background image

SMART MANAGER / CENTRAL REMOTE CONTROL

Model name:

BMS-SM1280HTLUL (SMART MANAGER)

BMS-CM1281TLUL (CENTRAL REMOTE CONTROL)

Installation Manual

• Save These Instructions!

ENGLISH

Summary of Contents for BMS-CM1281TLUL

Page 1: ...SMART MANAGER CENTRAL REMOTE CONTROL Model name BMS SM1280HTLUL SMART MANAGER BMS CM1281TLUL CENTRAL REMOTE CONTROL Installation Manual Save These Instructions ENGLISH ...

Page 2: ...cables 9 5 Switches for setting 12 6 Central control address group number setting 16 7 Mode setting for smart manager central remote control 19 8 Zone setting 20 9 Changing return back time temperature settings 21 10 Test run 22 Thank you very much for purchasing this TOSHIBA Carrier Smart Manager Central Remote Control Please read this manual carefully beforehand for proper installation of the Sm...

Page 3: ...quire hospitalization or long term treatment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets Symbols Meaning of Symbols Indicates prohibited items The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol Indicates compulsory mandatory items The actual contents of...

Page 4: ...ne1 Up to 64 units Line2 Up to 64 units Energy monitoring interface Up to 4 units Digital input output interface Up to 4 units Operating temperature humidity 32 to 104 o F 0 to 40 o C 10 to 90 RH no condensation Dimention 4 72 H x 7 09 W x 2 52 D inch 120 H x 180 W x 64 D mm 4 49 H x 6 97 W x 1 97 D inch 114 H x 177 W x 50 D mm Mass 1 77 lb 0 8 kg 1 99 lb 0 9 kg 7 09 180 4 72 120 0 75 19 5 51 140 ...

Page 5: ...he clamp filter Smart Manager only 7 Screws 8 4 for fixing the central controller 4 for fixing the power unit 8 Brackets 2 For combining the central controller and power unit 9 Bracket screws 4 For combining the central controller and power unit No Line Type Wire size Length 1 For TCC LINK 2 core shield wire AWG16 1 25 mm 3200 ft 1000 m max total length including AWG14 2 00 mm 6500 ft 2000 m max a...

Page 6: ...l controller away from a noise source Installing central controller Ø13 64 5 6 1 155 5 59 142 6 77 172 0 7 17 9 0 5 12 7 2 99 76 4 2 106 6 4 25 108 2 56 65 0 33 8 5 0 33 8 5 Panel Base Central Controller box Fix the panel by hooking the nails This hole is provided for penetration of the Central Controller box fixing screw Insert a flat blade screwdriver or the like into the right and left grooves ...

Page 7: ...install the unit in any of the following places Humid or wet place Dusty place Place exposed to direct sunlight Place where there is a TV set or radio within one meter Place exposed to rain outdoors under eaves etc Installation space and maintenance space A side space for connecting through cable inlets and an upper space for maintenance must be reserved before installation The other sides can be ...

Page 8: ... can combine the central controller and power unit using the supplied brackets as follows in order to control them as one unit Combination method Power unit Bracket Panel Fix the brackets and the central controller box together using the screws on the box Fix the power unit to the brackets using the bracket screws ...

Page 9: ...t should be open and insulated Central controller power cable Connect the earth wire securely to the earth terminal on the unit Fix the cable securely with the clamp Power cable Power supply 120V AC Connect the shield wire of the RS 485 communication cable to the FG terminal RS 485 communication cable TCC LINK communication cable 2 TCC LINK communication cable 1 Outdoor Unit Indoor Unit Remote con...

Page 10: ...tatic Non voltage contacts must be compatible with minimal current DC5V 3 mA Pulse width 300 ms or more Wiring length 320 ft 100 m or less N L 1 38 35 2 16 55 1 38 35 2 16 55 1 38 35 0 24 6 Length of stripped power cable Length of stripped TCC LINK communication cable Length of stripped digital Input Output communication wire Attach the supplied clamp filter to the LAN cable Wind the LAN cable aro...

Page 11: ...nd to the central control addresses 1 64 for indoor units respectively See 6 Central control address group number setting A Smart Manager has two TCC LINK communication lines line 1 and line 2 Each line can contain up to 64 groups and 64 zones and 128 groups and 128 zones can be set in total A zone is a control unit consisting of a combination of any indoor units You can make up to 64 zones pairin...

Page 12: ...p 2 Normal DS25 ON 3 Must be set to OFF DS24 ON OFF 4 Must be set to OFF LINE 2 LINE 1 OFF ON Buzzer Control group Selection Line OFF ON Indicate DS23 DS24 ALL groups group 1 16 group 17 32 group 33 48 group 49 64 Control groups Selection DS23 ON OFF SUB MAIN RCU CENTRAL SUB MAIN INHIBIT PERMIT Central Individual Sys con Central RCU change Central Control To avoid an electric shock hazard DO NOT t...

Page 13: ...groups OFF Group 1 16 ON 2 ON Group 17 32 ON 3 ON Group 33 48 ON 4 ON Group 49 64 ON 5 ON 6 Central control remote controller mode selection OFF Central control mode ON Remote controller mode Central control mode The smart manager central remote control is used as the central control device Remote controller mode The smart manager central remote control is used as the remote controller 7 Central c...

Page 14: ...l group selection is used Factory setting All OFF 6 Control group selection enable OFF Normal mode ON Control group selection Set this bit to ON when the control group selection is used To use the control group selection set DS23 2 to 5 and DS24 5 to 6 For details see 7 Mode setting for smart manager central remote control 7 Buzzer OFF With buzzer sound ON Without buzzer sound 8 indication OFF Dis...

Page 15: ... All indoor units will be stopped and cannot be operated with remote control COM DI DI3 COM DI DI3 All stop 2 Normal COM DI DI3 COM DI DI3 All stop 2 Normal Factory setting All OFF 2 Synchronization of zone setting data OFF With synchronization ON Without synchronization This bit specifies whether to perform synchronous communication of zone setting data between Smart Manager Central Remote Contro...

Page 16: ... Set SW30 2 on the interface P C board of the outdoor unit Header unit to ON only for one system and to OFF for others The location of SW30 is shown in the wiring diagram supplied with the outdoor unit Setting central control addresses group numbers Use manual setting from wired remote controller manual setting or automatic setting to set central control addresses A Manual setting from wired remot...

Page 17: ...ing 6 To continue registration repeat steps 3 to 5 7 Press the button to terminate the address setting C Automatic setting Set central control addresses automatically from the Smart Manager Central Remote Control Central control addresses are set automatically in ascending order of unit number 1 Press the button and ZONE button simultaneously for at least 4 seconds CODE No C1 flashes 2 Press the S...

Page 18: ...eck has been completed select CODE No C1 with the SET TEMP or button 2 Press the button 3 The number of group in which the error has been detected flashes Select the flashing group number to be corrected with the GROUP or button 4 Press the button to clear the set incorrect central control address After that set a correct central control address 5 Press the button to terminate the duplicate addres...

Page 19: ... group control mode is available only for one line Multiple group ranges can be specified by the control group setting OFF side Central control mode This Smart Manager Central Remote Control is used as a central control unit Settings with the remote controller are inhibited by the setting of the Smart Manager Central Remote Control ON side Remote control mode This Smart Manager Central Remote Cont...

Page 20: ...een fixed the marks of the group numbers registered in the zone light up 3 Change registration of groups in a zone Register groups in a zone 1 Select the group number to be set with the GROUP or button Pressing the SET TEMP or button skips the group number by 16 or by 16 2 Press the button The registered group number stops flashing and lights still 3 Pressing the button restores the state before t...

Page 21: ... 02 and time setting 30 flash 3 Change the time setting Press GROUP buttons to set the time setting to 045 4 Press the button to determine the data and CODE No stop flashing and stay lit To continuously change other settings repeat steps 2 to 4 above 5 Determine the change Press the button to write the updated data in the memory of the remote controller When the data has completely been written in...

Page 22: ...ach line only main units when group control is performed equals the group number count displayed on the Smart Manager Central Remote Control 4 When these numbers are identical there is no problem If they differ set central control addresses again according to Central Control Address Group Number Setting Also make sure that there is no incorrect wiring Conducting a Test Run for Air Conditioners 1 P...

Page 23: ...Smart Manager Central Remote Control Installation Manual EN 23 EN ...

Page 24: ...DE93929101 ...