background image

4

3” (76mm)

A13067

Fig. 4 

 

Condensate Trap

NOTE

:  The unit is shipped from the factory with the horizontal

drain connections capped as for vertical installations. For
horizontal installations, remove the caps and place them on the
vertical drain connections to keep an airtight installation.

NOTE

:  If unit is located in or above a living space, where damage

may result from condensate overflow, a field

supplied, external

condensate pan should be installed underneath the entire unit, and a
secondary condensate line (with appropriate trap) should be run
from the unit into the pan. Any condensate in this external
condensate pan should be drained to a noticeable place. As an
alternative to using an external condensate pan, some localities
may allow the running of a separate 3/4

in. (19 mm) condensate

line (with appropriate trap) per local code to a place where the
condensate will be noticeable. The owner of the structure must be
informed that when condensate flows from secondary drain or
external condensate pan, the unit requires servicing or water
damage will occur. To further protect against water damage, install
a float switch to shut the unit off if the water in the secondary pan
gets too high.

NOTE

:  To avoid drainage problems, test the primary drain line by

slowly pouring water into the pan. Check piping for leaks and
proper condensate drainage. Using the secondary drain as
explained in the previous note provides further protection against
overflow due to a clogged primary drain.

NOTE

:  

In applications where return air humidity levels stay at

70% or above for a prolonged period of time, condensation can
form on the bottom of pan and drip.

Condensate
Line

Trap

Sewer Line

Air Gap Above
Liquid Level

A10216

Fig. 5 

 

Condensate Drain to Waste Line

WASTE LINE CONNECTION

If the condensate line is to be connected to a waste (sewer) line, an

open trap must be installed ahead of the waste line to prevent

escape of sewer gases (See Fig. 5).

EXPLOSION HAZARD

Failure to follow this warning could

result in death, serious personal injury,

and/or property damage.
Provide trap with air gap in drain line

when connecting to waste (sewer) line.

!

WARNING

CARE AND MAINTENANCE

To continue high performance and minimize possible equipment

failure, it is essential that periodic maintenance be performed on

this equipment. Consult your local dealer as to the proper

frequency of maintenance, but it should be done at least annually.
The ability to properly perform maintenance on this equipment

requires certain mechanical skills and tools. If you do not possess

these, contact your dealer for maintenance. The only consumer

service recommended or required is  filter replacement or cleaning

on a monthly basis.

ENVIRONMENTAL HAZARD

Failure to follow this caution may result in environmental

damage.
Remove and recycle all components or materials (i.e., oil,

refrigerant, etc.) before unit final disposal.

CAUTION

!

Copyright 2019 CAC / BDP 

D

  7310 W. Morris St. 

D

  Indianapolis, IN  46231                         Edition Date: 08/19

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Catalog No:  IM-CAPVP-03

Replaces: IM-CAPVP-02

  CAPVP  

Summary of Contents for CAPVP1917ALA

Page 1: ... WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE is used to highlight suggestions which will result in enhanced installation reliability or operation ELECTRICAL SHOCK HAZARD Failure to follow this warning could result in personal injury or death Before...

Page 2: ... screwed to furnace 3 When installing wider coil on narrow furnace create field fabricatedadapter See Fig 2 4 When installing narrow coil on wide furnace create field fabricatedadapter See Fig 2 NOTE On upflow installations where the indoor coil is placed in an unconditioned space a 6 152 mm wide piece of insulation should be applied and wrapped around the outside of coil casing and supply duct co...

Page 3: ...evice while brazing valves must be wrapped with a heat sinking material such as a wet cloth CAUTION PERSONAL INJURY HAZARD Failure to follow this warning could result in personal injury Wear eye protection Coil is factory charged with 15 psi nitrogen The coil is under pressure and TXV screen is in place behind liquid line plug DO NOT removed liquid line plug first always remove the suction line pl...

Page 4: ...d primary drain NOTE In applications where return air humidity levels stay at 70 or above for a prolonged period of time condensation can form on the bottom of pan and drip Condensate Line Trap Sewer Line Air Gap Above Liquid Level A10216 Fig 5 Condensate Drain to Waste Line WASTE LINE CONNECTION If the condensate line is to be connected to a waste sewer line an open trap must be installed ahead o...

Reviews: