1400 1400 1400 1400 1400 1400 Motor Pulley Pitch Diamete...

Page 7: ... Rpm Range Std motor Std drive 658 808 658 808 799 965 Std motor Alt drive 794 974 794 974 939 1152 Alt motor Std drive 949 1145 949 1145 945 1187 Alt motor Alt drive 1126 1328 1126 1328 1152 1366 Motor Bearing Type Ball Ball Ball Maximum Allowable Rpm 1400 1400 1400 Motor Pulley Pitch Diameter Std motor Std drive 4 3 5 3 4 3 5 3 5 4 6 6 Std motor Alt drive 4 3 5 3 4 3 5 3 4 2 5 2 Alt motor Std dr...

Page 8: ...he factory ready for side supply installation If the horizontal option was not specified at time of ordering the unit a field installed accessory kit is required to convert the vertical unit into a horizontal supply configuration Installation of the duct block off covers should be complet ed prior to placing the unit unless sufficient side clearance is available A minimum of 66 in is required betw...

Page 9: ...with either a Carrier approved accessory thermostat or a Carrier approved space temperature sensor Install thermostat accord ing to the installation instructions included with accessory Locate thermostat assembly or space temperature sensor on a solid interior wall in the conditioned space to sense average temperature Route thermostat or space temperature sensor cable or equivalent single leads of...

Page 10: ...ECTRIC HEAT IFM POWER EXHAUST POWER SUPPLY DISCONNECT SIZE No 1 No 2 No 3 Min Max RLA LRA RLA LRA RLA LRA Qty Hp FLA ea kW FLA Hp FLA Qty Hp FLA ea MCA MOCP FLA 014 208 230 187 253 19 2 146 0 19 2 146 0 4 0 1 4 1 5 3 7 10 6 9 6 60 59 70 70 70 70 2 1 0 5 9 72 71 90 80 80 80 5 0 16 7 15 2 66 64 80 80 80 70 2 1 0 5 9 78 76 90 90 90 90 12 16 33 38 3 7 10 6 9 6 60 60 70 70 70 70 2 1 0 5 9 72 74 90 80 8...

Page 11: ...46 50 60 25 30 3 7 4 8 44 45 45 2 1 0 3 1 51 60 50 5 0 7 6 47 50 45 2 1 0 3 1 55 60 60 50 60 3 7 4 8 66 80 80 2 1 0 3 1 74 80 90 5 0 7 6 70 80 80 2 1 0 3 1 77 80 90 75 90 3 7 4 8 96 110 110 2 1 0 3 1 104 110 125 5 0 7 6 100 110 125 2 1 0 3 1 107 125 125 575 518 633 7 0 55 0 7 0 55 0 7 0 55 0 4 0 1 4 0 7 3 0 3 9 29 35 35 2 1 0 3 1 36 40 40 5 0 6 1 32 35 35 2 1 0 3 1 38 40 45 25 24 3 0 3 9 35 35 35 ...

Page 12: ...50 50 2 1 0 3 1 51 60 60 25 30 5 0 7 6 47 50 45 2 1 0 3 1 55 60 60 7 5 11 0 51 60 50 2 1 0 3 1 59 60 60 50 60 5 0 7 6 70 80 80 2 1 0 3 1 77 80 90 7 5 11 0 74 80 90 2 1 0 3 1 82 90 90 75 90 5 0 7 6 100 110 125 2 1 0 3 1 107 125 125 7 5 11 0 104 125 125 2 1 0 3 1 112 125 125 575 518 633 7 0 55 0 7 0 55 0 9 3 73 0 4 0 1 4 0 7 5 0 6 1 35 40 40 2 1 0 3 1 41 50 45 7 5 9 0 37 45 45 2 1 0 3 1 44 50 50 25 ...

Page 13: ...11 0 49 50 60 2 1 0 3 1 55 60 60 25 30 5 0 7 6 47 50 50 2 1 0 3 1 55 60 60 7 5 11 0 51 60 60 2 1 0 3 1 59 60 60 50 60 5 0 7 6 70 80 80 2 1 0 3 1 77 80 90 7 5 11 0 74 80 90 2 1 0 3 1 82 90 90 75 90 5 0 7 6 100 110 125 2 1 0 3 1 107 125 125 7 5 11 0 104 125 125 2 1 0 3 1 112 125 125 575 518 633 9 3 73 0 9 3 73 0 9 3 73 0 4 0 1 4 0 7 5 0 6 1 39 45 45 2 1 0 3 1 45 50 50 7 5 9 0 42 50 50 2 1 0 3 1 48 5...

Page 14: ...62 80 70 2 1 0 3 1 69 80 80 25 30 7 5 11 0 59 70 70 2 1 0 3 1 66 80 70 10 0 14 0 62 80 70 2 1 0 3 1 69 80 80 50 60 7 5 11 0 74 80 90 2 1 0 3 1 82 90 90 10 0 14 0 78 90 90 2 1 0 3 1 85 90 100 75 90 7 5 11 0 104 125 125 2 1 0 3 1 112 125 125 10 0 14 0 108 125 125 2 1 0 3 1 115 125 150 575 518 633 15 8 100 0 15 8 100 0 6 0 1 4 0 7 7 5 9 0 49 60 60 2 1 0 3 1 55 70 60 10 0 11 0 51 60 60 2 1 0 3 1 57 70...

