background image

315S: Installation Instructions

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

2

A07588

Fig. 1 – Piping Installation

Installation

IMPORTANT: 

Effective January 1, 2015, all split system and packaged

air  conditioners  must  be  installed  pursuant  to  applicable  regional

efficiency standards issued by the Department of Energy.

Check Equipment and Job Site

Unpack Unit

Move to final location. Remove carton taking care not to damage unit. 

Inspect Equipment

File  claim  with  shipping  company  prior  to  installation  if  shipment  is

damaged or incomplete. Locate unit rating plate on unit corner panel. It

contains information needed to properly install unit. Check rating plate

to be sure unit matches job specifications.

Rig and Mount Unit

Mount unit on a solid, level concrete pad. Position unit so water or ice

from roof does not fall directly onto unit. Use field-provided snow stand

or  ice  rack  where  prolonged  subfreezing  temperatures  or  heavy  snow

occurs. If conditions or local codes require unit be fastened to a pad, use

six (6) field-supplied tie-down bolts to fasten through slots provided in

unit mounting feet. 

Mounting on Roof

Mount unit on a level platform or frame at least 6 in. (152 mm)
above roof surface. Isolate unit and tubing from structure.
On rooftop applications, mount on level platform or frame. Place unit

above a load-bearing wall and isolate unit and tubing set from structure.

Arrange supporting members to adequately support unit and minimize

transmission  of  vibration  to  building.  Consult  local  codes  governing

rooftop applications.

NOTE: 

Unit must  be level to within ±2° (±3/8 in./ft.±9.5 mm/m) per

compressor manufacturer specifications.

Rigging

Keep  the  unit  upright  and  lift  unit  using  a  sling.  Use  cardboard  or

padding under the sling, and spreader bars to prevent sling damage to the

unit.  See 

Fig. 2

.  Install  the  unit  so  that  the  coil  does  not  face  into

prevailing  winds.  If  this  is  not  possible  and  constant  winds  above  25

mph  are  expected,  use  accessory  wind  baffle.  See  installation

instructions provided with the accessory kit.

NOTE: 

Accessory  wind  baffles  should  be  used  on  all  units  with

accessory low ambient temperature control.

A07396

Fig. 2 – Lifting Unit with Sling

Clearance Requirements

Single Unit Applications

With coil facing wall

: Allow 6” (152 mm) minimum clearance on coil

side and  coil end  and 20”  (504  mm) minimum clearance on  fan side.

Allow 24” (610 mm) minimum clearance on compressor end for service.

With Fan Facing Wall

: Allow 8” (203 mm) minimum clearance on coil

side and  coil end  and 20”  (504  mm) minimum clearance on  fan side.

Allow 24” (610 mm) minimum clearance on compressor end for service

when units are stacked or there is less than 40” (1016 mm) of clearance

above the unit. If there is 40” (1016 mm) clearance above unit and the

top  panel  is  accessible  for  removal  allow  8”  (203  mm)  minimum

clearance on compressor end for service.

Multi--Unit Applications

: Allow  24”  (610  mm)  minimum  clearance

between fan and coil sides of multiple units. Arrange units so discharge

of one does not enter inlet of another. Allow 24” (610 mm) minimum

clearance on compressor end when units are stacked or there is less than

40” (1016 mm) of clearance above the unit. If there is 40” (1016 mm)

clearance above unit and the top panel is accessible for removal allow 8”

(203 mm) minimum clearance on compressor end for service. 
When two units are installed end-to-end with the coil ends facing each

other, allow 12” (305 mm) minimum clearance between units.

IMPORTANT: 

When installing multiple units, ensure the discharge air

from one unit is not drawn into another unit. When installing single or

multiple units in an alcove, roof well, or partially enclosed area, ensure

there is adequate ventilation to prevent recirculation of discharge air.

CAUTION

!

CUT HAZARD

Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear

appropriate protective clothing and gloves when handling parts.

INSULATION

SUCTION TUBE

LIQUID TUBE

OUTDOOR WALL

INDOOR WALL

LIQUID TUBE

SUCTION TUBE

INSULATION

CAULK

HANGER STRAP

(AROUND SUCTION

TUBE ONLY)

JOIST

1” (25.4 mm) 

 MIN

THROUGH THE WALL

SUSPENSION

PERSONAL INJURY AND/OR EQUIPMENT DAMAGE 

HAZARD

Failure to follow this caution may result in personal injury
and/or equipment damage.
Be sure unit panels are securely in place prior to rigging.

Summary of Contents for bryant 315S

Page 1: ...windows patios decks etc where unit operation sound may disturb customer 3 Ensure that vapor and liquid tube diameters are appropriate for unit capacity 4 Run refrigerant tubes with no bends with cen...

Page 2: ...the accessory kit NOTE Accessory wind baffles should be used on all units with accessory low ambient temperature control A07396 Fig 2 Lifting Unit with Sling Clearance Requirements Single Unit Applica...

Page 3: ...such as a wet cloth Braze joints using a Sil Fos or Phos copper alloy Consult local code requirements Refrigerant tubing and indoor coil are now ready for leak testing This check should include all f...

Page 4: ...uum unit to 500 microns 2 When isolating the unit from the pump the pressure shall not rise above 1500 microns in 10 minutes Final Tubing Check IMPORTANT Check to be certain factory tubing on both ind...

Page 5: ...nimum of 15 minutes before checking charge 2 Measure suction pressure by attaching an accurate gage to suction valve service port 3 Measure suction temperature by attaching an accurate thermistor type...

Page 6: ...4 110 43 108 42 106 41 104 40 102 39 416 114 46 112 44 110 43 108 42 106 41 104 40 427 116 47 114 46 112 44 110 43 108 42 106 41 439 118 48 116 47 114 46 112 44 110 43 108 42 450 120 49 118 48 116 47...

Page 7: ...et and connect leads to control wiring Refer to thermostat Installation Instructions for wiring specific unit combinations see Fig 7 Use No 18 AWG color coded insulated 35 C minimum wire If thermostat...

Page 8: ...tory charge amount and desired subcooling are shown on unit rating plate Charging method is shown on information plate inside unit For TXV use subcooling method For piston use superheat method To prop...

Page 9: ...oastal applications See Owner s Manual for information WARNING PERSONAL INJURY AND OR PROPERTY DAMAGE HAZARD Failure to follow this warning could result in personal injury and or property damage For c...

Page 10: ...out notice and without obligations 10 Training My Learning Center is your central location for professional residential HVAC training resources that help strengthen careers and businesses We believe i...

Reviews: