![Carrier AQUAZONE VQL Installation, Start-Up And Service Instructions Manual Download Page 7](http://html.mh-extra.com/html/carrier/aquazone-vql/aquazone-vql_installation-start-up-and-service-instructions-manual_2560216007.webp)
7
Rear Return Front Supply
Air Out
BSP
NRP
Return
Air
CAP
B
W
F
D
E
1
1
N
K
3
2
1
U
V
P
5
4
Rear Return Top Supply
NRP
Air Out
BSP
Return
Air
CAP
B
F
D
3
2
1
Air Out
Return
Air
CAP
Front Return Rear Blow
BSP
Air Out
BSP
CSP
Return
Air
CAP
Front Return Top Blow
C
M
L
O
Q
R
(backside)
S
0.75
T
E
C
A
A
0.75
3’ Service
Access
5
4
CSP
CSP
CSP
NOTES:
1. All dimensions in inches [cm].
2. Units require 3
′
[91] clearance for water connec-
tions, CAP, CSP and BSP service access.
3. All side panels are removable except those iden-
tified by NRP (Non-Removable Panel).
LEGEND
BSP
— Blower Service Panel
CAP
— Control Access Panel
CSP
— Compressor Service Panel
NRP
— Non-Removable Panel
CONNECTIONS
Water Inlet
1
1
/
2
″
FPT
Water Outlet
1
1
/
2
″
FPT
Condensate Drain
1
″
FPT
High Voltage Access 1
3
/
8
or
1
3
/
4
″
K.O.
Low Voltage Access
1
/
2
″
K.O.
1
2
3
4
5
Fig. 4A — 50VQL080 Unit Dimensions
UNIT
50VQL
OVERALL
CABINET
DISCHARGE
CONNECTIONS
(Duct Flange [± 0.10 in.])
WATER
CONNECTIONS
ELECTRICAL
KNOCKOUTS
RETURN AIR CONNECTIONS
(Using Duct Flange)
A
Width
B
Depth
C
Height
D
Supply
Width
E
Supply
Depth
F
K
1-Water
Inlet
L
2-Water
Outlet
M
3-Cond-
ensate
N
O
P
Q
R
S
Return
Depth
T
Return
Height
U
V
W
080-100
in.
29.0
41.0
71.5
14.7
15.8
11.2
4.0
7.4
14.5
20.5
2.1
20.6
1.0
3.1
34.8
23.4
25.4
3.1
22.6
120
in.
29.0
41.0
71.5
18.8
16.1
5.8
4.0
7.4
14.5
20.5
2.1
20.6
1.0
3.1
34.8
23.4
25.4
3.1
22.6
Summary of Contents for AQUAZONE VQL
Page 15: ...15 AQUAZONE THERMOSTAT Fig 8A 50HQL072 120 and 50VQL160 With Complete C Controls Typical ...
Page 16: ...16 AQUAZONE THERMOSTAT Fig 8B 50HQL072 120 and 50VQL160 with Deluxe D Controls Typical ...
Page 17: ...17 AQUAZONE THERMOSTAT Fig 9A 50VQL080 120 with Complete C Controls Typical ...
Page 18: ...18 AQUAZONE THERMOSTAT Fig 9B 50VQL080 120 with Deluxe D Controls Typical ...
Page 19: ...19 AQUAZONE THERMOSTAT Fig 10A 50VQL200 300 with Complete C Controls Typical ...
Page 20: ...20 AQUAZONE THERMOSTAT Fig 10B 50VQL200 300 with Deluxe D Controls Typical ...