Page 15: ... 0 16 7 15 2 92 100 100 110 80 90 2 1 0 5 9 107 115 110 125 100 110 38 50 104 120 3 7 10 6 9 6 150 138 150 150 150 150 2 1 0 5 9 164 153 175 175 150 175 5 0 16 7 15 2 157 145 175 150 150 175 2 1 0 5 9 172 160 175 175 175 175 460 414 506 9 5 73 0 9 5 73 0 4 0 1 4 0 7 3 7 4 8 32 40 35 2 1 0 3 1 38 45 40 5 0 7 6 35 40 35 2 1 0 3 1 41 50 45 15 18 3 7 4 8 32 40 35 2 1 0 3 1 40 45 40 5 0 7 6 36 40 35 2 ...

Page 16: ... 49 50 60 25 30 3 7 4 8 47 50 45 2 1 0 3 1 55 60 50 5 0 7 6 51 60 45 2 1 0 3 1 59 60 60 50 60 3 7 4 8 70 80 80 2 1 0 3 1 78 80 90 5 0 7 6 73 80 80 2 1 0 3 1 81 90 90 75 90 3 7 4 8 100 110 110 2 1 0 3 1 108 125 125 5 0 7 6 103 125 125 2 1 0 3 1 111 125 125 575 518 633 7 0 55 0 7 0 55 0 7 0 55 0 4 0 1 4 0 7 3 0 3 9 32 35 35 2 1 0 3 1 39 45 40 5 0 6 1 35 40 35 2 1 0 3 1 41 50 45 25 24 3 0 3 9 39 40 3...

Page 17: ...50 50 2 1 0 3 1 54 60 60 25 30 5 0 7 6 51 60 45 2 1 0 3 1 59 60 60 7 5 11 0 55 60 50 2 1 0 3 1 63 70 60 50 60 5 0 7 6 73 80 80 2 1 0 3 1 81 90 90 7 5 11 0 78 80 90 2 1 0 3 1 85 90 90 75 90 5 0 7 6 103 125 125 2 1 0 3 1 111 125 125 7 5 11 0 108 125 125 2 1 0 3 1 115 125 125 575 518 633 7 0 55 0 7 0 55 0 9 3 73 0 4 0 1 4 0 7 5 0 6 1 38 45 40 2 1 0 3 1 44 50 45 7 5 9 0 40 45 45 2 1 0 3 1 47 50 50 25 ...

Page 18: ...1 0 52 60 60 2 1 0 3 1 58 60 60 25 30 5 0 7 6 51 60 50 2 1 0 3 1 59 60 60 7 5 11 0 55 60 60 2 1 0 3 1 63 70 60 50 60 5 0 7 6 73 80 80 2 1 0 3 1 81 90 90 7 5 11 0 78 80 90 2 1 0 3 1 85 90 90 75 90 5 0 7 6 103 125 125 2 1 0 3 1 111 125 125 7 5 11 0 108 125 125 2 1 0 3 1 115 125 125 575 518 633 9 3 73 0 9 3 73 0 9 3 73 0 4 0 1 4 0 7 5 0 6 1 42 50 45 2 1 0 3 1 48 50 50 7 5 9 0 45 50 50 2 1 0 3 1 51 60...

Page 19: ...80 70 2 1 0 3 1 72 90 80 25 30 7 5 11 0 62 80 70 2 1 0 3 1 69 80 70 10 0 14 0 65 80 70 2 1 0 3 1 72 90 80 50 60 7 5 11 0 78 80 90 2 1 0 3 1 85 90 90 10 0 14 0 81 90 90 2 1 0 3 1 89 100 100 75 90 7 5 11 0 108 125 125 2 1 0 3 1 115 125 125 10 0 14 0 111 125 125 2 1 0 3 1 119 125 150 575 518 633 15 8 100 0 15 8 100 0 6 0 1 4 0 7 7 5 9 0 52 60 60 2 1 0 3 1 58 70 60 10 0 11 0 54 60 60 2 1 0 3 1 60 70 7...

Page 20: ...the last filter into the center of the filter track NOTE For units with manual dampers replace the end filters with the manual dampers Install the filter in the center between the manual dampers 11 Install the filter retainer track along the bottom edge of the outdoor air hood using 4 screws provided See Fig 16 12 Install top section of the outdoor air hood using 9 screws provided See Fig 16 See F...

Page 21: ...D SIDE INNER FILTER TRACK ADD SEAL STRIP ADD SEAL STRIP UNIT BACK PANEL FILTER RETAINER FILTER MANUAL DAMPER IF EQUIPPED MOVEABLE DAMPER AIR FILTER POSITION LOCKING SCREW MOVEABLE DAMPER NOTE Units with manual damper only use one filter Fig 16 Outdoor Air Hood Details Fig 17 Outdoor Air Hood Assembled Fig 18 Manual Damper Details ...

Page 22: ...ndle 1 Open the control box access door 2 Remove the small cover plate located on the unit corner post near the control section 3 Remove the inner control box cover The handle and shaft are located in a plastic bag at the bottom of the control box 4 Insert the square shaft into the disconnect with the pins vertical On the 100 amp disconnect the shaft is keyed into the disconnect and can only be in...

Page 23: ... numbers for particular applications The available field installed accessories for the Centurion units are economizer power exhaust barometric relief damper 14 in roof curb 24 in roof curb electric heaters enthalpy control differential enthalpy control plugged filter indicator carbon dioxide detector smoke detector filter status switch fan status switch condenser hail guard horizontal duct accesso...

Page 24: ...inue or change at any time specifications or designs without notice and without incurring obligations PC 111 Catalog No 535 00092 Printed in U S A Form 50HG 7SI Pg 24 11 03 Replaces 50HG 3SI Book 1 4 Tab 1b 6b Copyright 2003 Carrier Corporation ...

Reviews: