52
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)
LEGEND
SCREEN NAME
PASSWORD
LEVEL
POINT NAME
EDITABLE
RANGE
DEFAULT
NOTES
Configuration
Set Points
User/Admin
Password level
access
Occupied Heating
X
40 - 90 F
72 F
Defines the Occupied
Heating Set Point
Occupied Cooling
X
55 - 99 F
76 F
Defines the Occupied
Cooling Set Point
Unoccupied Heating
X
40 - 90 F
55 F
Defines the Unoccupied
Heating Set Point
Unoccupied Cooling
X
55 - 99 F
90 F
Defines the Unoccupied
Cooling Set Point
Effective Heating
Set Point
X
0 - 10
F
Takes into effect bias (maximum
allowable set point deviation)
Effective Cooling
Set Point
X
0 - 10
F
Takes into effect bias (maximum
allowable set point deviation)
Optimal Start
Uses historical data to calculate
ramp up time so as to be at set point
at occupied/unoccupied time
Occupied RH
Set Point
X
0 - 100%
65%
Defines the control set point used
during occupied periods (Viewable
only if Humidity Sensor = Installed/
Determines when to start
Dehumidification when occupied)
Unoccupied RH
Set Point
X
0 - 100%
90%
Defines the control set point used
during unoccupied periods
(Viewable only if Humidity Sensor =
Installed/Determines when to start
Dehumidification when unoccupied)
DCV CTRL Start
Set Point
X
0 - 9999 ppm
500 ppm
Defines the control set point used to
start increasing ventilation during
occupied periods (Viewable only if
Ventilation DMP Type = DCV)
DCV Max CTRL
Set Point
X
0 - 9999 ppm
1050 ppm
Defines the control set point
used to define where the ventilation
will reach its maximum limit during
occupied periods (Viewable only if
Ventilation DMP Type = DCV/Used
to determine DCV ending control
point)
Configuration
Schedule
Weekly Schedule
User/Admin
Password level
access
Start Time
X
00:00 - 23:59
06:00
Defines the start time for an
occupied period
End Time
X
00:00 - 24:00
18:00
Defines the ending time of an
occupied period
Mon
X
No/Yes
Yes
Determines if this day is included
in this schedule
Tue
X
No/Yes
Yes
Determines if this day is included
in this schedule
Wed
X
No/Yes
Yes
Determines if this day is included
in this schedule
Thur
X
No/Yes
Yes
Determines if this day is included
in this schedule
Fri
X
No/Yes
Yes
Determines if this day is included
in this schedule
Sat
X
No/Yes
No
Determines if this day is included
in this schedule
Sun
X
No/Yes
No
Determines if this day is included
in this schedule
Configuration
Schedule
Exception
Schedules 1 - 12
User/Admin
Password level
access
Start Month
X
0 - 12
0
Defines the start month of this
hoilday schedule
Start Day
X
0 - 31
0
Defines the start day of this holiday
schedule
Start Time
X
00:00 - 23:59
0:00
Determines the start time for this
schedule
End Month
X
0 - 12
0
Defines the month to end this
hoilday schedule
End Day
X
0 - 31
0
Defines the day to end this holiday
schedule
End Time
X
00:00 - 24:00
0:00
Determines the time to end this
schedule
BAS —
Building Automation System
DCV —
Demand Controlled Ventilation
ECM —
Electronically Commutated Motor
IAQ
—
Indoor Air Quality
OAT
—
Outdoor Air Temperature
RH
—
Relative Humidity
SAT
—
Supply Air Temperature
SPT
—
Space Temperature
TPI
—
Third Party Integration