CNPVP

CNRVP

Installation Instructions

Cased N Coils

Upflow --- Downflow

Heating --- Cooling

NOTE

: Read the entire instruction manual before starting the

installation.

TABLE OF CONTENTS

PAGE

SAFETY CONSIDERATIONS

1

. . . . . . . . . . . . . . . . . . . . . . . . .

INTRODUCTION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

INSTALLATION

1

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Inspect Equipment

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Select Installation

2

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Installation of Furnace Coils

3

. . . . . . . . . . . . . . . . . . . . . . . .

Connect Refrigerant Piping

5

. . . . . . . . . . . . . . . . . . . . . . . . .

Connect Refrigerant, Liquid and Suction Lines

5

. . . . . . . . . .

Refrigerant Metering Device

5

. . . . . . . . . . . . . . . . . . . . . . . .

Condensate Drain Line Connection

5

. . . . . . . . . . . . . . . . . . .

Humidifier Application

6

. . . . . . . . . . . . . . . . . . . . . . . . . . . .

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,

or use can cause explosion, fire, electrical shock, or other
conditions which may cause personal injury or property damage.

Consult a qualified installer, service agency, or your distributor or

branch for information or assistance. The qualified installer or
agency must use factory--authorized kits or accessories when

modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses and work gloves. Use

quenching cloth for brazing operations. Have fire extinguisher
available. Read these instructions thoroughly and follow all

warning or cautions attached to the unit. Consult local building
codes and National Electrical Code (NEC) for special

requirements.
It is important to recognize safety information. This is the safety

alert symbol

. When you see this symbol on the unit and in

instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety--alert symbol.

DANGER identifies the most serious hazards which

will

result in

severe personal injury or death. WARNING signifies hazards

which

could

result in personal injury or death. CAUTION is used

to identify unsafe practices which

may

result in minor personal

injury or product and property damage. NOTE is used to highlight

suggestions which

will

result in enhanced installation, reliability, or

operation.

IMPORTANT

: Nitrogen can leak out through the hole that the

needle pierced in the plugs. This does not indicate a leaking coil
nor warrant return of the coil.

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury

or death.
Before installing, modifying or servicing system, always turn

off main power to system. There may be more than one

disconnect switch. Lock out and tag switch with a suitable

warning label.

!

WARNING

PERSONAL INJURY HAZARD

Failure to follow this caution may result in personal injury.
This coil contains Nitrogen precharge of 15 PSIG. Release of this

pressure through the center of the rubber plugs is required before

removing the plugs.

CAUTION

!

CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and

wear appropriate protective clothing and gloves when handling

parts.

CAUTION

!

INTRODUCTION

Use this instruction manual to install indoor coils on upflow or

downflow furnaces. Do not install coil in horizontal position.
Models CNPVP/CNRVP are enclosed in a painted casing and both

coils have factory--installed TXV’s. CNPVP models are used with

Puron (R--410A) systems and CNRVP models are used with R--22
systems.

NOTE

: Models with tin--plated copper coils, “T” in the 11th

position of the model number, are installed the same as standard
copper coils.

INSTALLATION

These units can be installed in multiple configurations. Before
installation, there are several performance requirements that must

be considered because poor installation can negatively alter
performance. This section will briefly discuss those factors.

Summary of Contents for CNPVP, CNRVP

Page 1: ...G signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation IMPORTANT Nitrogen can leak out through the hole that the needle pierced in the plugs This does not indicate ...

Page 2: ...e coil or lack of air to a slab in the coil It is recommended that on this type of application a field supplied adapter be placed between the coil and furnace to allow air to distribute properly between all slabs of the coil To install cased coils in upflow applications follow the instructions below Upflow Cased Coil Installation To install cased coils in downflow applications follow the instructi...

Page 3: ...ock off plates at casing base by removing 2 screws per plate from side of casing See Fig 3 Block Off Plates A05412 Fig 3 Block Off Plate Removal TRANSITION MODEL COILS APPLIED CENTERED OVER NARROW FURNACE 1 There is no transition required for this application 2 Remove coil from packaging and place on top of furnace with 1 5 8 41 mm overhang on both sides See Fig 4 Alternative A 3 Continue with nor...

Page 4: ...on en tirely on left side as in Fig 4 Alternative C Mark location of gas furnace flange on coil casing Remove coil from top of furnace Using tin snips make a notch in rail large enough to allow clearance for gas flow furnace flange 2 Place coil on top of gas furnace Make sure coil is shifted completely to left side and notch is sufficient so coil rests on top of furnace cabinet 3 Prepare and insta...

Page 5: ...ctions The coil can be connected to outdoor units using accessory tubing packages or field supplied tubing of refrigerant grade Always evacuate tubing and reclaim refrigerant when making connections or flaring tubing Leak check connections before insulating entire suction line SUCTION LINE Suction line is designed for field sweat connection Line is plugged to keep out moisture and dirt Remove thes...

Page 6: ...t for leaks and insulate traps and lines if located above a living area Consult local codes for additional restrictions or precautions Humidifier Application When installing a humidifier in a system which contains an N coil consideration must be given to location of coil slabs See Fig 9 1 Care must be taken to prevent damage of N coil when at taching humidifier to coil casing or plenum 2 The model...