background image

7

10a. Determine where the flexible conduit will pass through the house from inside to outside.

When you are certain you have clearance on each side and within the wall, drill a small pilot
hole through the wall to mark the location. 

10b. Using a hole saw, drill a 1-3/4 inch diameter hole in the house’s wall to allow the conduit

to fit through.

11a.  From the inside of the house, feed the end of the 30-foot conduit (which is pre-wired from

transfer switch) through the wall to outside. 

11b. Remove the threaded lock nut from the conduit coupling.

11c. Lift cover. Remove internal cover plate screw and internal cover.

Remove the knock out in the lower right corner of the external
connection box. From the rear of the connection box, feed wires
& 4 pin plug into box. Slip the lock nut over wires and plug and
tighten securely onto conduit coupling. Using appropriate
fasteners, mount external connection box over pre-drilled hole to
fully conceal the hole. Seal around the hole and conduit with
silicone caulk from both the inside and outside of the home.
Also, caulk around the sides and top of the box to seal the edges to the siding or wall.
Connect wires to lugs; Black to black, white to white, and red to red. Torque nuts to 20
in/lbs. Snap together the 4-pin plug connector. Loosen nut from grounding lug and attach
ground wire (green) from conduit. Reinstall nut and tighten to 45 in/lbs. Reinstall internal
cover plate and screw. Close cover and install lock. This wiring is complete. 

STEP 3

CONNECTION TO EXTERNAL CONNECTION BOX

Silicone Caulk

The outer diameter of  the conduit connector is 1-1/16”

10a

10b

1-3/4” Diameter Hole

1-3/4” Diameter Hole

The outer diameter of the threaded end is 15/16”.

11a

11b

STEP 4 

MOUNTING THE AUTOMATIC TRANSFER SWITCH

12. Locate automatic transfer switch with built-in emergency load  center within one foot of

main distribution panel. The automatic
transfer switch with built-in load center can
be located to the left or right of main
distribution panel. Hold transfer switch
against the mounting surface. Level the
transfer switch and mark the mounting
holes. Drill the appropriate size pilot holes.
Mount automatic transfer switch with built-
in load center to mounting surface with
appropriate fasteners.

13a. Remove the main electrical distribution panel cover. Remove

appropriate size knockout from the bottom or side of the main panel.
(A 2-foot flexible conduit is pre-wired from the transfer switch with
built-in load center.) Remove threaded lock nut from conduit
coupling.  Feed all wires through knockout into main panel. Slip lock
nut over wires and tighten securely on conduit coupling.  Remove the
black (hot) wire from a circuit breaker that protects a circuit you
want to have powered in the event of a power failure.

- continued on

page 8

STEP 5

CONNECTION OF EMERGENCY CIRCUITS

11c

Knockout

Although you may choose to perform
electrical connections yourself,
CARRIER recommends that a

licensed electrician or individual with complete
knowledge of electricity perform the procedures
in sections 12, 13a, and 13b.

Switch service main circuit breaker
to off” or open position prior to 
removal of cover or removal of any

wiring of the main electrical distribution panel.
The wires connected to
the service main circuit
breaker remain live or
“hot”.  Avoid contact with
these wires and the
service main circuit breaker connection lugs.

NOTE: Balance must be maintained when moving
circuit locations from main electrical
distribution panel to emergency load center.
Circuit breaker positions alternate buss bars
vertically. Circuits sharing a neutral wire should
either be moved together to adjacent positions in
emergency load center or not moved. If you are
unsure of proper procedure or if your installation
differs from that described in this guide, consult
a licensed professional at this time.

1 ft.

12

13a

Ground 
Screw   

DANGER 

DANGER 

 

WARNING

The external connection box must be locked to

ensure safety and to discourage tampering.

Reviews: