92
SYSTEM DESIGN SUMMARY
1. Intended for outdoor installation with free air inlet and outlet. Outdoor fan external static pressure available is less than 0.01--in. wc.
2. Minimum outdoor operating air temperature for cooling mode without low--ambient operation accessory is 55
_
F (12.8
_
C).
3. Maximum outdoor operating air temperature is 125
_
F (51.7
_
C).
4. For reliable operation, unit should be level in all horizontal planes.
5. For interconnecting refrigerant tube lengths greater than 80 ft (23.4 m) and/or 35 ft (10.7 m) vertical differential, consult Residential
Piping and Longline Guideline and Service Manual available from equipment distributor.
6. If any refrigerant tubing is buried, provide a 6 in. (152.4 mm) vertical rise to the valve connections at the unit. Refrigerant tubing
lengths up to 36 in. (914.4 mm) may be buried without further consideration. Do not bury refrigerant lines longer than 36 in. (914.4
mm).
7. Use only copper wire for electric connection at unit. Aluminum and clad aluminum are not acceptable for the type of connector
provided.
8. Do not apply capillary tube indoor coils to these units.
9. Factory--supplied filter drier must be installed.
Copyright 2011 Carrier Corp.
S
7310 W. Morris St.
S
Indianapolis, IN 46231
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Catalog No: CA16NA---04PD
Replaces: CA16NA--- 03PD
Printed in U.S.A.
Edition Date: 08/11
C
A
16N
A
Summary of Contents for CA16NA 018
Page 10: ...10 DIMENSIONS ENGLISH 18 30 CA16NA ...
Page 11: ...11 DIMENSIONS ENGLISH 36 61 CA16NA ...
Page 12: ...12 DIMENSIONS SI 18 30 CA16NA ...
Page 13: ...13 DIMENSIONS SI 36 61 CA16NA ...