background image

Optical smoke alarm device

Commercial reference: 2106-008

Developed by CAVIUS
The smoke alarm is designed for private homes.  

SAFETY INSTRUCTIONS:

The device comes with a 3V lithium battery. 

Bat-teries are to be handled with care and battery 

pow-ered devices should be kept out of reach of 

chil-dren. Do not try to recharge or burn the bat-

teries. 
TECHNICAL INFORMATION:

The maximum number of alarms that can be inter-

linked within a house group are 32. 

Please note: These must be alarms from the CAVIUS 

The distance between interlinked alarms depends 

on the house layout and they should always be 

tested after installation. It is not advised to get 

more than 10m distance between two smoke 

alarms.
Diameter: 78mm. Height: 44mm

The alarm is powered by a non-replaceable 10 

year battery (pack of 2 CR123A Lithium batteries).

In normal situations, minimum battery life is 10 

years, but severe RF interferences may affect 

battery life of your device.
Certified to EN 14604 : 2005 + AC2008 , EN 3000-

220

1. HOW TO SET UP AND CONNECT ALARMS: 
Please note: The product label must not be 

removed as it contains important information 

regarding the product. 
All alarms that need to be connected in the 

house should be put into ‘Learn Mode’ by sliding 

the switch on the back of the alarm to the ‘Learn 

Mode’ position. 
The red LED will light up to indicate that ‘Learn 

Mode’ has been selected. 

Please note that when the alarms are placed 

in ‘Learn Mode’ they can’t be inserted into the 

mounting base. 

Press and hold the test button at one alarm only, 

until  it  beeps  and  the  LED  flashes.  This  alarm 

will send out a specific house code to the other 

alarms. 

As  the  other  alarms  receive  the  specific  house 

code, they will also flash the LED light.

When  the red LED light flashes on all alarms, 

they are connected and MUST BE SWITCHED 

OUT OF ‘LEARN MODE’ and installed.  
Label the original “Learn” alarm in order to easily 

add new Cavius Wireless Family alarms to the 

system.
2. THE BEST AREAS TO INSTALL THE SMOKE 

ALARM:

• Install an alarm between possible fire sources 

and bedrooms as a minimum.

• Install alarms on each floor of the house, in hall-

ways and stairways. 

• Alarms in each room such as bed rooms and 

living rooms. Additional alarms increase the se-

curity.

3. AREAS WHERE NOT TO INSTALL SMOKE-

ALARMS:

• In dusty rooms.
• At the top of a high pointed ceiling, in ceiling 

corners, and within 30cm of a wall.

• In rooms where the temperature goes out side 

+4

o

 to 38

o

C or above 90% relative humidity not 

condensing.

• In kitchens, garages, laundries, or too close to 

fireplaces; areas where either dampness, gases 

or smoke could occur.

Place the alarm where it is reachable in order to 

test the battery and for maintenance. 
4. PLACEMENT:
Centrally located ceiling mounted is preferred but 

if must fit on a wall please consider the following:
For ceiling installation:

The smoke alarm should be a minimum of 30cm 

from the wall. 

For catheral or peak ceiling or wall installation:

With a minimum of one smoke alarm per floor and 

a maximum distance between smoke alarms of 

10 meters. 
5. INSTALLING THE SMOKE ALARM:
Detach the alarm from the mounting base by 

twisting counter clockwise.

MOUNTING

BASE

CHAMBER

FILTER

TEST BUTTON

RED LED

UK

Peak ceiling

Minimum 50cm 

from peak

Minimum 30cm and 

maximum 50cm from 

ceiling

Wall

Ceiling

Minimum30cm 

from wall

Wall

Ceiling

LEARN MODE

NORMAL MODE

MARK UP 

SCREW HOLES 

WITH A PEN

Optical

Siting of Optical Smoke alarms

PLEASE READ THE INSTALLATION GUIDE 

CAREFULLY BEFORE INSTALLATION AND 

RETAIN FOR FUTURE USE.