ELECTRICAL DATA
UNIT SIZE
--- VOLTAGE,
SERIES
V/PH
OPER
VOLTS*
COMPR
FAN
MCA
MIN
WIRE
SIZE
{
MIN
WIRE
SIZE
{
MAX
LENGTH
ft (m)
}
MAX
LENGTH
ft (m)
}
MAX
FUSE**
or CKT
BRK
AMPS
MAX
MIN.
LRA
RLA
FLA
60
°
C
75
°
C
60
°
C
75
°
C
18---30
208---230---1
253
197
48.0
9.0
0.5
11.8
14
14
67 (20.4)
64 (19.5)
15
24---30
58.3
13.5
0.75
17.6
14
14
45 (13.7)
43 (13.1)
25
30---30
64.0
12.8
0.75
16.8
14
14
47 (14.3)
45 (13.7)
25
36---30
77.0
14.1
1.4
19.0
12
12
66 (20.1)
63 (19.2)
30
42---30
112.0
17.9
1.2
23.6
12
12
53 (16.2)
51 (15.5)
40
48---30
109.0
19.9
1.2
26.2
10
10
76 (23.2)
73 (22.3)
40
60---30
134.0
26.4
1.2
34.2
8
8
91 (27.7)
86 (262)
50
30---50
208/230---3
253
197
58.0
10.1
0.75
13.4
14
14
68 (20.7)
65 (19.8)
20
36---50
71.0
9.2
1.4
12.9
14
14
70 (21.3)
67 (20.4)
20
42---50
88.0
13.5
1.2
18.1
12
12
80 (24.4)
76 (23.2)
30
48---50
83.1
13.6
1.2
18.2
12
12
79 (24.1)
76 (23.2)
30
60---50
110.0
17.7
1.2
23.3
12
12
62 (18.9)
59 (18.0)
40
36---60
460---3
506
414
38.0
5.6
0.7
7.8
14
14
233 (71.0)
222 (67.7)
15
42---60
44.0
6.0
0.53
8.0
14
14
227 (69.2)
216 (65.8)
15
48---60
41.0
6.1
0.6
8.2
14
14
222 (67.7)
211 (64.3)
15
60---60
52.0
7.8
0.6
10.3
14
14
177 (54.0)
168 (51.2)
15
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{
If wire is applied at ambient greater than 30
˚
C (86
˚
F), consult table 310---16 of the NEC (ANSI/NFPA 70). The ampacity of non---metallic---sheathed cable
(NM), trade name ROMEX, shall be that of 60
˚
C (140
˚
F) conditions, per the NEC (ANSI/NFPA 70) Article 336---26. If other than uncoated (no---plated), 60
_
or 75
˚
C (140
_
or 167
˚
C) insulation, copper wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables
of the NEC (ANSI/NFPA 70).
}
Length shown is as measured 1 way along wire path between unit and service panel for voltage drop not to exceed 2%.
** Time---Delay fuse.
FLA
--- Full Load Amps
LRA
--- Locked Rotor Amps
MCA
--- Minimum Circuit Amps
RLA
--- Rated Load Amps
NOTE
: Control circuit is 24---V on all units and requires external power source. Copper wire must be used from service disconnect to unit. All
motors/compressors contain internal overload protection.
Complies with 2001 requirements of ASHRAE Standards 90.1
A--WEIGHTED SOUND POWER (dBA)
UNIT SIZE --- VOLTAGE, SERIES
STANDARD
RATING
(dBA)
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125
250
500
1000
2000
4000
8000
18---30
74
50.0
61.5
64.5
66.5
64.0
61.0
54.5
24---30
74
55.5
63.5
67.0
70.0
66.0
63.5
57.0
30---30, 50
74
52.5
63.0
68.5
70.0
66.5
62.5
56.5
36---30, 50, 60
74
57.0
65.0
67.5
69.5
67.5
65.0
60.0
42---30, 50, 60
74
55.0
64.0
68.0
68.5
64.5
60.0
54.0
48---30, 50, 60
74
52.5
62.5
65.5
69.0
63.5
60.5
56.0
60---30, 50, 60
74
54.0
59.0
65.5
67.5
63.5
60.0
55.5
NOTE
: Tested in accordance with ARI Standard 270---95 (not listed in ARI).
CHARGING SUBCOOLING (TXV--TYPE EXPANSION DEVICE)
UNIT SIZE---VOLTAGE, SERIES
REQUIRED SUBCOOLING
_
F (
_
C)
18---30
8 (4.4)
24---30
13 (7.2)
30---30, 50
16 (8.9)
36---30, 50, 60
16 (8.9)
42---30, 50, 60
10 (5.6)
48---30, 50, 60
17 (9.4)
60---30, 50, 60
11 (6.1)
24AC
B
3