Smart Manager / Central Remote Control
Installation Manual
EN
5
-EN
Before installation
Confirm all the parts on the list below are supplied.
<Specifications for wiring>
Use the following materials to connect signal lines and power lines (procured on site)
Part name
Part name
Quantity
Remarks
1
Central Controller
1
2
Power unit
1
3
Installation Manual
Owner’s Manual
Network Configuration Guide
2
2 languages
English, French.
Central Remote Control has no Network Configuration
Guide
4
CD-R
1
Smart Manager only
5
Clamp filter
1
Smart Manager only
6
Tie-wrap
1
For fixing the clamp filter, Smart Manager only
7
Screws
8
4 for fixing the central controller
4 for fixing the power unit
8
Brackets
2
For combining the central controller and power unit.
9
Bracket screws
4
For combining the central controller and power unit
No
Line
Type / Wire size / Length
1
For TCC-LINK
2-core shield wire
AWG16 (1.25 mm²), 3200 ft (1000 m) max. (total length including
AWG14 (2.00 mm²), 6500 ft (2000 m) max. air conditioner area)
2
For RS-485
2-core shield wire
AWG16 (1.25 mm²), 1600 ft (500 m) max. (total length)
3
For power
(120 VAC)
UL, CSA approved power supply wire
AWG18 (0.75 mm²), 160 ft (50 m) max.
4
For digital Input / Output connection
2-core wire
AWG22 (0.3 mm²), 320 ft (100 m) max.
5
For power supply
(Between the power unit and central controller)
4-core wire
AWG18 (0.75 mm²), 60 ft (20 m) max.