background image

3

Field-supplied
Plenum

Field
Coil
Support Shelf

Furnace

See
Table 1 

A

3

16

1

16

1

4

 

1

2

 6

19 

3

16

(487)

(13)

(27)

(30)

(152)

(57)

A08336

Fig. 1 -- Correct Orientation of Coil Support on Furnace

Installation of Furnace Coils

Upflow Cased Coil Installation
NOTE

: On upflow installations where the indoor coil is placed in

an unconditioned space, a 6” (152 mm) wide piece of insulation
should be applied and wrapped around the outside of coil casing
and supply duct contact point.

1. Set coil in place on upflow furnace discharge air opening.

See Fig. 2.

2. When coil front width matches furnace front width, the coil

can be placed directly on furnace.

3. Ensure coil is level for proper condensate drainage. Do not

tip coil toward condensate drain. Coil enclosure need not be

fastened or screwed to furnace.

Supply

Upflow
Furnace

Downflow
Furnace

Evaporator
Coil

Return

Return

Supply

A05411

Fig. 2 -- Typical Coil Installation

NOTE

: When CNPVT/CNRVT (transition coils) are applied to

same width furnace, remove block--off plates at casing base by
removing 2 screws per plate from side of casing. See Fig. 3.

Block-Off

Plates

A05412

Fig. 3 -- Block--Off Plate Removal

TRANSITION MODEL COILS APPLIED CENTERED OVER

NARROW FURNACE

1. There is no transition required for this application.
2. Remove coil from packaging and place on top of furnace

with 1 5/8” (41 mm) overhang on both sides. See Fig. 4,
Alternative A.

3. Continue with normal installation practices. See Connect

Refrigerant Piping.

STANDARD MODEL COIL APPLIED CENTERED OVER
NARROW FURNACE WITH 2 1/4” (57 mm) MINIMUM

TRANSITION

1. Prepare transition, following recommended transition draw-

ing. See Fig. 5. Fabricate a 2 1/4” (57 mm) tall (minimum)
transition.

2. Place transition on top of gas furnace. See Fig. 4, Alternat-

ive B. Secure with sheet metal screws. Place coil on top of

transition. Make sure coil rests evenly on top of transition
and gas furnace.

3. Secure coil to transition using sheet metal screws.
4. Continue with normal installation practices. See Connect

Refrigerant Piping.

NOTE

: If coil (cased or uncased) is not being installed in the

standard orientation (front of coil matching front of furnace) then
coil must be raised 2 1/4” (57 mm) above furnace.

CNP

VP

/CNR

VP

Summary of Contents for CNPVP, CNRVP

Page 1: ...G signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation IMPORTANT Nitrogen can leak out through the hole that the needle pierced in the plugs This does not indicate ...

Page 2: ...e coil or lack of air to a slab in the coil It is recommended that on this type of application a field supplied adapter be placed between the coil and furnace to allow air to distribute properly between all slabs of the coil To install cased coils in upflow applications follow the instructions below Upflow Cased Coil Installation To install cased coils in downflow applications follow the instructi...

Page 3: ...ock off plates at casing base by removing 2 screws per plate from side of casing See Fig 3 Block Off Plates A05412 Fig 3 Block Off Plate Removal TRANSITION MODEL COILS APPLIED CENTERED OVER NARROW FURNACE 1 There is no transition required for this application 2 Remove coil from packaging and place on top of furnace with 1 5 8 41 mm overhang on both sides See Fig 4 Alternative A 3 Continue with nor...

Page 4: ...on en tirely on left side as in Fig 4 Alternative C Mark location of gas furnace flange on coil casing Remove coil from top of furnace Using tin snips make a notch in rail large enough to allow clearance for gas flow furnace flange 2 Place coil on top of gas furnace Make sure coil is shifted completely to left side and notch is sufficient so coil rests on top of furnace cabinet 3 Prepare and insta...

Page 5: ...ctions The coil can be connected to outdoor units using accessory tubing packages or field supplied tubing of refrigerant grade Always evacuate tubing and reclaim refrigerant when making connections or flaring tubing Leak check connections before insulating entire suction line SUCTION LINE Suction line is designed for field sweat connection Line is plugged to keep out moisture and dirt Remove thes...

Page 6: ...t for leaks and insulate traps and lines if located above a living area Consult local codes for additional restrictions or precautions Humidifier Application When installing a humidifier in a system which contains an N coil consideration must be given to location of coil slabs See Fig 9 1 Care must be taken to prevent damage of N coil when at taching humidifier to coil casing or plenum 2 The model...

Reviews: